In reply please refer to: Our Ref: SC-8218 Your Ref: MCU21/0033 18th May 2021 Noosa Council PO Box 141 Tewantin QLD 4565 Attention: Tara Norley RE: Response to Information Request MCU21/0033 Proposed Unit Development at 31 Bottlebrush Ave, Noosa Heads Dear Tara, In response to Council’s Further Advise Notice dated 7th April 2021, we provide the following further information. Item 15 and 16 By adopting the revised design, we certify that a B99 vehicle can enter and exit the site in a forward direction without scraping or bottoming out on the driveway and/or the road formation as modelled on Empire Engineering Civil Design (SC-8839). Item 17.1 A 10kL stormwater detention tank has been provided as sized and described in the Site Based Stormwater Management Plan as attached, discharging peak flows at a mitigated flow rate to the kerb and channel. Item 17.2 The existing upstream overland flow path has been diverted within the site, around the proposed unit development, directed down the south eastern property boundary. This was achieved by utilising the adequately sized Vantage Pipe ‘Vspoodrain’ product as seen on Empire Engineering Plans Drawing Number C003, before discharging to the kerb and channel via 2/100mm pipes. We trust the above response satisfies Council requirements in relation to this matter. Should you have any further queries, please contact the undersigned at our Sunshine Coast office. Yours faithfully Sean Dwyer Civil Engineer BE(Civil), M.I.E Aust, CPEng, RPEQ17012 For and on behalf of EMPIRE ENGINEERING Pty Ltd
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original (Engineering IR Response.pdf)
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.
Full text of the other 13 pages
Page 2
In reply please refer to:
Our: Troy Paulsen
At: Sunshine Coast
Our Ref: SC-8839
18th May 2021
Noosa Shire Council
PO Box 141
Tewantin QLD 4565
RE: SITE BASED STORM WATER MANAGEMENT PLAN FOR PROPOSED
APPARTMENTS AT 31 BOTTLEBRUSH AVE, NOOSAVILLE
1. INTRODUCTION
The proposed development consists of a multi-apartment development and associated car
parking. The site is fronting Bottlebrush Ave to the South West and existing residential
allotments to the remaining boundaries. The site is currently occupied by a single two story
residential dwelling with its associated access driveway. The total site area is 506m 2 and has an
approximate fraction impervious of 46% (Fi = 0.46).
2. STORMWATER CONNECTION
Under existing conditions, stormwater runoff discharges to the kerb and channel fronting the
subject site, before falling to the North West before flowing into the existing 300mm diameter
underground stormwater network. The proposed stormwater will continue to discharge into the
Bottlebrush Ave kerb and channel in accordance with local council’s discharge flow rates of
maximum 25L/s.
3. STORMWATER QUANTITY
The proposed development will increase the impervious nature of the site compared to pre-
development to a fraction impervious of 80% (Fi = 0.80). Therefore, peak flow mitigation is
proposed to limit minor and major flows (50%, 20%, 10%, 5%, 2% & 1% AEP), to that of the
pre-development scenario to ensure the downstream pipe capacity is not worsened.
Page 3
Detention will be incorporated in the post-development scenario for the minor events that will
discharge into the existing kerb and channel. XP-STORM V2017.2 was used to determine the
detention volume required and the results are illustrated in Table 1.1. Table 1.1 illustrates that
10kL of detention with two 100mm diameter outlet mitigates the minor event discharge to less
than the required 25L/s flow rate and less than the pre-development scenario.
A concept stormwater management plan has been provided in Attachment 1, and hydrographs
have been attached in Attachment 2.
AEP (ARI) Pre-Development Post-Development Peak
Peak Flows Flows (Mitigated)
50% (2yr) 0.024 0.015
20% (5yr) 0.033 0.018
10% (10yr) 0.043 0.020
5% (20yr) 0.049 0.021
2% (50yr) 0.046 0.023
1% (100yr) 0.051 0.025
Table 1.1 – Pre vs Post Development Discharge
Page 4
Subject Site:
31 Bottlebrush Ave,
Noosaville
N
Figure 1.1 Site Location
Should you have any further requirements in relation to the above matters, please contact the
undersigned.
Yours Faithfully,
Troy Paulsen
RPEQ No. 6990
For and on behalf of
Empire Engineering Pty Ltd
Page 5
ATTACHMENT 1: Concept Stormwater Management Plan [OCR of page images] ATTACHMENT 1: Concept Stormwater Management Plan td te bbb beg ed OPLETETTELELTTELL EDIE by OCELELLEEELELELEELELELEA EEL EDEL ‘Fi COLELELELEELELELELEELETEDELLTLELELEEE PAGE OLEULLLELEELELELELEELELELELLELELEED tt tt Fi AOLELELEELELELELEELELELELEE ED CL IELELEELELELEELELEE LGD ELEE tes CbEttE ELS tH: Clipe ch ti tests et ttt tt ér be A ‘C4 COCEELELEEE LET: AOL EDELLTLELEELEL ELLE EES ‘t OLE AIEEE EE: tht eg ‘onee, ee eee tts tilt tt tt tt LETHE ELE sthtirlbistttttbheg OCPEEE, bP IEEE DRL ETE tts SPbEt tty 2 > ‘te Post Outlet >
Page 6
ATTACHMENT 2: Hydrographs
Pre-Development
Post-Development
[OCR of page images]
ATTACHMENT 2: Hydrographs
Node - Pre-Development
= = =
ECN_50Opct_15min_2[Max 0.024] ECN_20pct_15min_2[Max 0.033] ECN_10pct_30min_3[Max 0.043]
ss = =
ECN_5pct_30min_3[Max 0.049] ECN_2pct_30min_6[Max 0.046] ECN_1pct_30min_6[Max 0.051]
0.050
0.045
0.040
0.035
> 0.030
So
it 0.025
0.020
0.015
0.010
0.005
0.000
Fri 0:30 1:00
Jan 2016 Time
Pre-Development
Conduit 2/100mm Dia from 10kL Tank to Post Outlet
= = =
ECN_SOpct_15min_10[Max 0.015] ECN_20pct_15min_10[Max 0.018] ECN_10pct_30min_3[Max 0.020]
= — —
ECN_5pct_30min_3[Max 0.021] ECN_2pct_30min_6[Max 0.023] ECN_1pct_30min_6[Max 0.025]
0.025
0.020
0.015
&
we
0.010
0.005
0.000
Fri 0:30 1:00
Jan 2016 Time
Post-Development
Page 7
ATTACHMENT 3: Vantage Pipes - Technical Manual V Spoon Drain [OCR of page images] ATTACHMENT 3: Vantage Pipes - Technical Manual V Spoon Drain
Page 8
Technical
Manual
May 2016
VSpoonDrain™
TM
[OCR of page images]
™
Vantage
Page 9
1.0 Introduction Looking for a quick solution to forming open channel Applications: drains? Using VantagePipes™ VSpoonDrain™ Open Back of barrier drainage for retaining walls Channel Drainage as a permanent formwork allows for Channel drains alongside hardstand areas, grated rapid construction with minimal hand finishing of placed covers can be used if desired concrete. Available in sizes from 225 up to 750mm, An easy method for forming an open drain into there is a size to suit any application. concrete slabs. Benefits: Available in standard 4m lengths, VSpoonDrain allows Rapid setup of forms and location braces rapid installation and cost savings for open channel Easy placement of backfill concrete with minimal drains. labour required Minimal finishing of backfill concrete Smooth, aesthetically pleasing and hydraulically efficient finished surface. Notes: VSpoonDrain can be cut to any custom length and butt jointed Join VSpoonDrain to the next adjacent length by simply placing end to end, so that the specially grooved ends are mated in a rebate joint. Fill any gaps between spoon drain lengths using a flexible mastic VSpoonDrain is not suitable for areas subject to traffic loads. 2 Technical Manual - VSpoonDrain™ [OCR of page images] Looking for a quick solution to forming open channel drains? Using VantagePipes™ VSpoonDrain™ Open Channel Drainage as a permanent formwork allows for rapid construction with minimal hand finishing of placed concrete. Available in sizes from 225 up to 750mm, there is a size to suit any application Benefits: Rapid setup of forms and location braces Easy placement of backfill concrete with minimal labour required Minimal finishing of backfill concrete Smooth, aesthetically pleasing and hydraulically efficient finished surface Notes: VSpoonDrain can be cut to any custom length and butt jointed Join VSpoonDrain to the next adjacent length by simply placing end to end, so that the specially grooved ends are mated in a rebate joint. Fill any gaps between spoon drain lengths using a flexible mastic VSpoonDrain is not suitable for areas subject to traffic loads. Applications: Back of barrier drainage for retaining walls Channel drains alongside hardstand areas, grated covers can be used if desired An easy method for forming an open drain into concrete slabs. Available in standard 4m lengths, VSpoonDrain allows rapid installation and cost savings for open channel drains. 2 Technical Manual - VSpoonDrain™
Page 10
2.0 Design & Installation
2.1 Design
Simple, easy to use VantagePipes™ VSpoonDrain™ almost
VSpoonDrainTM
designs itself. Typically backed by a 15-20MPa mass concrete
support, the VSpoonDrain acts as a permanent formwork
for the smooth drainage channel providing quick and easy Masonry Anchor
installation.
In most cases reinforcing mesh is not required, however this
should be checked by an appropriately qualified person for
site specific requirements.
Embankment VSpoonDrainTM Retaining Wall
Formwork
Concrete Plinth
Concrete Plinth Option
Concrete plinth poured and set to reqd level in advance
(2 per length)
Reinforcing
Mesh (if required)
VSpoonDrain secured to plinths using required masonry
15-20MPa
anchors
Mass Concrete Masonry anchors left in position after concrete curing.
Threaded rod
Typical back of barrier installation Timber
hanger
2.2 Installation
Install side forms if required and VSpoonDrain hangers
Position and secure the VSpoonDrain (see possible setup
diagrams below)
VSpoonDrain can be cut to any required length and
angles and butt jointed
Join VSpoonDrain to the next adjacent length by simply
placing end to end, so that the specially grooved ends are
mated in a rebate joint
Fill any gaps between VSpoonDrain lengths using a
flexible mastic
Formwork
Cover the VSpoonDrain using a piece of form ply to
prevent concrete spills into the VSpoonDrain channel VSpoonDrain TM
during pouring
Place concrete and trowel finish edges flush with the top
edge of the VSpoonDrainchannel Timber Hanger Option
After suitable curing time has elapsed, remove formwork Timber hanger fabricated and attached to VSpoonDrain
and braces and plug any remaining holes with a suitable with threaded rod (2 per length)
urethane or grout filler material. VSpoonDrain and hangers positioned and secured to
framework
Threaded rod removed and hole filled after concrete
curing.
Technical Manual - VSpoonDrain™ 3
[OCR of page images]
2.1 Design
Simple, easy to use VantagePipes™ VSpoonDrain™ almost
designs itself. Typically backed by a 15-20MPa mass concrete
support, the VSpoonDrain acts as a permanent formwork
for the smooth drainage channel providing quick and easy
installation.
VSpoonDrain"™
Masonry Anchor
In most cases reinforcing mesh is not required, however this
should be checked by an appropriately qualified person for
site specific requirements.
VSpoonDrain™ Retaining Wall
Embankment
Formwork
Concrete Plinth
Concrete Plinth Option
Concrete plinth poured and set to reqd level in advance
(2 per length)
Re |e
ren rare VSpoonDrain secured to plinths using required masonry
anchors
Masonry anchors left in position after concrete curing.
15-20MPa
Mass Concrete
Threaded rod
Typical back of barrier installation Timber
hanger
2.2 Installation
Install side forms if required and VSpoonDrain hangers
Position and secure the VSpoonDrain (see possible setup
diagrams below)
VSpoonDrain can be cut to any required length and
angles and butt jointed
Join VSpoonDrain to the next adjacent length by simply
placing end to end, so that the specially grooved ends are
mated in a rebate joint
Fill any gaps between VSpoonDrain lengths using a
flexible mastic
Cover the VSpoonDrain using a piece of form ply to
prevent concrete spills into the VSpoonDrain channel
during pouring
Place concrete and trowel finish edges flush with the top
Formwork
VSpoonDrain™
edge of the VSpoonDrainchannel Timber Hanger Option
After suitable curing time has elapsed, remove formwork Timber hanger fabricated and attached to VSpoonDrain
and braces and plug any remaining holes with a suitable with threaded rod (2 per length)
urethane or grout filler material VSpoonDrain and hangers positioned and secured to
framework
Threaded rod removed and hole filled after concrete
curing
Technical Manual - VSpoonDrain™
Page 11
Fast. Smart. Proven. Strong. 1800 659 850 | VantagePipes.com.au COPYRIGHT MAY 2016 © FRCPA PTY LTD t/as VantagePipes ABN 64 605 089 941 05/16
Page 12
ATTACHMENT 4: Vantage Pipes - V Spoon Drain Calculations [OCR of page images] ATTACHMENT 4: Vantage Pipes - V Spoon Drain Calculations D = 300 = 150 = 0.013 S= 0.015 Surface Width (a) = 300 P= 471.2389 Height over CL (b) = 0 angle = 0 included angle = 180 Area= 35342.92 R= 75 Vel= 1.677908 Flow (Q) = 59
Page 13
ATTACHMENT 5: Stormwater Management Plan [OCR of page images] ATTACHMENT 5: Stormwater Management Plan
Page 14
LEGEND
VISITOR
UPSTREAM OVERLAND FLOW
PATH CALCULATIONS
SITEWORKS LAYOUT PLAN
Project North:
N
Scales:
0 1 2 3 4 5m 1:100 at A1
A
1:200 at A3
SECTION SECTION
Status:
NOTES Client: COLE PROJECTS Designed: SFD Drawn: AJP Title: Date: MAY 2021 Scale: AS NOTED
Issue Amendment Date Dft 1. This is the property of the engineer, and may not be Sunshine Coast Office Bundaberg Office
A
B
FOR APPROVAL
FOR APPROVAL
14.05.21
17.05.21
AJP
AJP
used, copied, or reproduced wholly, or in part without the
express permission of the engineer. Infringement in any
L2, 13 Norval Court Maroochydore Q 4558
PO Box 102 Mooloolaba Q 4557
66A Barolin Street Bundaberg Q 4670
PO Box 2052 Bundaberg Q 4670
Project: PROPOSED APARTMENT DEVELOPMENT Approved: STORMWATER MANAGEMENT PLAN Job Ref No: Drawing No: Issue:
C FOR APPROVAL 18.05.21 AJP way may result in legal action.
Engineering P: 07 5477 6437 P: 07 4154 4894 31 BOTTLEBRUSH AVENUE,
2. Figured dimensions take precedence over scaled.
3. Verify all dimensions on site. ACN 112761510 ABN 21112761510
E: [email protected] E: [email protected]
NOOSA HEADS TROY PAULSEN / RPEQ: 6990
SC-8839 C003 C