Log in to see the plans as drawn 4. Design 4.3 BYPASS
The SPELBasin® system is designed for flows that
exceed the design treatment flow rate (TFR) to be
Unlike traditional biofilter design, it is not necessary to bypassed externally. This is typically achieved by
utilise drainage, transition and filter media layers. The ensuring that when the inlet cannot carry any additional
SPELBasin® system is delivered with the proprietary flow, flow is re-directed to a nearby/adjacent inlet pit.
media pre-mixed ready for installation into the If the SPELBasin® requires an underground pipe inlet
prefabricated chamber. Of importance, however, is that type, the bypass can be formed into the inlet chamber,
the geotextile protecting the outer geogrid and internal or as a separate pit.
collection pipes is not damaged during the media
installation. 4.4 INLET AND OUTLET CONFIGURATIONS
4.1 OUTLET INVERT LEVEL (SATURATED ZONE) Multiple configurations are possible with the
SPELBasin® depending on the site constraints. Some
The SPELBasin® system is designed to accommodate examples are indicated below.
up to 300mm reservoir of water as a saturated/
anaerobic layer at the bottom. The levels from this
outlet to the receiving drainage network should be
checked to ensure the outlet is free-draining.
As a secondary guide, the Facility for Advancing Water
Biofiltraton (FAWB, 2009) recommend calculating the
saturated zone with the following equation;
D = 8x t
Where: D = depth of saturated zone (mm)
t = average of the longest annual dry period
(days)
This level tends to determine the inlet level that runoff
can enter the SPELBasin®.
4.2 INLET INVERT LEVEL & TYPE
The inlet level of the SPELBasin® system depends on
the type of inlet structure;
• Kerb inlet;
• Grated inlet; and/or
• Pipe inlet.
Kerb and grated inlets have up to 150 mm of flexibility
to match with surface levels. This also enables up to
150mm of extended detention within the SPELBasin®
system.
Piped inlets have ~600 mm of flexibility to ensure the FIGURE 5.
SPELBASIN® INLET AND OUTLET CONFIGURATIONS
inlet pipe and outlet discharge to a free water surface.
The exact dimensions will depend on the inlet pipe
diameter, depth/cover and class.
6 Technical Design Guidelien SPELBasin