Part RFI - Effluent Disposal Report

of 11

Page text shows just the words. Original shows the document exactly as it was published.

Page text read automatically using OCR, there may be inaccuracies

                                                                            QBCC Licence No.1018403

            THE ONLY NAME IN SOILS                 UNIT 3/53 GATEWAY DR, NOOSAVILLE , 4566

                                   Ph.0754740900/ Fax.0754740901/ email: [email protected]

JOB NUMBER    20/0668    EFFLUENT DISPOSAL REPORT
CLIENT        DONOVAN BISS
SITE LOCATION PROPOSED STUDIO AND PROPOSED RESIDENCE,
              503 MIDDLE CREEK ROAD, FEDERAL.
REPORT DATE   27/10/2020



1.   INTRODUCTION

     The purpose of this report is to evaluate and define a suitable on-site sewerage treatment and
     disposal system for household effluents in accordance with Australian Standard 1547 -
     2012“On-site domestic-wastewater management”. The Qld Plumbing & Wastewater Code-2019
     has been used for reference purposes during the compiling of this report.

     This report relates exclusively to the proposed studio and proposed residence at 503 Middle
     Creek Road, Federal. This document has been prepared for the express purpose stated above.
     This document does not cover any other elements related to construction on the site.


2.   SITE DESCRIPTION AND WEATHER CONDITIONS

     The site is an acreage allotment, which fronts a sealed road.
     The slope configuration in relation to surface drainage is linear planar.
     The soil surface condition was moist at the time of testing. There was no evidence of cracking
     of the surface during the investigation.
     The site has no visible rock outcrops on the surface of the allotment.
     The proposed effluent disposal area is exposed to sun and wind.
     The proposed effluent disposal area is well grassed. The proposed effluent disposal area is
     approximately level. Surface water drainage from adjoining allotments will not traverse this site.
     Surface water from the tested area will drain towards the rear.
     The weather conditions prior to testing were periods of moist conditions.
     The site has a Creek 12m downhill from the proposed effluent disposal area.

3.   SOIL PROFILE

     The borelogs carried out at the site, refer attached Site Plan for localities, indicate that the soil
     profile typically consists of a moist, brown, medium plasticity SANDY CLAY. Underlying this
     is a moist, brown, high plasticity SANDY CLAY.
     Groundwater was not encountered during the field investigation.
     Rock was not encountered during the field investigation.

     RESERVE AREA

     A 100% reserve effluent disposal area can be obtained on this allotment.



     Whilst every effort has been made to ensure that the borelogs carried out at the subject allotment
Log in to download the original file

Part RFI - Effluent Disposal Report.pdf · 356 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 10 pages

Page 2

     are indicative of the soil profile over the site any discrepancy between the profile detailed in the
     borelogs and that observed during construction shall be referred to Global Testing for
     immediate attention.

4.   INVESTIGATION DETAILS

     The investigation carried out at the site included machine augered boreholes up to 2000mm
     depth and a series of three permeability test pits located as shown on the attached site report.
     All testing carried out was in accordance with Australian Standard 1547 - 2012 “On-site
     domestic-wastewater management”.


5.   TEST RESULTS AND CONCLUSIONS (TABLE A1)
      Test No.  Soil           Slope Setback   Recommended                                  Beavers
                Permeability   (m/m) Distance Design Irrigation                             Gardner
                (based on test       (m)       Rate (mm/Day)                                Setback
                results)Ksat                   As per AS/NZS                                Distance
                                                 1547-2012
      PT 1           0.09
      PT 2                   0.08
      PT 3                   0.08
      Average                0.08            .0            10*               3                  1m

     *Minimum setback distance from a watercourse (when an Advanced Secondary ASTP is
      recommended) required by Noosa Council Policy.

     Determination of Soil Category (Table 5.1 of AS/NZS 1547:2012)
       Soil Category         Soil Texture         Structure          Indicative          Indicative
             BH5                                                    Permeability       Drainage class
                                                                    (ksat)(m/day)
              5               Light Clays          Moderately        0.06 to 0.12      Poorly Drained
         (00-300mm)                                Structured
              6              Medium to             Moderately           < 0.06           Very Poorly
        (300-2000mm)         Heavy Clays           Structured                             Drained

     The Design Irrigation Rate of 3mm/day was adopted from the above results in Table A1.

     Noosa Council’s policy suggests that the use of a primary treated effluent disposal system
     will be satisfactory provided;
        # Sufficient permeable surface soil overlying rock is present over the disposal area, not
          less than 1.2metres depth.
        # A suitable soil category material (as per AS1547-2012) is encountered.
        # A Minimum set-back distance of 50m is obtained.
        # Permeability rates are within the required parameters.
     Not all the above requirements have been met, therefore it is concluded that the use of a
     primary treated effluent disposal system is not acceptable.




                                        Report 20/0668 edr page2

Page 3

6.      RECOMMENDATIONS
         The Design Irrigation Rate of 3mm/day be adopted.
         The site be provided with an “Aerated wastewater-treatment system” capable of
          producing Advanced secondary effluent (e.g Taylex ABS), or an equivalent system, to
          council’s approval in lieu of a septic tank. A Macerator Pump will be required for the
          proposed studio.
         The disposal system be by, # A Covered surface drip irrigation system consisting of
          ‘Wasteflow or Netafim’ Pressure-Compensating Drippers, as per AS/NZS
          1547:2012.
         Purple line is to be used from the ASTP to the irrigation area.
         An in-line filter is to be installed between the Treatment Plant and the Irrigation System.
          Regular maintenance of the Filter shall be undertaken, according to manufacturer’s
          recommendation.
         An 150mm high diversion bank/border shall be constructed around the irrigated
          area.
         The dripper system shall evenly distribute effluent to avoid clogging by soil or root
          intrusion. Maximum spacing shall be 1000mm.
         Non-return valves and flush-out valves should be installed on irrigation lines. The
          minimum required amount of effluent to be pumped at regular intervals, should be such,
          that all irrigation lines are full, and effluent delivered equally.
         The Wasteflow/Netafim lines are to be placed on the surface, with a 150mm layer of
          mulch placed over the irrigation lines. Evergreen plants are to be planted (32 plants
          minimum) to maximize evapo-transpiration.
         The disposal area required is 320m2.
          This area has been calculated on a daily flow rate of 960 litres/day (8 people @120L per
          person/ per day) and a design irrigation rate of 3mm/day.
          This flow rate will accommodate the proposed 4 bedroom residence & studio only. A
          100% reserve area (as per site plan) is to be-kept free of buildings and traffic.
         The disposal area should be located in the vicinity of PT 1, PT 2 and PT 3 as per
          attached site plan.
         All set-back distances as required by the local authority shall be met;

        . Stormwater run-off including roof-water from buildings shall be diverted around and away
           from the disposal area. Imported fill may be required should there be insufficient soil
           available for the design of the disposal system.
Certification
The local authority may request that an inspection and certification is undertaken on the installation
of the system when nearing completion. The installer must contact Sunshine Coast Council prior to
‘burying’ the system, if certification is required.
          Please note: Personal Hygiene Products, Bleaches and detergents high in phosphorous will
          damage the capabilities of the Treatment System’s performance. Information should be
           sought by the Treatment System’s manufacturer for a guide of suitable products acceptable
           for the system.
Yours Sincerely,




Michael S. Pinkney (Laboratory Manager)
                                         Report 20/0668 EDR-page3

Page 4

                   THE ONLY NAME IN SOILS

SOIL PROFILE REPORT
CLIENT:               Donovan Biss.                          AUTHORIZED                Donovan Biss.
                                                             BY:
PROJECT:              503 Middle Creek Road,                 DATE TESTED:              11/08/2020
                      Federal.                               JOB NO:                   20/0668

                        Drilling Method: Jacro 105 100mm                                          Borehole
                                                                                                   No: 5
   Depth            Description                                                  PENET.          Comments
                                                                                (blows per
   (mm)                                                                          100mm)
                                                                            1      2    3    4
       0            SANDY CLAY (CI) Medium plasticity,
                    pale brown, fine to coarse sand, moist,
                    stiff.
     100
     200
     300            SANDY CLAY (CH) High plasticity,
                    pale brown/grey, fine to coarse sand,
                    moist, stiff.

      400
      500
      600
      700
      800
      900
     1000
     1100
     1200
     1300
     1400
     1500
     1600
     1700
     1800
     1900
     2000           HOLE TERMINATED.
     2100
     2200
     2300
     2400
     2500
Borelogging in accordance with AS1726-1993 Site Investigation Code

                                                       20/0668 edr Page 4

Page 5

                     THE ONLY NAME IN SOILS


SOIL PROFILE REPORT
CLIENT:               Donovan Biss.                          AUTHORIZED                 Donovan Biss.
                                                             BY:
PROJECT:              503 Middle Creek Road,                 DATE TESTED:               11/08/2020
                      Federal.                               JOB NO:                    20/0668

                        Drilling Method: Jacro 105 100mm                                           Borehole
                                                                                                    No: 6
   Depth            Description                                                   PENET.          Comments
                                                                                 (blows per
   (mm)                                                                           100mm)
                                                                             1      2    3    4
       0            SANDY CLAY (CI) Medium plasticity,
                    pale brown, fine to coarse sand, moist,
                    stiff.

     100
     200
     300            SANDY CLAY (CH) High plasticity,
                    pale brown/grey, fine to coarse sand,
                    moist, stiff.

      400
      500
      600
      700
      800
      900
     1000
     1100
     1200
     1300
     1400
     1500
     1600
     1700
     1800
     1900
     2000           HOLE TERMINATED.
     2100
     2200
     2300
     2400
     2500
Borelogging in accordance with AS1726-1993 Site Investigation Code
                                                        20/0668-edr Page 5

Page 6

                  THE ONLY NAME IN SOILS



SOIL PROFILE REPORT
CLIENT:               Donovan Biss.                          AUTHORIZED                 Donovan Biss.
                                                             BY:
PROJECT:              503 Middle Creek Road,                 DATE TESTED:               11/08/2020
                      Federal.                               JOB NO:                    20/0668

                        Drilling Method: Jacro 105 100mm                                           Borehole
                                                                                                    No: 7
   Depth            Description                                                   PENET.          Comments
                                                                                 (blows per
   (mm)                                                                           100mm)
                                                                             1      2    3    4
       0            SANDY CLAY (CI) Medium plasticity,
                    pale brown, fine to coarse sand, moist,
                    stiff.

     100
     200
     300            SANDY CLAY (CH) High plasticity,
                    pale brown/grey, fine to coarse sand,
                    moist, stiff.

      400
      500
      600
      700
      800
      900
     1000
     1100
     1200
     1300
     1400
     1500
     1600
     1700
     1800
     1900
     2000           HOLE TERMINATED.
     2100
     2200
     2300
     2400
     2500
Borelogging in accordance with AS1726-1993 Site Investigation Code
                                                        20/0668-edr Page 6

Page 7

* DO NOT Allow newspapers, disposable or sanitary napkins, rubber products,
         nappy liners, cotton buds etc. to enter the system.



* DO NOT Use an in-sink garbage grinder. These are not recommended by most
         councils as they can add extra loading equivalent to about 2 persons.



* DO NOT Use strong caustics, acids, alkalis or chemical detergents. These can
         damage the system and cause bad odours.




* DO NOT Use disinfectants or other bactericides.



* DO NOT Put grease/fats or food scraps down the kitchen sink i.e plates should be
         scraped resonably clean prior to washing up.


* NEVER       Dispose of used cooking oil or similar material down the sink.




                                     20/0668 edr Page 7

Page 8

               LIMITATIONS AND ADDITIONAL NOTES

1. A Site Classification Report may be requested by Certifiers or Local Council to aid in
   approval of this report regarding articulation, if the site is suspected of being classified as H,
   E or P in accordance with AS2870. Global Testing should be contacted to undertake this
   testing (additional charge applies), if not previously requested. This Effluent Disposal
   Report does not address articulation or flexible joints (an RPEQ should be sought if design
   of either of these is required- additional charges apply).
2. If any future amendments are required due to the movement of the building footprint,
   amount of bedrooms, on-site earthworks, or requests for an alternative area or alternative
   system, an additional charge of $330 will apply to complete an updated Effluent Disposal
   Report.
3. Global Testing has completed this report based on plans and information as supplied by the
   client.
4. Any levels or slope measurements within this report are approximate only, and should not be
   used for construction purposes.



                                         20/0668 edr Page 8

Page 9

Job No: 20/0688    Date Tested: 08/08/2020     Site : 503 Middle Creek Road, Federal Client : Donovan Biss SCALE 1:500




                                                                                           Proposed Advanced Secondary ASTP
                                                                                           (To be installed)
                             Proposed Macerator Pump
                             (To be installed)



                                                                                                   12m
                                                                                       30m
                  Proposed Studio
                                                                          10.6m
                                                              BH1
                                                                              16%            BH6
                                                                                 BH5
                                                              PN1       10m   Slope
                                                                                 PT1
                                                                                             PT2


                                                                                                   BH3
                                                                    BH2                            PN3
                                                                    PN2
                                                                                                            BH4
                                                                3%                                          PN4
                                                                Slope


                                                                                              Proposed Residence




                                                                                       Proposed Covered Surface Drip Irrigation
                                                                                       Area - 320m2
                                                                                       (To be planted out (minimum 32 plants),
                                                                                        mulched, bordered and installed)
                                                                                       Wasteflow or Netafim Pressure-
                                                                                       Compensating Dripper lines to be used)

Page 10

                    Covered Surface Drip Irrigation System
                             (32 plants)
150mm cover of mulch         Plant surface          1000mm max. Spacing


Ground Level




                                  Netafim or Wasteflow Pressure Compensating Dripper Lines
                                             Place on surface and cover with 150mm mulch.

150mm high mound surround




                       Diversion drain
                                         or Cut off drain         Irrigation lines




                       Slope greater than 15%

                                  Typical Plan Layout of Manifold and Laterals for an
Netafim or                                   Irrigation Area of 320m2
Wasteflow Pressure
Compensating Dripper
Lines
                                                            1m
To Advanced Secondary
ASTP

                          10.6m




          Flush-out Valves


                                                                 30m

Page 11