Compiled Approved Plans 51983.3225.11

of 50

Plans and drawings: the text below has words only, no drawings.

Log in to see the plans as drawn

Original PDF page 1, section 1. The text section number identifies this passage in the reader.

           GENERAL SPECIFICATION                                                                                                                                     Construction Notes
                                                                                                                           Timber Frame: Framing to be built in accordance with AS 1684 Termite protected timbers shall be used on all framing
   ALL BUILDING WORK TO BE CARRIED OUT TO THE BUILDING CODE OF AUSTRALIA & THE BUILDING ACT 1975.                          Approved type flashing & sarking to be attached between cladding & frame along with slab & frame to prevent moisture getting to the frames
   BUILDER TO SUPPLY FOOTPATH PROTECTION & REQUIRED SIGNS TO COMPLY TO WORKPLACE HEALTH & SAFETY ACT.
   PRINCIPLE CONTRACTOR TO HAVE A SITE SPECIFIC WORKPLACE HEALTH & SAFETY MANAGEMENT PLAN TO COMPLY WITH                   All wet areas to be made waterproof or resistant to comply to AS 3740 & BCA 3.8.1
   GOVERNMENT REGULATIONS TO BE KEPT ONSITE & GIVEN TO ALL CONTRACTORS                                                     Linings used shall be approved for use in wet areas & shall be fixed in strict accordance
   WRITTEN DIMENSIONS TO TAKE PRECEDENCE OVER SCALE.                                                                       with Manufactures specifications. Wet Areas include Laundry & Bathroom
   BUILDER TO VERIFY ALL SET-OUT DIMENSIONS PRIOR TO PLACEMENT OF CONCRETE
   BUILDING MUST COMPLY WITH THE NATIONAL CONSTRUCTION CODES (BCA) & THE QUEENSLAND HOME BUILDING CODE                     All walls to be checked to ensure they are fixed correctly, straight & plumb prior to fixing plasterboard or interior lining
   ALL CONCRETE SLABS & FOOTINGS TO COMPLY WITH (AS 2870)                                                                  Plasterboard or interior linings to be fixed to dry frames in strict compliance with manufactures details. Setting of plasterboard to be done in strict
   ALL STRUCTURAL TIMBERS TO COMPLY WITH NATIONAL TIMBER FRAMING CODES (AS1684.2 &AS1720) & CONSTRUCTION TIMBERS           compliance with manufactures specifications, Sanded to provide a flat smooth finish
   IN QUEENSLAND (CTIQ)
   TERMITE PROTECTION TO (AS3660.1) CERTIFICATES TO BE SUPPLIED & GIVEN TO CERTIFIER                                       Painting: Paints & application to comply to AS 2311 Min 3 coat application system to be used
   ALL WET AREAS TO BE WATERPROOFED, INTERNAL WATERPROOFING TO COMPLY TO (AS 3740) AS IN BCA 3.8.1                         Substrate to be clean & dry correct type sealers & primers to be used for substrate
   ALL GLASS TO COMPLY TO (AS 1288) WINDOWS & DOORS ALONG WITH SCREENING OR SECURITY SCREENS TO COMPLY TO                  If paint is sprayed on then a back roll should be done between coats & after final coat
   RELEVANT REGULATIONS                                                                                                    Mould resistant paint to be used in Bathrooms, Ceilings to have approved ceiling paint applied & be a matt finish
   PLASTERBOARD TO (AS 2589), PAINTING TO COMPLY TO (AS 2311) TILING TO COMPLY TO (AS 3958)
   STAIRS TO COMPLY TO BCA 3.9.1 BALUSTRADE TO COMPLY TO BCA 3.9.2,                                                        Concrete slabs & footings to be poured AS per Plans & in accord with AS 2870
   WIND CLASSIFICATION (N3).                                                                                               Slabs shall be finished to suit floor coverings

                                                                                                                           All external windows & doors to have appropriate flashing & seals fitted to prevent water getting into building or
                                                                                                                           to the frame work



                                                                                                                   -
                                                                                                          NOOSA COUNCIL
                                                                                                         APPROVED PLANS
                                                                                                     51983.3225.11 27 APR 2018




Client: Peter & Lois Lumley Unit 21/30 Hastings St. The Hastings Noosa Heads Wind Classification N3                                                                                              Mobile: 0407 693 018                                Date     26/04/2018 5:52:54 AM
                                                                                                                       ACCOLADE Building Designs                                                                                                    Drawn by: S.Horn Drawn for A3 Sheet
RPD: Lot 21 on GTP 1154         Parish: Weyba       County: March       Site Area : 97 m²                                   Proprietor: Steven Horn                                   Email: [email protected] Project Number
                                                                                                                                                                                                                                                                                     0817LPL
Proposed Partial Enclosure of Ground Level Under Existing Unit                                                                 QBSA Lic. 54806                                        Issue Date            25 - April - 2018                            Sheet No. 1          of     6
Full text of sections 2 to 18 (of 50)

Section 2

                                                                                                                                                                                                                                                                               Hastings           Street


                       Hastings             Street




                                                                                                  Lot 22
                                                                                                                 270° 00' 00"

                                                                                                                   6.300 m




                                                                          0° 00' 00"




                                                                                                                                    0° 00' 00"
                                                                                        8.200 m




                                                                                                                                                 2.900 m
                                                                                                                                                                                         270° 00' 00"
                                                     Main Driveway

                                                                                                                                                                                          8.500 m
                                                                                                           Existing Residence




                                                                                                                                                     Existing Balcony
                                                                                          Lot 21




                                                                                                                                                                                                                180° 00' 00"
                                                                                                                                                                                       97 m²




                                                                                                                                                                                                                               5.300 m




                                                                                                                                                                                                                                                                                                                     Proposed alterations on Lot 21
                                                                                                                                                                        270° 00' 00"

                                                                                                                                                                                                  -
                                                                                                                                                                         14.800 m
                                                                                                                                                                              NOOSA COUNCIL
                                                                        Lot 20




                                                                                                                                                                             APPROVED PLANS
                                                                                                                                                                         51983.3225.11 27 APR 2018




              NORTH




                                  Noosa                        Parade




  Real Property Description
                                                                                                                                                                                                                                                            Noo
                                                                                                                                                                                                                                                                sa P
       Lot No. 21 on GTP. 1154                                                                                                                                                                                                                                      a   rade
       Parish: Weyba
       County: March
       Locality: Noosa Heads
       Address: Unit 21 The Hastings
                 Hastings St..
       Site Area: 97 m²



Client: Peter & Lois Lumley Unit 21/30 Hastings St. The Hastings Noosa Heads Wind Classification N3                                                                                                                                             Mobile: 0407 693 018        Date     26/04/2018 5:52:56 AM
                                                                                                                                                                                                        ACCOLADE Building Designs                                           Drawn by; S.Horn Drawn for A3 Sheet
RPD: Lot 21 on GTP 1154                   Parish: Weyba                                County: March                    Site Area : 97 m²                                                                   Proprietor: Steven Horn      Email: [email protected]
                                                                                                                                                                                                                                                                                          Project Number                                              0817LPL
Proposed Partial Enclosure of Ground Level Under Existing Unit                                                                                                                                               QBSA Lic. 54806             Issue Date:   25 - April - 2018                  Scale      1 : 100 Sheet No. 2                               of 6

Section 3

                                                                                                                                                                         5480                                                                                               2100

                                                                                                                                          2785                                                 1900                        705                                             2190                             Decking boards to be replaced with
                                                                                                                  90                                                     70                                           70          90                                                           70           Scyon Secura Exterior Flooring (Or Similar)
                                                                                                                                           2625                                                                            635                                             2030                             Waterproofed & Coated with approved coloured coating
                                                                                                                                                                                                                                                                                                            Existing balustrade to be made 1000mm High
                                                                                                                                                                                                                                                                                                            & to comply with BCA 3.9.2
                                                                                                                                                                                                                                                                                                                                                                                                                                                                        Existing supports
                                                                                                                   Builder to determine all dimensions on site to coincide with existing structure

                                                                                                                                                          Existing 90 mm SHS posts                                                                                                                                                                                                                                                   Existing 1st Floor

                                                                                                                                                   Existing 100x75 RHS bracing




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                               Existing Deck
                                                                                                                                                                                                                                                                                                                                                                                                                                                                        WC




                                                                                                                                                                                                                                       Existing 100x75 RHS bracing
                                                                                                                                                                                                                                                                                                                                                                                           Existing Door
                                                                                                                                                                                                                                                                                                                                                                                         To be removed
                                                                                                                                                                                                                                                                                     Fire Rated Wall                                                                                    walls made good
                                               Driveway


                                                                                                                                                                                                                                                                                     FRL 60/60/60




                                                                                                                                                                                                                                                                                                                                                                           2440
                                                                                                                                                                                                                                                                                                                                                                                                                            Existing Stairs
                                                                                                                                                              Existing Carport Slab                                                                                                     1
  3290




                                                                                                                                                                                                                                                                                        5                Ply Bracing 4 mm (F27)                                                                                                                                         Existing supports

                                                                                                                                                                                                                                                                                                         M12 Tiedown Rods                                                                                                                         1st Level
                                                                                                                                                                                                                                                                                                                                                                                                                                 2                   1 : 100




                                                                                                                                                                                                                                                                                                                                                                      90
                                                                                                                              W1 Between Bench top & wall cabinets                       Louvers to be full blades only
                                                                                                                                       Height to contain full 102 lvrs




                                                                                                                                                                                                                                                                                                                                                               600
                                               Main




                                                                                                                                                                                                                                                                                                                                                   850
                                                                                                                                close off wall cabinets to upper floor                                                                                                    Cupboard
                                                                                                                                                  W1                                                                                                                                                                                                                                                                                           5480                                                          2065




                                                                                                                                                                                                                                                                                                                                                          90
         90




                                                                                                                                                                                   Alcove slab level with carport                                                                                                                                                                                                                 Existing 90 mm SHS posts
                      600




                                                                                                                                                                                                                                                                                                                                                   510
                                                                                                                                                                                   Water not to pond in Alcove
                                                                                                                       BRM
                                                                                                                                                  TUB                                          D1
                                                                                                                                    WM                          Drier                                                                                                                                                                                                                                                                   Existing 100x75 RHS bracing
                 70




                                                                                                                                                                                                                                                                                                                                                          70
                                                           A




                                                                                                                                                                                                                                                                                                                                                                                                                                                                             Existing 100x75 RHS bracing
                                                                                                                                                                                                                                                                                                                   Cladding to match upper floor
                                                           5                                                                                                                        Proposed Entrance




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   Driveway
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            2435
                                                                                                                           Remove Existing Slab & replace
              2300




                                                                                                                                                                          770




                                                                                                                                                                                                                                                                                                                                                                           4230
                                                                                                                                   Laundry/Bathroom
                                                                                        Mechanical Exhaust vent




                                                                                                                                                                                                                                                                                                                                                                                                                                        Existing Carport Area




                                                                                                                                                                                                                                                                                                                                                               3450
                                                                                                                                                                                                                                                                                                    W4
  3380




                                                                                                                                                                                   M12
                                                                                                                                                                                                                    Proposed Entry Storeroom
                      2620




                                                                                                                                                                                                                                                                                                                                                   2620
                                                                                                                        900x900                                                                                                                                                                                                                                                                                                                                                                            Existing 90 mm
                                                                                                                                                                                   PB


                                                                                                                          SHR




                                                                                                                                                                                                                                                                                                                                                                                              6670
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                SHS posts

                                                                                                                                                                                   M12                                                                                                                                                                                                                                       Existing
         90




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   Cantilevered Deck Over
                                                                                                                                                                                                                                                                                                                                                                                                                             Laundry
                                                                                                                                                                                                                                                                                                    M12




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            4235
                                                                                                                                                                                                                                                                                        PB
                                                                           New door




                                                                                                                                    Remove Existing Slab & replace                                                                                                                                                                                                                                                             6.1 m²




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   Main
              810




                                                                                                                                                                              up
                                                                             D2




                                                                                                                       Storage under stairs                                                                                                                                        PB




                                                                                                                                                                                                                                                                                                                                                                  90
         90




                                                                                                                                                                                                                                                      M12
                                                               door to match cladding




                                                                                                                             Replace existing staircase                  W2                                                           M12                            W3                                                                                                                                              Existing Open Stairs              up
                                                                                                                                                                                Laundry/Bath floor White Gloss Tiles                     -
                                                                                                                                                                                                                                Bifold door to be lockable
                                                                                                                                                                                Main Floor Painted concrete (Light Gray colour)
                                                                                                                                                                                                                            NOOSA
                                                                                                                                               Window to be as high as possible                                                 StorageCOUNCIL
                                                                                                                                                                                                                                         for Owners
                                                                                                                                               Builder to determine on site     To Owners selection                                                                                                                                                                                                                                  Existing 90 mm SHS posts
                                                                                                                                                                                                                                APPROVED PLANS                                                                                                                                                                                                 5480
                                                                                                                                                                                                                       51983.3225.11 27 APR 2018
                                                                                                                                                                                    Additional Lower floor addition to be clad with Shadow Clad to match existing external walls & painted the same colour
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                             2065

                         Ground Floor Plan                                                                                                                                                             All dimensions to be confirmed on site to coincide with existing residence
         1                   1 : 50
                                                                                                                                                                                    Builder Note : Some existing walls in existing laundry to be framed &
                                                                                                                                                                                                  lined as they may be cladding attached to minimal framing                                                                                                                                                 Existing Ground Floor Plan
                                                                                                                                                                                                                                                                                                                                                                                             3               1 : 100
                                                                                                                                                                                                  Window Schedule

                                                                                                                                  Mark Height Width                  Comments                         Location                                 Lintels                                       Jamb Studs                                                                                                                                     Door Schedule
     20.2 m²           Additional Enclosed Area :
      6.1 m²               Existing Laundry Area:                                                                                 W1       541         610           Louvers/Obs.                   Laund/Bath                       70x35 MGP 12                                                   2
     26.3 m²          Total enclosed Lower Floor:                                                                                 W2       900         600           Double Hung                     Ent/Stairs                      70x35 MGP 12                                                   2                                                                             Mark Height Width                  Comments                         Location                      Lintel                                                   Jamb Studs
     45.4 m²               Total Area Inc. Carport                                                                                W3       600        1200            Alum Slider                Store/Mud Room                      70x35 MGP 12                                                   2
                                                                                                                                                                                                                                                                                                                                                                                   D1        2100          1800       Alum Sliding                      Entry          120x35 Smart LVL 15                                                                     2
                                                                                                                                  W4       600        2100            Alum Slider                Store/Mud Room                  2/120x35 Smart LVL 14                                              2
                             Upper Floors not Noted                                                                                                                                                                                                                                                                                                                                D2        1500          620          External                  Store under Stairs      70x35 MGP 12                                                                         2
                                                                                                                                  W5       1171        610              Louvers                  Store/Mud Room                      70x35 MGP 12                                                   2




Client: Peter & Lois Lumley Unit 21/30 Hastings St. The Hastings Noosa Heads Wind Classification N3                                                                                                                                                                                                                                                                                                               Mobile: 0407 693 018                                    Date                                          26/04/2018 5:52:56 AM
                                                                                                                                                                                                                                                                                   ACCOLADE Building Designs                                                                                                                                                             Drawn by: S.Horn Drawn for A3 Sheet
RPD: Lot 21 on GTP 1154                                   Parish: Weyba                                                            County: March                     Site Area : 97 m²                                                                                                          Proprietor: Steven Horn                                                                              Email: [email protected] Project Number
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   0817LPL
Proposed Partial Enclosure of Ground Level Under Existing Unit                                                                                                                                                                                                                                     QBSA Lic. 54806                                                                                   Issue Date           25 - April - 2018                                                                Sheet No. 3                                    of       6

Section 4

                                                                                                                                                                                                               Existing Support to balcony




                                                                                                                                                                                                                                                                                                it
                                                                                                                      it




                                                                                                                                                                                                                                                                                              Un
                                                                                                                    Un
                                                                                                                                                    Balustrade or privacy screens




                                                                                                      in g




                                                                                                                                                                                                                                                                                             ing
                                                                                                                                                    to Owners selection to be &




                                                                                                   is t




                                                                                                                                                                                                                                                                                         is t
                                                                                                 Ex
                                                                                                                                                    approved by body corporate




                                                                                                                                                                                                                                                                                       Ex
                                                                                                                                                    Existing Balcony
                                                                                                                                                    to be made waterproof                                                                        Existing
                                                                                                                                                                                                                                                 Balcony
                  Existing 100x75 RHS
                  Bracing to remain
                  framing to be fixed to                                                                                                 W3
                  RHS & clad over                                                                                                                                                                                                                                                                                               Existing 100x75 RHS
                                                                                            W2                                                                                                                                                              W5
                                                                                                                                                                                                               Proposed wall                                                                                                    Bracing
                                                                                                                                Proposed wall                                                                                                                                     D1                   W1
                                                                                                                                                    Window to fit between existing bracing
                  Existing SHS into frame


                                                                               Cladding to match existing upper floors
                                                                                                                                                                                                                                                                  Existing Carport


                                                    South Elevation                                                                                                                                                                                              North Elevation
                                     1                 1 : 100                                                                                                                                  -
                                                                                                                                                                                                                                                    2
                                                                                                                                                                         NOOSA COUNCIL                                                                            1 : 100
                                                                                                                                                                        APPROVED PLANS
                                                                                                                                                                    51983.3225.11 27 APR 2018




                                                                                                                                                                                             East Elevation                                                       Exist                                  Exist

                                                                                                                                                                               3             1 : 100
                                                                       it
                                                                     Un




                                                                                                                                                                                                                                                                                         it
                                                                                                                                                                                                                                                                                       Un
                                                                    ing




                                                                                                                                                                                                                                                                                ing
                                                                is t




                                                                                                                                                                                                                                                                            is t
                                                              Ex




                                                                                                                                                                                                                   Existing Support to balcony




                                                                                                                                                                                                                                                                          Ex
                                                                                                                                                                                                                                                                          Exist             Exist
                                                                                                                                                                                                                   Existing Balcony to be
                                                                                                                                                                                                                   made waterproof


                                                                                                                                                    West Elevation
                                                                                                                                                4                                                                                                                W4                                                       Existing 100x75 RHS
                                                                                                                                                                                                                                                                                                                          Cross bracing
                                                                                                    Proposed wall
                                                                            Existing wall




                                                                                                                                                    1 : 100
                                                                                                                            Door under steps
                                                                                                                            Height to suit
                                                                                                                            Clad to match                                                                                                                                                              Existing Carport
                                           Existing Carport


Client: Peter & Lois Lumley Unit 21/30 Hastings St. The Hastings Noosa Heads Wind Classification N3                                                                                                                                                                 Mobile: 0407 693 018        Date     26/04/2018 5:52:57 AM
                                                                                                                                                                                              ACCOLADE Building Designs                                                                         Drawn by; S.Horn Drawn for A3 Sheet
RPD: Lot 21 on GTP 1154                Parish: Weyba                      County: March                                    Site Area : 97 m²                                                           Proprietor: Steven Horn                               Email: [email protected]
                                                                                                                                                                                                                                                                                                                                          Project Number                0817LPL
Proposed Partial Enclosure of Ground Level Under Existing Unit                                                                                                                                          QBSA Lic. 54806                                      Issue Date:                            25 - April - 2018                     Scale   1 : 100 Sheet No. 4    of 6

Section 5

                                                                                                                                                                                                     NOTES:

unit 5, the hastings, noosa parade
                 lot 5 on GTP1154
                                                                                                                                                                                                     1. ALL CONSTRUCTION TO BE IN ACCORDANCE WITH THE AUSTRALIAN


                                                                                       TO NOOSA PARADE
                                                                                                                                                                                                     DOMESTIC BUILDING CODE.
                                                                                                                                                                                                     2. ALL TIMBER FRAMING TO BE IN ACCORDANCE WITH AS 1684.2 2010
                                                                                                                                                                                                     RESIDENTIAL TIMBER FRAMING MANUAL.
                                                                                                                                                                                                     3. PINE FRAMING TO BE MINIUMUM STRESS GRADE MGP 10/MGP12
                                                                                                                                                                                                     4.HARDWOOD FRAMING TO BE MINIMUM STRESS GRADE F14 & MINIMUM
                                                                                                                                                                                                     JOINT GROUP J2.
                                                                                          -                                                                                                          5. TIMBER FOR TRUSSES TO BE MINIMUM JOINT GROUP JD4.
                                                                                                                                                                                                     6. TRUSSES TO BE FIXED IN ACCORDANCE WITH MANUF.
                                                                                  APPROVED PLAN                                                                                                      SPECIFICATIONS ALL OTHER FIXINGS TO BE IN ACCORDANCE WITH
                                                                                                                                                                                                     AS 1684.2 2010
                                                                                    51983.3225.10                                                                                                    7.LAMINATED BEAM SIZES BASED ON HYNEBEAM SPAN TABLES WHERE

                                                                                  NOOSA COUNCIL                                                                                                      OTHER BRANDS ARE USED, SIZES TO BE CONFIRMED WITH
                                                                                                                                                                                                     MANUFACTURERS SPECIFICATIONS.




                                                       180d00'30"
                                                                                   1 AUGUST 2017                                                                                                     8. ALL DIMENSIONS TAKE PRECEDENCE OVER SCALES
                                                                                                                                                                                                     9. BUILDER AND TRADES ARE TO CONFIRM ALL MEASUREMENTS, DETAILS




                                                       129.960
                                                                                                                                                                                                     AND SPECIFICATIONS PRIOR TO SETOUT AND ORDERING OF MATERIALS
                                                                                                                                                                                                     10. ANY ERRORS ARE TO BE ADDRESSED TO THE DESIGNER AS NO
                                                                                                                                                                                                     RESPONSIBILITY WILL BE TAKEN AFTER CONSTRUCTION HAS COMMENCED
                                                                                                                                                                                                     11. ALL TRADES ARE TO CONFORM WITH THE CURRENT AUSTRALIAN
                                                                                                                                                                                                     STANDARDS RELATING TO HIS OR HER OWN WORK
                                                                                                                                                                                                     12. TERMITE PROTECTION TO BE PROVIDED AS PER AS 3660.1.2000



                                                                                                                                                                                                     DOMESTIC SMOKE ALARMS:
                                                                                                                                                                            unit 7                   1. ALL BEDROOMS AND HALLWAYS ARE TO BE INSTALLED WITH
                                                                                                                                                                                                     PHOTO ELECTRIC SMOKE ALARMS IN ACCORDANCE WITH BUILDING FIRE
                                                                                                                                                                                                     SAFETY LEGISLATION AMENDMENT REGULATION 2016
                                                                                                                                                                                                     2. SMOKE ALARMS MUST BE POSITIONED IN ACCORDANCE WITH AS
                                                                                                                                                                                                     1670.6 - 1997 FIRE DETECTION, WARNING, CONTROL AND INTERCOM
                                                                                                                                                                                                     SYSTEMS.
                                                                                                                                                    unit 6                                           3. DEVICES MUST BE EITHER INTERCONNECTED OR HARD WIRED
                                                                                                                                                                                                     (EXISTING DWELLINGS ONLY) THAT CANNOT BE
                                                                                                                                                                                                     REMOVED FROM DEVICE




                                                                                                                                                                                 5050
                                                                                                                                                                    3000




                                                                                                                                                                                          70.770
                                                                                                                                                                                                   NOTE: SMOKE ALARMS TO BE INSTALLED IN ALL HALLWAYS AND BEDROOMS




                                                                                                                                                                                          0d0'
                                                                                                                                                                                                   TO EXISTING RESIDENCE


                                                                                                                                                                           (PROPOSED
                                                                                                                                                                           BUILD IN)




                                                                                                                                           4800
                                                                                                                                                                                         2500
                                                                                                                                                             3420


                                                                                                                                                                           unit 5

                                                                                                                                           unit 4               5420




                                                                                                                                                                                        46.300
                                                                                                                                                                                        8d57'
                                                                           TO HASTINGS STREET




                                                                                                                                                                                                                                                        site plan
                            PROPOSED:                  CLIENT: PAUL TEYCHENNE BUILDER: MICK GARDNER MANDY'S DESIGN & DRAFTING SHEET: 1 of 4 DATE:                                                                                     ISSUE NO:
                           BUILD IN GROUND+ALTERATIONS                        PH: 0414 697 882      PH: 0403 481 474          SCALE: 1:100 JULY 2017                                                                                  A
                              NOTE: THESE DRAWINGS TO BE READ IN CONJUNCTION   NOTE: BUILDER TO CONFIRM SITING AND DIMENSIONS BEFORE CONSTRUCTION
                              WITH ENGINEERS DRAWINGS                          RESPONSIBILITY LIES THERE WITH

Section 6

                                                                                                                                                                                                                                                                                                          NOTES:


unit 5, the hastings, noosa parade
                 lot 5 on GTP1154
                                                                                                                                                                                                                                                                                                          1. ALL CONSTRUCTION TO BE IN ACCORDANCE WITH THE AUSTRALIAN
                                                                                                                                                                                                -                                                                                                         DOMESTIC BUILDING CODE.
                                                                                                                                                                                                                                                                                                          2. ALL TIMBER FRAMING TO BE IN ACCORDANCE WITH AS 1684.2 2010
                                                                                                                                                                                        APPROVED PLAN                                                                                                     RESIDENTIAL TIMBER FRAMING MANUAL.
                                                                                                                                                                                                                                                                                                          3. PINE FRAMING TO BE MINIUMUM STRESS GRADE MGP 10/MGP12
                                                                                                                                                                                          51983.3225.10                                                                                                   4.HARDWOOD FRAMING TO BE MINIMUM STRESS GRADE F14 & MINIMUM

                                                                                                                                                                                        NOOSA COUNCIL                                                                                                     JOINT GROUP J2.
                                                                                                                                                                                                                                                                                                          5. TIMBER FOR TRUSSES TO BE MINIMUM JOINT GROUP JD4.
                                                                                                                                                90                                       1 AUGUST 2017                      90
                                                                                                                                                                                                                                          3710
                                                                                                                                                                                                                                                             70
                                                                                                                                                                                                                                                                  960
                                                                                                                                                                                                                                                                        70
                                                                                                                                                                                                                                                                             1660
                                                                                                                                                                                                                                                                                        90
                                                                                                                                                                                                                                                                                                          6. TRUSSES TO BE FIXED IN ACCORDANCE WITH MANUF.
                                                                                                                                                                                                                                                                                                          SPECIFICATIONS ALL OTHER FIXINGS TO BE IN ACCORDANCE WITH
                                                                                                                                   2270              830
                                                                                                                                                                                                                                                                                                          AS 1684.2 2010
                                                                                                                                                                                                                                 1209DH                        0906AW                                     7.LAMINATED BEAM SIZES BASED ON HYNEBEAM SPAN TABLES WHERE
                                                                                                                                                                                                                                                                                                          OTHER BRANDS ARE USED, SIZES TO BE CONFIRMED WITH




                                                                                        existing internal space
                                                                                                                                                                                                                                                                                                          MANUFACTURERS SPECIFICATIONS.




                                                                                                                             880
                                                                                                                                                                                                                                          proposed pantry                                                 8. ALL DIMENSIONS TAKE PRECEDENCE OVER SCALES
                                                                                                                                                                                                                                                                                                          9. BUILDER AND TRADES ARE TO CONFIRM ALL MEASUREMENTS, DETAILS



                                                                                                  2520
                                                                                                                             EXIST                                                                                                                                                                        AND SPECIFICATIONS PRIOR TO SETOUT AND ORDERING OF MATERIALS
                                                                                                                                          840
                                             existing cross bracing




                                                                                                                             L'DRY                                                                                                                                                                        10. ANY ERRORS ARE TO BE ADDRESSED TO THE DESIGNER AS NO
                                                                                                                                                                                                                                                                                                          RESPONSIBILITY WILL BE TAKEN AFTER CONSTRUCTION HAS COMMENCED
                                                                                                                                                                                                                                                                                                          11. ALL TRADES ARE TO CONFORM WITH THE CURRENT AUSTRALIAN
                                                                                                                                                     UP

                                                                             EXISTING
                                                                                                                                                                                                                                    existing first floor                                                  STANDARDS RELATING TO HIS OR HER OWN WORK
                                                                                                                                                                                                                                                                                                          12. TERMITE PROTECTION TO BE PROVIDED AS PER AS 3660.1.2000
                                                                             CARPORT
                                                                                                                                                                                                                                                   close off opening, remove wc and
                                                                                                                                                                                                                                                        vanity to make as pantry and                      DOMESTIC SMOKE ALARMS:




                                                                                                                                                                                                                   2109DH
                                                                                                                                                                                                                                                              entry from kitchen side                     1. ALL BEDROOMS AND HALLWAYS ARE TO BE INSTALLED WITH
                                                                                            existing 90x90shs posts                                                                                                                                                                                       PHOTO ELECTRIC SMOKE ALARMS IN ACCORDANCE WITH BUILDING FIRE
                                                                                                                                                                                                                                                                                                          SAFETY LEGISLATION AMENDMENT REGULATION 2016
                                                                                                                                                                                                                                                       2121OXSD                                           2. SMOKE ALARMS MUST BE POSITIONED IN ACCORDANCE WITH AS
                                                                                                                                                                                                                                                                                                          1670.6 - 1997 FIRE DETECTION, WARNING, CONTROL AND INTERCOM

                                     Existing Ground                                                                                                                                                    Existing First Floor                                balcony                                       SYSTEMS.
                                                                                                                                                                                                                                                                                                          3. DEVICES MUST BE EITHER INTERCONNECTED OR HARD WIRED
                                                                                                                                                                                                                                                                                                          (EXISTING DWELLINGS ONLY) THAT CANNOT BE
                                                                                                                                                                                                                                                                                                          REMOVED FROM DEVICE

                                                                                                                                                                                                                                                                                                          NOTE: SMOKE ALARMS TO BE INSTALLED IN ALL HALLWAYS AND BEDROOMS
                                                                                                                                                                                                                                                                                                          TO EXISTING RESIDENCE




                                        90                                                                        70         70                 90
                                                                              3710                                     960            1660
                                                                      existing windows to remain
                                                                       0906AW            0906AW 0906AW




                                                               divide bathroom                                    close off opening
                                                              make as 2 rooms
                                                                      remove existing
                                                                      cupboard
                                                                         bed                                                 bed
                                                                                                                                                           Elevation 1 - a




                                                                                                                                                                             02 of 04
                                                                                   2109DH                   2109DH

                 Existing Upper Floor




                                                                                                                                                                                                                                                                                                                                                            existing floor
                                                             Elevation 2 - a

                                                                                                                                                                                                existing carport
                                                                        02 of 04
                                                                                                                                                                                                                                                                                             Elevation 1 - a
                                                                                                                                                                                            Elevation 2 - a
                            PROPOSED:                  CLIENT: PAUL TEYCHENNE BUILDER: MICK GARDNER MANDY'S DESIGN & DRAFTING SHEET: 2 of 4 DATE:                                                                                                                                                                                         ISSUE NO:
                           BUILD IN GROUND+ALTERATIONS                        PH: 0414 697 882      PH: 0403 481 474          SCALE: 1:100 JULY 2017                                                                                                                                                                                      A
                              NOTE: THESE DRAWINGS TO BE READ IN CONJUNCTION                                                                 NOTE: BUILDER TO CONFIRM SITING AND DIMENSIONS BEFORE CONSTRUCTION
                              WITH ENGINEERS DRAWINGS                                                                                        RESPONSIBILITY LIES THERE WITH

Section 7

                                                                                                                                                                                                                                                                                                                                            NOTES:


unit 5, the hastings, noosa parade
                 lot 5 on GTP1154
                                                                                                                                                                                                                                                                                                                                            1. ALL CONSTRUCTION TO BE IN ACCORDANCE WITH THE AUSTRALIAN
                                                                                                                                                                                                                                                                                                                                            DOMESTIC BUILDING CODE.
                                                                                                                                                                                                                                                                                                                                            2. ALL TIMBER FRAMING TO BE IN ACCORDANCE WITH AS 1684.2 2010
                                                                                                                                                                                                                                                                                                                                            RESIDENTIAL TIMBER FRAMING MANUAL.




                                                         elevation C
                                                                                                                                                                                                                                                                                                                            04 of 04
                                                                                                                                     90                           90         90                                                                                                                                                             3. PINE FRAMING TO BE MINIUMUM STRESS GRADE MGP 10/MGP12
                                              04 of 04                                                                                           2270                  830                                                                                                                                                                  4.HARDWOOD FRAMING TO BE MINIMUM STRESS GRADE F14 & MINIMUM
                                                                                                                                                                                                                                                                                                                 01        elevation B      JOINT GROUP J2.
                                                                                                                                                                                                                                                                                                                                            5. TIMBER FOR TRUSSES TO BE MINIMUM JOINT GROUP JD4.
                                                                                                                                                           bath/l'dry                                                                                                                                                                       6. TRUSSES TO BE FIXED IN ACCORDANCE WITH MANUF.
                                                                                                                                                01                store under                                                                                                                                                               SPECIFICATIONS ALL OTHER FIXINGS TO BE IN ACCORDANCE WITH
                                                                                                                                                                                                                                                                  1209DH                                                                    AS 1684.2 2010
                                                                                                                                                         0606AW                                                                                                    existing                                                                 7.LAMINATED BEAM SIZES BASED ON HYNEBEAM SPAN TABLES WHERE




                                                                                                                                                                                        90
                                                                                                                                                                                                                                                                                                                                            OTHER BRANDS ARE USED, SIZES TO BE CONFIRMED WITH
                                                                                                                                          tub




                                                                                                                      u/bench wms
                                                                                                                       + dryer over
                                                                                                                                                                                                                                                                                                                                            MANUFACTURERS SPECIFICATIONS.
                                                                                                                                                                                                                                                                                              kit                                           8. ALL DIMENSIONS TAKE PRECEDENCE OVER SCALES




                                                                                                                                                                                                                                                                                                                 pantry
                                                                                                                                                                                                                                                                                                                                            9. BUILDER AND TRADES ARE TO CONFIRM ALL MEASUREMENTS, DETAILS




                                                                                                                                                                                             2520
                                                                                                                                                       620
                                                                                                                                                       shr
                                                                                                                                                                                                                                                                                                                                            AND SPECIFICATIONS PRIOR TO SETOUT AND ORDERING OF MATERIALS
                                                                                                                                                                                                                                                                                                                                            10. ANY ERRORS ARE TO BE ADDRESSED TO THE DESIGNER AS NO

                                                                       existing cross bracing
                                                                                                                                                                                                                                                                                                                                            RESPONSIBILITY WILL BE TAKEN AFTER CONSTRUCTION HAS COMMENCED




                                                                                                                                                 720
                                                                                                                                                                                                                                                                              kitchen to be renovated
                                                                                                                                                                                                                                                                                                                                            11. ALL TRADES ARE TO CONFORM WITH THE CURRENT AUSTRALIAN




                                                                                                                                                                                    90
                                                                                                                                                                       UP                                                                                                                                                                   STANDARDS RELATING TO HIS OR HER OWN WORK
                                                                                                       EXISTING
                                                                                                                                                     entry                                                                                                                             existing living                                      12. TERMITE PROTECTION TO BE PROVIDED AS PER AS 3660.1.2000




                                                                                                                          2121OXSD
                                                                                                       CARPORT




                                                                                                                                                                                  0315OXSW
                                                                                                                                                                                             2600
                                                                                                                                                       (tiles)
                                                                                                                                                                                                                                                                                                                                             DOMESTIC SMOKE ALARMS:




                                                                                                                                                                                                                                                       existing
                                                                                                                                                                                                                                                                                                                                             1. ALL BEDROOMS AND HALLWAYS ARE TO BE INSTALLED WITH
                                                                                                                                                                                                                                                                                                      existing
                                                                                                                                                                                                                                                                                                                                             PHOTO ELECTRIC SMOKE ALARMS IN ACCORDANCE WITH BUILDING FIRE
                                                                                                existing 90x90shs posts




                                                                                                                                                                                        90
                                                                                                                                                                                                                                                                                                                                             SAFETY LEGISLATION AMENDMENT REGULATION 2016
                                                                                                                                                     0315OXSW                                                                                                                                        2121OXSD                                2. SMOKE ALARMS MUST BE POSITIONED IN ACCORDANCE WITH AS
                                                                                                                                                01                                                                                                                                                         existing deck                     1670.6 - 1997 FIRE DETECTION, WARNING, CONTROL AND INTERCOM
                                                                                                                                                                                                                                                                                                                                             SYSTEMS.
                                                                                                                                                                                                                                                                                                                                             3. DEVICES MUST BE EITHER INTERCONNECTED OR HARD WIRED
                                                                                                           3380                                         3290                                                                                                                                                                                 (EXISTING DWELLINGS ONLY) THAT CANNOT BE
                                                                                                                                                                                                                                                                                                                                             REMOVED FROM DEVICE

                                                                                                                                                                                                                                                                                                                 01
                                                                                                                                                                                                                                                                                                                                         NOTE: SMOKE ALARMS TO BE INSTALLED IN ALL HALLWAYS AND BEDROOMS
                                                                                                                                                                                                                                                                                                                                         TO EXISTING RESIDENCE

                                                                           Ground Floor                                                                                                                                                                First Floor
                                                                                                                                                                                                                                         01

                                                                                                                                                                                                               existing 0906AW       existing 0906AW
                                                                                                                                                                                                           T                     T
                                                                                                                                                                                                    1580




                                                                                                                                                                                                       800

                                                                                                                                                                                                                      recess
                                                                                                                                                                                                                                 S                                                                                                               -
                                                                                                                                                                                                                                                                                                                                         APPROVED PLAN
                                                                                                                                                                                                                   bed                   S
                                                                                                                                                                                                                                                                                                                                           51983.3225.10
                                                                                                                                                                                                                                              bed
                                                                                                                                                                                                                                                                                                                                         NOOSA COUNCIL
                                                                                                                                                                                                                                                                                                                                          1 AUGUST 2017




                                                                                                                                                                                                                                                                                                                                                                                              proposed floor
                                                                                                                                                                                                                                         01
                                                                                                                                                                 elevation D
                                                                                                                                                                                                                                                                                elevation A




                                                                                                                                                                                                                                                                                                04 of 04
                                             Upper Floor                                                                                                          04 of 04




                            PROPOSED:                  CLIENT: PAUL TEYCHENNE                                                                                                                                          BUILDER: MICK GARDNER MANDY'S DESIGN & DRAFTING SHEET: 3 of 4 DATE:                                                                                  ISSUE NO:
                           BUILD IN GROUND+ALTERATIONS                                                                                                                                                                 PH: 0414 697 882      PH: 0403 481 474          SCALE: 1:100 JULY 2017                                                                               A
                              NOTE: THESE DRAWINGS TO BE READ IN CONJUNCTION                                                 NOTE: BUILDER TO CONFIRM SITING AND DIMENSIONS BEFORE CONSTRUCTION
                              WITH ENGINEERS DRAWINGS                                                                        RESPONSIBILITY LIES THERE WITH

Section 8

                                                    -                                                                                                                                                  NOTES:


unit 5, the hastings, noosa parade
                 lot 5 on GTP1154
                                                                                                                                                                                                       1. ALL CONSTRUCTION TO BE IN ACCORDANCE WITH THE AUSTRALIAN
                                            APPROVED PLAN                                                                                                                                              DOMESTIC BUILDING CODE.

                                              51983.3225.10                                                                                                                                            2. ALL TIMBER FRAMING TO BE IN ACCORDANCE WITH AS 1684.2 2010
                                                                                                                                                                                                       RESIDENTIAL TIMBER FRAMING MANUAL.
                                            NOOSA COUNCIL                                                                                                                                              3. PINE FRAMING TO BE MINIUMUM STRESS GRADE MGP 10/MGP12
                                                                                                                                                                                                       4.HARDWOOD FRAMING TO BE MINIMUM STRESS GRADE F14 & MINIMUM
                                             1 AUGUST 2017                                                                                                                                             JOINT GROUP J2.
                                                                                                                                                                                                       5. TIMBER FOR TRUSSES TO BE MINIMUM JOINT GROUP JD4.
                                                                                                                                                                                                       6. TRUSSES TO BE FIXED IN ACCORDANCE WITH MANUF.
                                        UPPER FLOOR TOP PLATE                                                                                                                                          SPECIFICATIONS ALL OTHER FIXINGS TO BE IN ACCORDANCE WITH
                                        UPPER FLOOR JOINERY                                                                                                                                            AS 1684.2 2010
                                                                                                                                                                                                       7.LAMINATED BEAM SIZES BASED ON HYNEBEAM SPAN TABLES WHERE
                                                                                                                                                                                                       OTHER BRANDS ARE USED, SIZES TO BE CONFIRMED WITH
                                                                                                                                                                                                       MANUFACTURERS SPECIFICATIONS.




                                                                    2400
                                                                                                                                                                                                       8. ALL DIMENSIONS TAKE PRECEDENCE OVER SCALES
                                                                                                                                                                                                       9. BUILDER AND TRADES ARE TO CONFIRM ALL MEASUREMENTS, DETAILS
                                        UPPER FLOOR                                                                                                                                                    AND SPECIFICATIONS PRIOR TO SETOUT AND ORDERING OF MATERIALS
                                        FIRST FLOOR TOP PLATE                                                                                                                                          10. ANY ERRORS ARE TO BE ADDRESSED TO THE DESIGNER AS NO
                                                                                                                                                                                                       RESPONSIBILITY WILL BE TAKEN AFTER CONSTRUCTION HAS COMMENCED
                                        FIRST FLOOR JOINERY LINE                                                                                                                                       11. ALL TRADES ARE TO CONFORM WITH THE CURRENT AUSTRALIAN
                                                                                                                                                                                                       STANDARDS RELATING TO HIS OR HER OWN WORK
                                                                    2400                                                                                                                               12. TERMITE PROTECTION TO BE PROVIDED AS PER AS 3660.1.2000


                                        FIRST FLOOR                                                                                                                                                   DOMESTIC SMOKE ALARMS:
                                        GROUND FLOOR TOP PLATE                                                                                                                                        1. ALL BEDROOMS AND HALLWAYS ARE TO BE INSTALLED WITH
                                        GROUND FLOOR JOINERY LINE                                                                                                                                     PHOTO ELECTRIC SMOKE ALARMS IN ACCORDANCE WITH BUILDING FIRE
                                                                                                                                              awning window                                           SAFETY LEGISLATION AMENDMENT REGULATION 2016
                                                                                                                                                                                                      2. SMOKE ALARMS MUST BE POSITIONED IN ACCORDANCE WITH AS
                                                                    2400




                                                                                                                                                                                                      1670.6 - 1997 FIRE DETECTION, WARNING, CONTROL AND INTERCOM
                                                                                                                                                                                                      SYSTEMS.
                                        GROUND FLOOR                                                                                                                                                  3. DEVICES MUST BE EITHER INTERCONNECTED OR HARD WIRED
                                                                    100




                                                                                                                                                                                                      (EXISTING DWELLINGS ONLY) THAT CANNOT BE
                                        PAD LEVEL
                                                                                                                                                                                                      REMOVED FROM DEVICE

                                                                                             vertical timber cladding alike existing
                                              elevation A                                                                                           elevation B                                    NOTE: SMOKE ALARMS TO BE INSTALLED IN ALL HALLWAYS AND BEDROOMS
                                                                                                                                                                                                   TO EXISTING RESIDENCE




                                                                                                                                                                         upper floor top plate

                                                                                                                                                                         upper floor joinery




                                                                                                                                                                                                                                                2400
                                                                                                                                                                         upper floor                      bed
                                                                                                                                                                         first floor top plate
                                                                                                                                                                         first floor joinery




                                                                                                                                                                                                                                                2400
                                                                                                                                                                         first floor                                  kit
                                                                                                                                                                         ground floor top plate
                                                                                                                                                                         ground floor joinery
                                                                                                                                                                  90mm timber framing+




                                                                                                                                                                                                                                   2300
                                                                                                                                                                                                  vj lined and painted




                                                                                                                                                                                                                                                2400
                                                                                                                                                                  cladding over alike existing    between joists, nominal height
                                                                                                                                                                                                  to u/side of lining 2400
                                                                                                                                                                         ground floor




                                                                                                                                                                                                                                                           elevations
                                                                                                                                                                                                               slab and footings as required




                                                elevation C                                                                            elevation D                Section 1
                            PROPOSED:                  CLIENT: PAUL TEYCHENNE BUILDER: MICK GARDNER MANDY'S DESIGN & DRAFTING SHEET: 4 of 4 DATE:                                                                                              ISSUE NO:
                           BUILD IN GROUND+ALTERATIONS                        PH: 0414 697 882      PH: 0403 481 474          SCALE: 1:100 JULY 2017                                                                                           A
                              NOTE: THESE DRAWINGS TO BE READ IN CONJUNCTION   NOTE: BUILDER TO CONFIRM SITING AND DIMENSIONS BEFORE CONSTRUCTION
                              WITH ENGINEERS DRAWINGS                          RESPONSIBILITY LIES THERE WITH

Section 9

           GENERAL SPECIFICATION                                                                                                                                     Construction Notes
                                                                                                                           Timber Frame: Framing to be built in accordance with AS 1684 Termite protected timbers shall be used on all framing
   ALL BUILDING WORK TO BE CARRIED OUT TO THE BUILDING CODE OF AUSTRALIA & THE BUILDING ACT 1975.                          Approved type flashing & sarking to be attached between cladding & frame along with slab & frame to prevent moisture getting to the frames
   BUILDER TO SUPPLY FOOTPATH PROTECTION & REQUIRED SIGNS TO COMPLY TO WORKPLACE HEALTH & SAFETY ACT.
   PRINCIPLE CONTRACTOR TO HAVE A SITE SPECIFIC WORKPLACE HEALTH & SAFETY MANAGEMENT PLAN TO COMPLY WITH                   All wet areas to be made waterproof or resistant to comply to AS 3740 & BCA 3.8.1
   GOVERNMENT REGULATIONS TO BE KEPT ONSITE & GIVEN TO ALL CONTRACTORS                                                     Linings used shall be approved for use in wet areas & shall be fixed in strict accordance
   WRITTEN DIMENSIONS TO TAKE PRECEDENCE OVER SCALE.                                                                       with Manufactures specifications. Wet Areas include Laundry & Bathroom
   BUILDER TO VERIFY ALL SET-OUT DIMENSIONS PRIOR TO PLACEMENT OF CONCRETE
   BUILDING MUST COMPLY WITH THE NATIONAL CONSTRUCTION CODES (BCA) & THE QUEENSLAND HOME BUILDING CODE                     All walls to be checked to ensure they are fixed correctly, straight & plumb prior to fixing plasterboard or interior lining
   ALL CONCRETE SLABS & FOOTINGS TO COMPLY WITH (AS 2870)                                                                  Plasterboard or interior linings to be fixed to dry frames in strict compliance with manufactures details. Setting of plasterboard to be done in strict
   ALL STRUCTURAL TIMBERS TO COMPLY WITH NATIONAL TIMBER FRAMING CODES (AS1684.2 &AS1720) & CONSTRUCTION TIMBERS           compliance with manufactures specifications, Sanded to provide a flat smooth finish
   IN QUEENSLAND (CTIQ)
   TERMITE PROTECTION TO (AS3660.1) CERTIFICATES TO BE SUPPLIED & GIVEN TO CERTIFIER                                       Painting: Paints & application to comply to AS 2311 Min 3 coat application system to be used
   ALL WET AREAS TO BE WATERPROOFED, INTERNAL WATERPROOFING TO COMPLY TO (AS 3740) AS IN BCA 3.8.1                         Substrate to be clean & dry correct type sealers & primers to be used for substrate
   ALL GLASS TO COMPLY TO (AS 1288) WINDOWS & DOORS ALONG WITH SCREENING OR SECURITY SCREENS TO COMPLY TO                  If paint is sprayed on then a back roll should be done between coats & after final coat
   RELEVANT REGULATIONS                                                                                                    Mould resistant paint to be used in Bathrooms, Ceilings to have approved ceiling paint applied & be a matt finish
   PLASTERBOARD TO (AS 2589), PAINTING TO COMPLY TO (AS 2311) TILING TO COMPLY TO (AS 3958)
   STAIRS TO COMPLY TO BCA 3.9.1 BALUSTRADE TO COMPLY TO BCA 3.9.2,                                                        Concrete slabs & footings to be poured AS per Plans & in accord with AS 2870
   WIND CLASSIFICATION (N3).                                                                                               Slabs shall be finished to suit floor coverings

                                                                                                                           All external windows & doors to have appropriate flashing & seals fitted to prevent water getting into building or
                                                                                                                           to the frame work




             APPROVED PLAN
               51983.3225.09
             NOOSA COUNCIL
              1 AUGUST 2017
Client: M & K Himgston       Unit 20/30 Hasting St. The Hastings Noosa Heads                  Wind Classification N3                                                                             Mobile: 0407 693 018                                Date     23/03/2017 3:20:18 PM
                                                                                                                       ACCOLADE Building Designs                                                                                                    Drawn by: S.Horn Drawn for A3 Sheet
RPD: Lot 20 on GTP 1154         Parish: Weyba       County: March       Site Area : 106 m²                                  Proprietor: Steven Horn                                   Email: [email protected] Project Number
                                                                                                                                                                                                                                                                                     1016HMK
Proposed Partial Enclosure of Ground Level Under Existing Unit                                                                 QBSA Lic. 54806                                        Issue Date            23 - March - 2017                            Sheet No. 1          of      6

Section 10

                                                                                                                                                                                                                                                                                                          Hasting          Street
                                                                       Hasting                Street

                                                                                                                                                             APPROVED PLAN
                                                                                                                                                               51983.3225.09
                                                                                                                                                             NOOSA COUNCIL
                                                                                                                                                              1 AUGUST 2017

                                                                                             Lot 21



                                                                                                                                                                                                       4300

                                                                                                  90° 00' 00"

                                                                                                   11.500 m




                                                                                                                                                                              180° 00' 00"

                                                                                                                                                                                             6.300 m
                                                                                                                                Existing Balcony
                            Main Driveway




                                                                             Existing Residence




                                                                                                                                                                                                                                 EMT A
                                                                                                                  600 Sleeper retaining wall                   270° 00' 00"
                                               0° 00' 00"

                                                            10.900 m




                                                                                                                                                                                                                                          180° 00' 30"

                                                                                                                                                                                                                                                         129.960 m
                                                                                                                                                                 4.100 m
                                                                                                                         180° 00' 00"

                                                                                                                                                   4.600 m

                                                                                    Lot 20
                                                                                                                                                                         Lot 19


                                                                                                  270° 00' 00"
              NORTH
                                                                                                       7.400 m




  Real Property Description
                                                                                                                                                                                                                                                                                       Noo
                                                                                                                                                                                                                                                                                           sa P
       Lot No. 20 on GTP. 1154                                                                                                                                                                                                                                                                 a   rade
       Parish: Weyba
       County: March
       Locality: Noosa Heads
       Address: Unit 20 The Hastings
                 Hasting St..                                                                Noosa Parade
       Site Area: 106m²

                                                                                                                                                                                                              Proposed alterations on Lot 20

Client: M & K Himgston                      Unit 20/30 Hasting St. The Hastings Noosa Heads                                                                    Wind Classification N3                                                                                      Mobile: 0407 693 018                     Date       23/03/2017 3:20:20 PM
                                                                                                                                                                                                              ACCOLADE Building Designs                                                                             Drawn by: S.Horn Drawn for A3 Sheet
RPD: Lot 20 on GTP 1154                       Parish: Weyba                           County: March              Site Area : 106 m²                                                                                      Proprietor: Steven Horn                     Email: [email protected] Project Number
                                                                                                                                                                                                                                                                                                                                                 1016HMK
Proposed Partial Enclosure of Ground Level Under Existing Unit                                                                                                                                                              QBSA Lic. 54806                          Issue Date   23 - March - 2017                     Sheet No. 2         of    6

Section 11

                                                                                                                                                                                                                                                                                                                                                       Decking boards to be replaced with
                                                                                              2190                                            1055                     1550                                           2785
                                                                                                                                                                                                                                                                                                                                                       Scyon Secura Exterior Flooring (Or Similar)
                                               70                                                                                        90             70                               70                                                     90                                                                                                     Waterproofed & Coated with approved coloured coating
                                                                                             2030                                             985                       1550                                          2625                                                                                                                             Existing balustrade to be made 1000mm High
                                                                                                                                                                                                                                                                                                                                                       & to comply with BCA 3.9.2
                                                                                                                                                                                                                                                                                                                                                                                                                Existing supports
                                                                                                                                                     Builder to determine all dimensions on site to coincide with existing structure

                                                                                                                                                                          Existing 90 mm SHS posts                                                                                                                                                                                                                                                                                         Existing 1st Floor




                                                                                                                                                                                                                                                                                                                                                  90
                                                                                                                                                                               Existing 100x75 RHS bracing




                                                                                                                                                                                                                                                                                                                                                                                                                  Existing Deck
                                                                                                           Existing 100x75 RHS bracing
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  WC
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Existing Door
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              To be removed
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              walls made good
   2440




                                        Sleeper Retaining wall
                                        Approx 600 mm high                                                                                                                                                                                                                                                                                                                                                                                                                                                    Existing Stairs
                                        Builder to determine on site                                                                                           Existing Carport Slab




                                                                                                                                                                                                                                                                                                                                           3200
                                                                                                                                                                                                                                                                                                                                                                                                                Existing supports
                                                                                                                                                                               Termite protection to slab joints
                                                                                                                                                                               Termite protected timbers to be                                                                                                                                                                                                                                                                                      1st Level
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       2




                                                                                                                                                                                                                                                                                                                                                              Driveway
                                                                                                                                                                               used for framing
                                                                                                                                                                                                       W1 Between Benchtop & wall cabinets
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        1 : 100
          70




                                                                                                                                                                                                       Height to contain full 102 lvrs
               530




                                                                                           Cupboard                                                                                                    close off wall cabinets to upper floor
                           850




                                                                                                                                                                                                                                                                                                                                                       6670
          70




                                                                                                                                                                                                                 W1
                      90




                                                                                                                                                                                                                                                                                                                                                  90
                                                                                                                                                                                                                                                                                                                               600
                                                                                                                                                                                                                                                                                         Window to be as high as possible
                                                                                                                                                                                                                                                                                         Size to be full louvers blades 6 of
                                                                                                                                                                                                                                         BRM                                                                                                                                                                            2065                                                                            5480
                                                                                                                                                                                                                TUB
                                                                                                                                                                                               Drier                           WM




                                                                                                                                                                                                                                                                                         Builder to determine on site
                                                                                                                                                                          D1




                                                                                                                                                                                                                                                                                                                                      70
                                    A                                                                                                                                                                                                                                                                                                                                                                                                                                                     Existing 90 mm SHS posts




                                                                                                                                                                                                                                                                                                                                                              Main
                                                    6 mm villa board to be nail off as




                                    5




                                                                                                                                                                                                                                                                                                                                           2300
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           Existing 100x75 RHS bracing




                                                                                                                                                                                         770
   4230




                                         D2




                                                                                                                                                                                                             Laundry/Bathroom
                                                    bracing sheet for this wall




                                                                                                                                                                                                                                                                                                                                                                                                                                                    Existing 100x75 RHS bracing
                                                                                                                                                                                                                                                        Mechanical Exhaust vent
                                                                                             Proposed Store/Mudroom
               3470




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            Driveway
                                                                                                                                                                                                                                                                                                                                                                                                2435
                           3200




                                                                                                                                                                 Proposed Entrance




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                     3290
                                                                                                                                                                                                                                                                                                                               2620
                                                                                                                                                                                                                                      900x900                                                                                                                                                                                                                                               Existing Carport Area
                                                                                                                                                                                                                                        SHR




                                                                                                                                                                                                                                                                                                                                                  90
                                                                                                                                                                                                                                                                                                                                                                                                              Existing 90 mm
                                                                                                                                                                                                                                                                                                                                                                                                              SHS posts
                                                                                                                                                                                                 Remove Existing Slab & replace




                                                                                                                                                                                                                                                      New door
                                                                                                                                                         770




                                                                                                                                                                                                                                                                                                                                           810
                                                                                                                                                                                       up                                                                                                                                                                                                                                                                                                                          Existing




                                                                                                                                                                                                                                                 D3




                                                                                                                                                                                                                                                                                                                                                                                                                         Cantilevered Deck Over
                                                                                                                                                                                                                      Storage under stairs




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              1580
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   Laundry




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                     2480
                                                                                                                                                                                                                                                                                                                                                  90




                                                                                                                                                                                                                                                                                                                                                                                                4235
          90




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         6.1 m²




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            Main
                                                                                                                                                                                                                                                                door to match cladding
                                                                                                      W3                                                                                W2             Existing Stairs to be replaced




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Exist
                                  APPROVED PLAN




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              900
                                                                                                                                                                                                              with solid risers

                                    51983.3225.09                                                                                                                                                       Concrete slab under existing stairs                                                                                     Additional Eclosed Area :                20.5 m²




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                     900
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   up             Existing Open Stairs
                                                                                                                                                                                                        approx 50mm below slab for existing                                                                                     Existing Laundry Area:                    6.1 m²
                                  NOOSA COUNCIL                                                                                                                                                         room                                                                                                                    Total enclosed Lower Floor:              26.6 m²
                                                                                                                                                                                                                                                                                                                                Total Area Inc. Carport                  45.4 m²
                                   1 AUGUST 2017                                                                                                                                                        to be removed & replaced to match                                                                                                                                                                                                                                               Existing 90 mm SHS posts
                                                                                                                                                                                                        existing Slab Level                                                                                                     Upper Floors not Noted
                                                                                                                                                                                                                                                                                                                                                                                                                        2065                                                            2695                               2785
                                                                                                      3105                                                             1550                                           2625
                                               70                                                                                                         70                            70                                                      90
                                                                                                                                                                   7580
                                                                                                                                                                                                                                                                                                                                                                                                  Existing Ground Floor Plan
                                                                                                                                                                       Ground Floor Plan                                                                                                                                                                                                 3
                                                                                                                                                             1            1 : 50
                                                                                                                                                                                                                                                                                                                                                                                                       1 : 100
                                                                                                                                                                                                                                           Window Schedule                                                                                                                                                                                                                        Door Schedule
     Additional Lower floor addition to be clad with Shadow Clad to match existing external walls & painted the same colour
                                                                                                                                                                                                             Mark Height Width                  Comments                                                                              Location                                     Mark Height Width               Comments                                                              Location                          Lintel        Jamb Studs
                        All dimensions to be confirmed on site to coincide with existing residence                                                                                                             W1        541        610         Louvers/Obs.                                                                      Laund/Bath                                        D1   2040          870                 Entry Door                                                      Entrance
                                                                                                                                                                                                               W2        900        600         Double Hung                                                                        Ent/Stairs                                       D2   2100          1800               Alum Sliding                                                 Store/Mud Room              120x42 Smart LVL           2
                                                                                                                                                                                                               W3        600        1200         Alum Slider                                                                   Store/Mud Room                                       D3   2040          620                  External                                                   Store under Stairs


Client: M & K Himgston                                      Unit 20/30 Hasting St. The Hastings Noosa Heads                                                                                              Wind Classification N3                                                                                                                                                                                                                   Mobile: 0407 693 018                                                              Date    23/03/2017 3:20:20 PM
                                                                                                                                                                                                                                                                                         ACCOLADE Building Designs                                                                                                                                                                                                                  Drawn by: S.Horn Drawn for A3 Sheet
RPD: Lot 20 on GTP 1154                                                                  Parish: Weyba                                   County: March              Site Area : 106 m²                                                                                                                                          Proprietor: Steven Horn                                                   Email: [email protected] Project Number
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            1016HMK
Proposed Partial Enclosure of Ground Level Under Existing Unit                                                                                                                                                                                                                                                                     QBSA Lic. 54806                                                        Issue Date                                                               23 - March - 2017                                     Sheet No. 3                   of    6

Section 12

                                                                                                                                                    APPROVED PLAN
                                                                                                                                                      51983.3225.09
                                                                                                                                                    NOOSA COUNCIL
                                                                                                                                                     1 AUGUST 2017


                                                                                                                                                                                                                                                      Existing Support to balcony




                                                                                        it
                                                                                      Un
                                                                                     ing




                                                                                                                                                                                                                              it
                                                                                                                                                                                                                            Un
                                                                                 is t
                                                                               Ex




                                                                                                                                                                                                                           ing
     Existing Balcony




                                                                                                                                                                                                                       is t
                                                                                                                                                                                                                     Ex
     to be made waterproof                                                                                                                                                       Existing Wall
                                                                                                                                                                                 New window                                                             Existing
                                                                                                                                                                                                                                                        Balcony
                                                                                                              Existing 100x75 RHS
                                                                                                              Bracing to remain
                                                                                                              framing to be fixed to
                                                                                                              RHS & clad over
                                                                                                                                                                                 Existing 100x75 RHS            W1                                                            Proposed wall
                                                                                                              Existing SHS into frame                                            Bracing
                                                                               Proposed wall

                                                                    Cladding to match existing upper floors
                                                Proposed Area                                                                                                                                                    Existing Carport


                                             North Elevation                                                                                                                                                   South Elevation
                               1               1 : 100                                                                                                                                                 2        1 : 100
                                               it
                                             Un




                       Exist                                Exist
                                         ing
                                     is t
                                   Ex




                                                                                                                                                                                                                                                   it
                                                                                                                                                                                                                                                 Un
                                                                                                                                                                                                                                               ing
                                                                                                                                                                                                                                           is t
                                                                                                                                                                                                                                         Ex
                                                                                 Balustrade made to comply
                                     Exist          Exist
                                             Existing
                     1000




                                             Balcony
                                                                                                                                                                                                                                                                                    Existing 100x75 RHS
                                                                                                                                                                                                                                      Existing Wall                                 Cross bracing

                                                                                                    East Elevation                                               West Elevation                                        D3



               Existing Carport
                                                    Proposed wall                          4         1 : 100
                                                                                                                                                            3     1 : 100
                                                                                                                                                                                                                                                           Existing Carport

                                                                                                                                                                                                              Enclosed under existing stairs


Client: M & K Himgston                   Unit 20/30 Hasting St. The Hastings Noosa Heads                                           Wind Classification N3                                                         Mobile: 0407 693 018        Date     23/03/2017 3:20:21 PM
                                                                                                                                                            ACCOLADE Building Designs                                                         Drawn by; S.Horn Drawn for A3 Sheet
RPD: Lot 20 on GTP 1154                        Parish: Weyba                  County: March             Site Area : 106 m²                                      Proprietor: Steven Horn                    Email: [email protected]
                                                                                                                                                                                                                                                                        Project Number              1016HMK
Proposed Partial Enclosure of Ground Level Under Existing Unit                                                                                                   QBSA Lic. 54806                           Issue Date:           23 - March - 2017                      Scale     1 : 100 Sheet No. 4   of 6

Section 13

                                                                                                                                                                                                                       NOTES:

unit 13, the hastings, noosa parade                                                                                                                                                                                    1. ALL CONSTRUCTION TO BE IN ACCORDANCE WITH THE AUSTRALIAN
                                                                                                                                                                                                                       DOMESTIC BUILDING CODE.
                                                                                                                                                                                                                       2. ALL TIMBER FRAMING TO BE IN ACCORDANCE WITH AS 1684.2 2010
                                                                                                                                                                                                                       RESIDENTIAL TIMBER FRAMING MANUAL.


                                                                                               NO
                                                                                                                                                                                                                       3. PINE FRAMING TO BE MINIUMUM STRESS GRADE MGP 10/MGP12
                                                                                                                                                                                                                       4.HARDWOOD FRAMING TO BE MINIMUM STRESS GRADE F14 & MINIMUM


                                                                                                            OS
                                                                                                                                                                                                                       JOINT GROUP J2.
                                                                                                                                                                                                                       5. TIMBER FOR TRUSSES TO BE MINIMUM JOINT GROUP JD4.
                                                                                                                                                                                                                       6. TRUSSES TO BE FIXED IN ACCORDANCE WITH MANUF.

                                                                                                                         A                                                                                             SPECIFICATIONS ALL OTHER FIXINGS TO BE IN ACCORDANCE WITH


                                                                                                                                   PA
                                                                                                                                                                                                                       AS 1684.2 2010
                                                                                                                                                                                                                       7.LAMINATED BEAM SIZES BASED ON HYNEBEAM SPAN TABLES WHERE
                                                                                                                                                                                                                       OTHER BRANDS ARE USED, SIZES TO BE CONFIRMED WITH

                                                                                                                                              RA                                                                       MANUFACTURERS SPECIFICATIONS.
                                                                                                                                                                                                                       8. ALL DIMENSIONS TAKE PRECEDENCE OVER SCALES


                                                                                                                                                            DE
                                                                                                                                                                                                                       9. BUILDER AND TRADES ARE TO CONFIRM ALL MEASUREMENTS, DETAILS
                                                                                                                                                                                                                       AND SPECIFICATIONS PRIOR TO SETOUT AND ORDERING OF MATERIALS
                                                                                                                                                                                                                       10. ANY ERRORS ARE TO BE ADDRESSED TO THE DESIGNER AS NO
                                                                                                                                          45.07                                                                        RESPONSIBILITY WILL BE TAKEN AFTER CONSTRUCTION HAS COMMENCED
                                                                                                                                                  0                                                                    11. ALL TRADES ARE TO CONFORM WITH THE CURRENT AUSTRALIAN
                                                                                                                                                                                                                       STANDARDS RELATING TO HIS OR HER OWN WORK
                                                                                                                                                                                                                       12. TERMITE PROTECTION TO BE PROVIDED AS PER AS 3660.1.2000



                                                                                                                                                                                                                       DOMESTIC SMOKE ALARMS:
                                                                                                                                                                                                                       1. ALL BEDROOMS AND HALLWAYS ARE TO BE INSTALLED WITH
                                                                                                                                                                                                                       PHOTO ELECTRIC SMOKE ALARMS IN ACCORDANCE WITH BUILDING FIRE
                                                                                                                                                                                                                       SAFETY LEGISLATION AMENDMENT REGULATION 2016




                                                                                                                                                                      6600
                                                                                                                                                                                                                       2. SMOKE ALARMS MUST BE POSITIONED IN ACCORDANCE WITH AS




                                                                                                                                                                                               5400
                                                                                                                                                                                                                       1670.6 - 1997 FIRE DETECTION, WARNING, CONTROL AND INTERCOM
                                                                                                                                                            UNIT 14                                                    SYSTEMS.
                                                                                                                                                                                                                       3. DEVICES MUST BE EITHER INTERCONNECTED OR HARD WIRED
                                                                                                                                                                             existing timber fence                     (EXISTING DWELLINGS ONLY) THAT CANNOT BE




                                                                                                                                                                                                      600
                                                                                                                                                                                                                       REMOVED FROM DEVICE
                                                             129.360




                                                                                                                                                                                                                     NOTE: SMOKE ALARMS TO BE INSTALLED IN ALL HALLWAYS AND BEDROOMS
                                                                                                                                                                                                                     TO EXISTING RESIDENCE

                                                                                                                                                                             UNIT 13                                                                   -

                                                                                                                                                                                                                                    NOOSA COUNCIL
                                                                                                                                                                                                                                    APPROVED PLAN
                                                                                                                                                                                                                                51983.3225.08 5 APR 2017
                                                                                                                                                                       (PROPOSED BUILD IN)




                                                                                                                                                                                                            62.648




                                                                                                                                                                                                                                                                          site plan
                                       PROPOSED:                  CLIENT: JENIFER BASHFORD BUILDER: MICK GARDNER MANDY'S DESIGN & DRAFTING SHEET: 1 of 4 DATE:                                                                                             ISSUE NO:
                                      BUILD IN GROUND+ALTERATIONS PH: 0412 104 710         PH: 0414 697 882      PH: 0403 481 474          SCALE: 1:100 MAR 2017                                                                                           C
                                      NOTE: THESE DRAWINGS TO BE READ IN CONJUNCTION   NOTE: BUILDER TO CONFIRM SITING AND DIMENSIONS BEFORE CONSTRUCTION
                                      WITH ENGINEERS DRAWINGS                          RESPONSIBILITY LIES THERE WITH

Section 14

                                                                                                                                                                                                                                                                                                                                                NOTES:


unit 13, the hastings, noosa parade                                              90         90                          90
                                                                                                                                                                                                                                                                                                                                                1. ALL CONSTRUCTION TO BE IN ACCORDANCE WITH THE AUSTRALIAN
                                                                                                                                                                                                                                                                                                                                                DOMESTIC BUILDING CODE.
                                                                                                                                                                                                                                                                                                                                                2. ALL TIMBER FRAMING TO BE IN ACCORDANCE WITH AS 1684.2 2010




                                                       elevation C
                                                                                                                                                                                                                                                                                                                                 04 of 04       RESIDENTIAL TIMBER FRAMING MANUAL.
                                                                                      810               2280
                                           04 of 04                                                                                                                                                                                                                                                                                             3. PINE FRAMING TO BE MINIUMUM STRESS GRADE MGP 10/MGP12
                                                                                                                                                                                                                                               01                                                                                               4.HARDWOOD FRAMING TO BE MINIMUM STRESS GRADE F14 & MINIMUM
                                                                                                                                                                                                                                                                                                                               elevation B      JOINT GROUP J2.
                                                                                                                                                                                                                                          70              70                                        70                                          5. TIMBER FOR TRUSSES TO BE MINIMUM JOINT GROUP JD4.
                                                                                 store under                01                                                                                                                     1630        1010                           3730                                                              6. TRUSSES TO BE FIXED IN ACCORDANCE WITH MANUF.
                                                                                                                             proposed bath/l'dry                                                                                                                                                                                                SPECIFICATIONS ALL OTHER FIXINGS TO BE IN ACCORDANCE WITH
                                                                                             0606AW
                                                                                                                                                                                                                                                                                        existing                                                AS 1684.2 2010
                                                      90                                                          tub                                                                                                                                                                                                                           7.LAMINATED BEAM SIZES BASED ON HYNEBEAM SPAN TABLES WHERE




                                                                                                                         u/bench wms
                                                                                            620




                                                                                                                         + dryer over
                                                                                                                                                                                                                                                                                                                                                OTHER BRANDS ARE USED, SIZES TO BE CONFIRMED WITH




                                                                                                                                                                                                                                                 pantry
                                                                                                                                                                                                                                                                       kitkitchen to be renovated                                               MANUFACTURERS SPECIFICATIONS.




                                                                                                                                                                                                                                                               2/520




                                                                                                                                                                                                                                                                                                         1950
                                                          2520

                                                                                                                                                                                                                                                                                                                                                8. ALL DIMENSIONS TAKE PRECEDENCE OVER SCALES




                                                                                                  shr
                                                                                                                                                                                                                                                                                                                                                9. BUILDER AND TRADES ARE TO CONFIRM ALL MEASUREMENTS, DETAILS




                                                                                                                                                                  existing cross bracing
                                                                                                                                                                                                                                                                                                                                                AND SPECIFICATIONS PRIOR TO SETOUT AND ORDERING OF MATERIALS




                                                                                                            720
                                                                                                                                                                                                                                                      (door size to                                                                             10. ANY ERRORS ARE TO BE ADDRESSED TO THE DESIGNER AS NO
                                                                                                                                                                                                                                                                                                                                                RESPONSIBILITY WILL BE TAKEN AFTER CONSTRUCTION HAS COMMENCED
                                                      90




                                                                                      UP                                                                                                                                                              be confirmed)
                                                                                                                                                                                                                                                                                                                                                11. ALL TRADES ARE TO CONFORM WITH THE CURRENT AUSTRALIAN
                                                                                                                                              EXISTING                                                                                                cabinetry to be confirmed                                                                 STANDARDS RELATING TO HIS OR HER OWN WORK
                                                                                                                                                                                                                                                      by owner/builder




                                                                                                                             2121OXSD
                                                                                                                                              CARPORT                                                                                                                                                                                           12. TERMITE PROTECTION TO BE PROVIDED AS PER AS 3660.1.2000




                                                                                                                                                                                                                                                                                                         3300
                                                                      0315OXSW
                                                          2600




                                                                                                  (tiles)

                                                                                                                                                                                                                                                                                                                                                 DOMESTIC SMOKE ALARMS:
                                                                                                                                        existing 90x90shs posts                                                                                                                                                                                  1. ALL BEDROOMS AND HALLWAYS ARE TO BE INSTALLED WITH
                                                      90




                                                                                                                                                                                                                                                                                                                                                 PHOTO ELECTRIC SMOKE ALARMS IN ACCORDANCE WITH BUILDING FIRE
                                                                                            0315OXSW 01                                                                                                                                                                                                                                          SAFETY LEGISLATION AMENDMENT REGULATION 2016
                                                                                                                                                                                                                                                                                                                                                 2. SMOKE ALARMS MUST BE POSITIONED IN ACCORDANCE WITH AS
                                                                                                  3290                                         3380                                                                                            01                                                                                                1670.6 - 1997 FIRE DETECTION, WARNING, CONTROL AND INTERCOM
                                                                                                                                                                                                                                                                                                                                                 SYSTEMS.
                                                                                                                                                                                                                                                                                                                                                 3. DEVICES MUST BE EITHER INTERCONNECTED OR HARD WIRED
                                                                                                                                                                                                                                                                                                                                                 (EXISTING DWELLINGS ONLY) THAT CANNOT BE
                                                                                                                                                                                                                                                                                                                                                 REMOVED FROM DEVICE
                                                                     Ground Floor                                                                                                                                                  First Floor




                                                                                                                                                                                                                                                                                                                elevation A
                                                                                                                                                                                                 01                                                                                                                           04 of 04
                                                                                                                                                                                                                                                                                                                                             NOTE: SMOKE ALARMS TO BE INSTALLED IN ALL HALLWAYS AND BEDROOMS
                                                                                                                                                                                                                                                                                                                                             TO EXISTING RESIDENCE




                                                                                                                                                                                                   existing       existing                                                                                                                                                    -

                                                                                                                                                                                                                             T                                                                                                                             NOOSA COUNCIL
                                                                                                                                                                                                              T
                                                                                                                                                                                                                                                                                                                                                           APPROVED PLAN
                                                                                                                                                                                                                                                                                                                                                       51983.3225.08 5 APR 2017
                                                                                                                                                                                             720




                                                                                                                                                                                                                             720
                                                                                                                                                                                                              S

                                                                                                                                                                                                      S
                                                                                                                                                                                                                  bed
                                                                                                                                                                                           bed



                                                                                                                                                                                                 01




                                                                                                                                                                                                                                                                                                                                                                                                  proposed floor
                                                                                                                                  elevation D


                                                                                                                                        04 of 04              Upper Floor



                                       PROPOSED:                  CLIENT: JENIFER BASHFORD BUILDER: MICK GARDNER MANDY'S DESIGN & DRAFTING SHEET: 3 of 4 DATE:                                                                                                                                                                                                                    ISSUE NO:
                                      BUILD IN GROUND+ALTERATIONS PH: 0412 104 710         PH: 0414 697 882      PH: 0403 481 474          SCALE: 1:100 MAR 2017                                                                                                                                                                                                                  C
                                      NOTE: THESE DRAWINGS TO BE READ IN CONJUNCTION                                                      NOTE: BUILDER TO CONFIRM SITING AND DIMENSIONS BEFORE CONSTRUCTION
                                      WITH ENGINEERS DRAWINGS                                                                             RESPONSIBILITY LIES THERE WITH

Section 15

                                                                                                                                                                                                                         NOTES:


unit 13, the hastings, noosa parade                                                                                                                                                                                      1. ALL CONSTRUCTION TO BE IN ACCORDANCE WITH THE AUSTRALIAN
                                                                                                                                                                                                                         DOMESTIC BUILDING CODE.
                                                                                                                                                                                                                         2. ALL TIMBER FRAMING TO BE IN ACCORDANCE WITH AS 1684.2 2010
                                                                                                                                                                                                                         RESIDENTIAL TIMBER FRAMING MANUAL.
                                                                                                                                                                                                                         3. PINE FRAMING TO BE MINIUMUM STRESS GRADE MGP 10/MGP12
                                                                                                                                                                                                                         4.HARDWOOD FRAMING TO BE MINIMUM STRESS GRADE F14 & MINIMUM
                                                                                                                                                                                                                         JOINT GROUP J2.
                                                                                                                                                                                                                         5. TIMBER FOR TRUSSES TO BE MINIMUM JOINT GROUP JD4.
                                                                                                                                                                                                                         6. TRUSSES TO BE FIXED IN ACCORDANCE WITH MANUF.
                                         UPPER FLOOR TOP PLATE                                                                                                                                                           SPECIFICATIONS ALL OTHER FIXINGS TO BE IN ACCORDANCE WITH
                                         UPPER FLOOR JOINERY                                                                                                                                                             AS 1684.2 2010
                                                                                                                                                                                                                         7.LAMINATED BEAM SIZES BASED ON HYNEBEAM SPAN TABLES WHERE
                                                                                                                                                                                                                         OTHER BRANDS ARE USED, SIZES TO BE CONFIRMED WITH
                                                                                                                                                                                                                         MANUFACTURERS SPECIFICATIONS.




                                                                     2400
                                                                                                                                                                                                                         8. ALL DIMENSIONS TAKE PRECEDENCE OVER SCALES
                                                                                                                                                                                                                         9. BUILDER AND TRADES ARE TO CONFIRM ALL MEASUREMENTS, DETAILS
                                         UPPER FLOOR                                                                                                                                                                     AND SPECIFICATIONS PRIOR TO SETOUT AND ORDERING OF MATERIALS
                                         FIRST FLOOR TOP PLATE                                                                                                                                                           10. ANY ERRORS ARE TO BE ADDRESSED TO THE DESIGNER AS NO
                                                                                                                                                                                                                         RESPONSIBILITY WILL BE TAKEN AFTER CONSTRUCTION HAS COMMENCED
                                         FIRST FLOOR JOINERY LINE                                                                                                                                                        11. ALL TRADES ARE TO CONFORM WITH THE CURRENT AUSTRALIAN
                                                                                                                                                                                                                         STANDARDS RELATING TO HIS OR HER OWN WORK
                                                                     2400


                                                                                                                                                                                                                         12. TERMITE PROTECTION TO BE PROVIDED AS PER AS 3660.1.2000


                                         FIRST FLOOR                                                                                                                                                                    DOMESTIC SMOKE ALARMS:
                                         GROUND FLOOR TOP PLATE                                                                                                                                                         1. ALL BEDROOMS AND HALLWAYS ARE TO BE INSTALLED WITH
                                         GROUND FLOOR JOINERY LINE                                                                                                                                                      PHOTO ELECTRIC SMOKE ALARMS IN ACCORDANCE WITH BUILDING FIRE
                                                                                                                                                                                              awning window             SAFETY LEGISLATION AMENDMENT REGULATION 2016
                                                                                                                                                                                                                        2. SMOKE ALARMS MUST BE POSITIONED IN ACCORDANCE WITH AS
                                                                     2400




                                                                                                                                                                                                                        1670.6 - 1997 FIRE DETECTION, WARNING, CONTROL AND INTERCOM
                                                                                                                                                                                                                        SYSTEMS.
                                         GROUND FLOOR                                                                                                                                                                   3. DEVICES MUST BE EITHER INTERCONNECTED OR HARD WIRED
                                                                     100




                                                                                                                                                                                                                        (EXISTING DWELLINGS ONLY) THAT CANNOT BE
                                         PAD LEVEL
                                                                                                                                                                                                                        REMOVED FROM DEVICE

                                                                                              vertical timber cladding alike existing
                                             elevation A                                                                                                    elevation B                                              NOTE: SMOKE ALARMS TO BE INSTALLED IN ALL HALLWAYS AND BEDROOMS
                                                                                                                                                                                                                     TO EXISTING RESIDENCE



                                                                                                                                                                          UPPER FLOOR TOP PLATE
                                                                                                                                                                          UPPER FLOOR JOINERY




                                                                                                                                                                                                                                                                          2400
                                                                                                                                                                          UPPER FLOOR
                                                                                                                                                                                                                                      bed
                                                                                                                                                                          FIRST FLOOR TOP PLATE
                                                                                                                                                                          FIRST FLOOR JOINERY LINE




                                                                                                                                                                                                                                                                          2400
                                                                                                                                                                          FIRST FLOOR                                       kit
                                                                                                                                                                          GROUND FLOOR TOP PLATE
                                                                                                                                                                          GROUND FLOOR JOINERY LINE




                                                                                                                                                                                                                                                   u/side of joists
                                                                                                                                                                                                                                            2300




                                                                                                                                                                                                                                                                          2400
                                                                                                                                                                                                        vj lined and painted




                                                                                                                                                                                                                                                   proposed
                                                                                                                                                                                                        between joists, nominal height to                                        90mm timber framing + cladding
                                                                                                                                                                                                        u/side of lining 2400                                                    over alike existing
                                                                                                                                                                          GROUND FLOOR


                                                                                                                                                                                                                   slab and footings as required

                                                                                                                                                                                        Section 1                                                                     -




                                                                                                                                                                                                                                                                                                        elevations
                                                                                                                                                                                                                           NOOSA COUNCIL
                                                                                                                                                                                                                           APPROVED PLAN
                                                                                                                                                                                                                       51983.3225.08 5 APR 2017
                                                         elevation C                                                                    elevation D
                                       PROPOSED:                  CLIENT: JENIFER BASHFORD BUILDER: MICK GARDNER MANDY'S DESIGN & DRAFTING SHEET: 4 of 4 DATE:                                                                                                                    ISSUE NO:
                                      BUILD IN GROUND+ALTERATIONS PH: 0412 104 710         PH: 0414 697 882      PH: 0403 481 474          SCALE: 1:100 MAR 2017                                                                                                                  C
                                      NOTE: THESE DRAWINGS TO BE READ IN CONJUNCTION   NOTE: BUILDER TO CONFIRM SITING AND DIMENSIONS BEFORE CONSTRUCTION
                                      WITH ENGINEERS DRAWINGS                          RESPONSIBILITY LIES THERE WITH

Section 16

           GENERAL SPECIFICATION                                                                                                                                     Construction Notes
                                                                                                                           Timber Frame: Framing to be built in accordance with AS 1684 Termite protected timbers shall be used on all framing
   ALL BUILDING WORK TO BE CARRIED OUT TO THE BUILDING CODE OF AUSTRALIA & THE BUILDING ACT 1975.                          Approved type flashing & sarking to be attached between cladding & frame along with slab & frame to prevent moisture getting to the frames
   BUILDER TO SUPPLY FOOTPATH PROTECTION & REQUIRED SIGNS TO COMPLY TO WORKPLACE HEALTH & SAFETY ACT.
   PRINCIPLE CONTRACTOR TO HAVE A SITE SPECIFIC WORKPLACE HEALTH & SAFETY MANAGEMENT PLAN TO COMPLY WITH                   All wet areas to be made waterproof or resistant to comply to AS 3740 & BCA 3.8.1
   GOVERNMENT REGULATIONS TO BE KEPT ONSITE & GIVEN TO ALL CONTRACTORS                                                     Linings used shall be approved for use in wet areas & shall be fixed in strict accordance
   WRITTEN DIMENSIONS TO TAKE PRECEDENCE OVER SCALE.                                                                       with Manufactures specifications. Wet Areas include Laundry & Bathroom
   BUILDER TO VERIFY ALL SET-OUT DIMENSIONS PRIOR TO PLACEMENT OF CONCRETE
   BUILDING MUST COMPLY WITH THE NATIONAL CONSTRUCTION CODES (BCA) & THE QUEENSLAND HOME BUILDING CODE                     All walls to be checked to ensure they are fixed correctly, straight & plumb prior to fixing plasterboard or interior lining
   ALL CONCRETE SLABS & FOOTINGS TO COMPLY WITH (AS 2870)                                                                  Plasterboard or interior linings to be fixed to dry frames in strict compliance with manufactures details. Setting of plasterboard to be done in strict
   ALL STRUCTURAL TIMBERS TO COMPLY WITH NATIONAL TIMBER FRAMING CODES (AS1684.2 &AS1720) & CONSTRUCTION TIMBERS           compliance with manufactures specifications, Sanded to provide a flat smooth finish
   IN QUEENSLAND (CTIQ)
   TERMITE PROTECTION TO (AS3660.1) CERTIFICATES TO BE SUPPLIED & GIVEN TO CERTIFIER                                       Painting: Paints & application to comply to AS 2311 Min 3 coat application system to be used
   ALL WET AREAS TO BE WATERPROOFED, INTERNAL WATERPROOFING TO COMPLY TO (AS 3740) AS IN BCA 3.8.1                         Substrate to be clean & dry correct type sealers & primers to be used for substrate
   ALL GLASS TO COMPLY TO (AS 1288) WINDOWS & DOORS ALONG WITH SCREENING OR SECURITY SCREENS TO COMPLY TO                  If paint is sprayed on then a back roll should be done between coats & after final coat
   RELEVANT REGULATIONS                                                                                                    Mould resistant paint to be used in Bathrooms, Ceilings to have approved ceiling paint applied & be a matt finish
   PLASTERBOARD TO (AS 2589), PAINTING TO COMPLY TO (AS 2311) TILING TO COMPLY TO (AS 3958)
   STAIRS TO COMPLY TO BCA 3.9.1 BALUSTRADE TO COMPLY TO BCA 3.9.2,                                                        Concrete slabs & footings to be poured AS per Plans & in accord with AS 2870
   WIND CLASSIFICATION (N3).                                                                                               Slabs shall be finished to suit floor coverings
                                                                                                           -
                                                                                             NOOSA COUNCIL                 All external windows & doors to have appropriate flashing & seals fitted to prevent water getting into building or
                                                                                            APPROVED PLANS                 to the frame work
                                                                                       51983.3225.07 29 MARCH 2017




Client: M & K Himgston       Unit 20/30 Hasting St. The Hastings Noosa Heads                  Wind Classification N3                                                                             Mobile: 0407 693 018                                Date     23/03/2017 3:20:18 PM
                                                                                                                       ACCOLADE Building Designs                                                                                                    Drawn by: S.Horn Drawn for A3 Sheet
RPD: Lot 20 on GTP 1154         Parish: Weyba       County: March       Site Area : 106 m²                                  Proprietor: Steven Horn                                   Email: [email protected] Project Number
                                                                                                                                                                                                                                                                                     1016HMK
Proposed Partial Enclosure of Ground Level Under Existing Unit                                                                 QBSA Lic. 54806                                        Issue Date            23 - March - 2017                            Sheet No. 1          of      6

Section 17

                                                                                                                                                                                                                                                                                                            Hasting          Street
                                                                       Hasting                Street




                                                                                             Lot 21



                                                                                                                                                                                                         4300

                                                                                                  90° 00' 00"

                                                                                                   11.500 m




                                                                                                                                                                                180° 00' 00"

                                                                                                                                                                                               6.300 m
                                                                                                                                Existing Balcony
                            Main Driveway




                                                                             Existing Residence




                                                                                                                                                                                                                                   EMT A
                                                                                                                  600 Sleeper retaining wall                  270° 00' 00"
                                               0° 00' 00"

                                                            10.900 m




                                                                                                                                                                                                                                            180° 00' 30"

                                                                                                                                                                                                                                                           129.960 m
                                                                                                                                                                4.100 m
                                                                                                                         180° 00' 00"

                                                                                                                                                    4.600 m

                                                                                    Lot 20
                                                                                                                                                                           Lot 19


                                                                                                  270° 00' 00"
              NORTH
                                                                                                       7.400 m




                                                                                                                                                                       -
                                                                                                                                                         NOOSA COUNCIL
  Real Property Description                                                                                                                             APPROVED PLANS                                                                                                                   Noo
                                                                                                                                                                                                                                                                                             sa P
       Lot No. 20 on GTP. 1154                                                                                                                     51983.3225.07 29 MARCH 2017                                                                                                                   a   rade
       Parish: Weyba
       County: March
       Locality: Noosa Heads
       Address: Unit 20 The Hastings
                 Hasting St..                                                                Noosa Parade
       Site Area: 106m²

                                                                                                                                                                                                                Proposed alterations on Lot 20

Client: M & K Himgston                      Unit 20/30 Hasting St. The Hastings Noosa Heads                                                                   Wind Classification N3                                                                                         Mobile: 0407 693 018                     Date       23/03/2017 3:20:20 PM
                                                                                                                                                                                                                ACCOLADE Building Designs                                                                             Drawn by: S.Horn Drawn for A3 Sheet
RPD: Lot 20 on GTP 1154                       Parish: Weyba                           County: March              Site Area : 106 m²                                                                                        Proprietor: Steven Horn                     Email: [email protected] Project Number
                                                                                                                                                                                                                                                                                                                                                   1016HMK
Proposed Partial Enclosure of Ground Level Under Existing Unit                                                                                                                                                                QBSA Lic. 54806                          Issue Date   23 - March - 2017                     Sheet No. 2         of    6

Section 18

                                                                                                                                                                                                                                                                                                                                                     Decking boards to be replaced with
                                                                                            2190                                            1055                     1550                                           2785
                                                                                                                                                                                                                                                                                                                                                     Scyon Secura Exterior Flooring (Or Similar)
                                             70                                                                                        90             70                               70                                                     90                                                                                                     Waterproofed & Coated with approved coloured coating
                                                                                           2030                                             985                       1550                                          2625                                                                                                                             Existing balustrade to be made 1000mm High
                                                                                                                                                                                                                                                                                                                                                     & to comply with BCA 3.9.2
                                                                                                                                                                                                                                                                                                                                                                                                                Existing supports
                                                                                                                                                   Builder to determine all dimensions on site to coincide with existing structure

                                                                                                                                                                        Existing 90 mm SHS posts                                                                                                                                                                                                                                                                                           Existing 1st Floor




                                                                                                                                                                                                                                                                                                                                                90
                                                                                                                                                                             Existing 100x75 RHS bracing




                                                                                                                                                                                                                                                                                                                                                                                                                  Existing Deck
                                                                                                         Existing 100x75 RHS bracing
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  WC
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              Existing Door
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              To be removed
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              walls made good
   2440




                                      Sleeper Retaining wall
                                      Approx 600 mm high                                                                                                                                                                                                                                                                                                                                                                                                                                                      Existing Stairs
                                      Builder to determine on site                                                                                           Existing Carport Slab




                                                                                                                                                                                                                                                                                                                                         3200
                                                                                                                                                                                                                                                                                                                                                                                                                Existing supports
                                                                                                                                                                             Termite protection to slab joints
                                                                                                                                                                             Termite protected timbers to be                                                                                                                                                                                                                                                                                        1st Level
                                                                                                                                                                                                                                                                                                                                                                                     -
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       2




                                                                                                                                                                                                                                                                                                                                                            Driveway
                                                                                                                                                                             used for framing
                                                                                                                                                                                                     W1 Between Benchtop & wall cabinets                                                                                                                                     NOOSA COUNCIL                                                                                                              1 : 100
          70




                                                                                                                                                                                                     Height to contain full 102 lvrs
               530




                                                                                         Cupboard                                                                                                    close off wall cabinets to upper floor                                                                                                                                 APPROVED PLANS
                           850




                                                                                                                                                                                                                                                                                                                                                                       51983.3225.07 29 MARCH 2017




                                                                                                                                                                                                                                                                                                                                                     6670
          70




                                                                                                                                                                                                               W1
                      90




                                                                                                                                                                                                                                                                                                                                                90
                                                                                                                                                                                                                                                                                                                             600
                                                                                                                                                                                                                                                                                       Window to be as high as possible
                                                                                                                                                                                                                                                                                       Size to be full louvers blades 6 of
                                                                                                                                                                                                                                       BRM                                                                                                                                                                              2065                                                                            5480
                                                                                                                                                                                                              TUB
                                                                                                                                                                                             Drier                           WM




                                                                                                                                                                                                                                                                                       Builder to determine on site
                                                                                                                                                                        D1




                                                                                                                                                                                                                                                                                                                                    70
                                  A                                                                                                                                                                                                                                                                                                                                                                                                                                                       Existing 90 mm SHS posts




                                                                                                                                                                                                                                                                                                                                                            Main
                                                  6 mm villa board to be nail off as




                                  5




                                                                                                                                                                                                                                                                                                                                         2300
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           Existing 100x75 RHS bracing




                                                                                                                                                                                       770
   4230




                                       D2




                                                                                                                                                                                                           Laundry/Bathroom
                                                  bracing sheet for this wall




                                                                                                                                                                                                                                                                                                                                                                                                                                                    Existing 100x75 RHS bracing
                                                                                                                                                                                                                                                      Mechanical Exhaust vent
                                                                                           Proposed Store/Mudroom
               3470




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            Driveway
                                                                                                                                                                                                                                                                                                                                                                                                2435
                           3200




                                                                                                                                                               Proposed Entrance




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                     3290
                                                                                                                                                                                                                                                                                                                             2620
                                                                                                                                                                                                                                    900x900                                                                                                                                                                                                                                                 Existing Carport Area
                                                                                                                                                                                                                                      SHR




                                                                                                                                                                                                                                                                                                                                                90
                                                                                                                                                                                                                                                                                                                                                                                                              Existing 90 mm
                                                                                                                                                                                                                                                                                                                                                                                                              SHS posts
                                                                                                                                                                                               Remove Existing Slab & replace




                                                                                                                                                                                                                                                    New door
                                                                                                                                                       770




                                                                                                                                                                                                                                                                                                                                         810
                                                                                                                                                                                     up                                                                                                                                                                                                                                                                                                                            Existing




                                                                                                                                                                                                                                               D3




                                                                                                                                                                                                                                                                                                                                                                                                                         Cantilevered Deck Over
                                                                                                                                                                                                                    Storage under stairs




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              1580
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   Laundry




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                     2480
                                                                                                                                                                                                                                                                                                                                                90




                                                                                                                                                                                                                                                                                                                                                                                                4235
          90




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         6.1 m²




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            Main
                                                                                                                                                                                                                                                              door to match cladding
                                                                                                    W3                                                                                W2             Existing Stairs to be replaced




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          Exist




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                              900
                                                                                                                                                                                                            with solid risers
 Wall not approved in accordance with condition 4 of the Decision
 Notice                                                                                                                                                                                               Concrete slab under existing stairs                                                                                     Additional Eclosed Area :                  20.5 m²




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                     900
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   up             Existing Open Stairs
                                                                                                                                                                                                      approx 50mm below slab for existing                                                                                     Existing Laundry Area:                      6.1 m²
                                                                                                                                                                                                      room                                                                                                                    Total enclosed Lower Floor:                26.6 m²
                                                                                                                                                                                                                                                                                                                              Total Area Inc. Carport                    45.4 m²                                                                                                        Existing 90 mm SHS posts
                                                                                                                                                                                                      to be removed & replaced to match
                                                                                                                                                                                                      existing Slab Level                                                                                                     Upper Floors not Noted
                                                                                                                                                                                                                                                                                                                                                                                                                        2065                                                            2695                               2785
                                                                                                    3105                                                             1550                                           2625
                                             70                                                                                                         70                            70                                                      90
                                                                                                                                                                 7580
                                                                                                                                                                                                                                                                                                                                                                                                  Existing Ground Floor Plan
                                                                                                                                                                     Ground Floor Plan                                                                                                                                                                                                   3
                                                                                                                                                           1            1 : 50
                                                                                                                                                                                                                                                                                                                                                                                                       1 : 100
                                                                                                                                                                                                                                         Window Schedule                                                                                                                                                                                                                          Door Schedule
     Additional Lower floor addition to be clad with Shadow Clad to match existing external walls & painted the same colour
                                                                                                                                                                                                           Mark Height Width                  Comments                                                                              Location                                       Mark Height Width               Comments                                                              Location                          Lintel        Jamb Studs
                        All dimensions to be confirmed on site to coincide with existing residence                                                                                                           W1        541         610        Louvers/Obs.                                                                      Laund/Bath                                          D1   2040          870                 Entry Door                                                      Entrance
                                                                                                                                                                                                             W2        900         600        Double Hung                                                                        Ent/Stairs                                         D2   2100          1800               Alum Sliding                                                 Store/Mud Room              120x42 Smart LVL           2
                                                                                                                                                                                                             W3        600        1200         Alum Slider                                                                   Store/Mud Room                                         D3   2040          620                  External                                                   Store under Stairs


Client: M & K Himgston                                    Unit 20/30 Hasting St. The Hastings Noosa Heads                                                                                              Wind Classification N3                                                                                                                                                                                                                     Mobile: 0407 693 018                                                              Date    23/03/2017 3:20:20 PM
                                                                                                                                                                                                                                                                                       ACCOLADE Building Designs                                                                                                                                                                                                                    Drawn by: S.Horn Drawn for A3 Sheet
RPD: Lot 20 on GTP 1154                                                                Parish: Weyba                                   County: March              Site Area : 106 m²                                                                                                                                          Proprietor: Steven Horn                                                     Email: [email protected] Project Number
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            1016HMK
Proposed Partial Enclosure of Ground Level Under Existing Unit                                                                                                                                                                                                                                                                   QBSA Lic. 54806                                                          Issue Date                                                               23 - March - 2017                                     Sheet No. 3                   of    6

The text continues on section 19.

Used in these records

About this file

File size
8.5 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Compiled Approved Plans 51983.3225.11.pdf · 8.5 MB (large file)