Site Catchment Areas for DRAINS Modelling
Project number:    20220078                                       Calculations:                         B. Parry
Street Address:    6 Wyandra Street
Locality:          Noosa Heads, Noosa Shire Council               Date:                                 24/06/2022


Existing Site
                                         Existing Site            Directly connected (m²)               Indirectly connected (m²)
Wyandra St         Roof                                   172.5                                 172.5                                      0
                   Impervious Ground                      67.38                                     0                                  67.38
                   Driveway                               64.47                                     0                                  64.47
                   Total Imp                             304.35
                   Total Per                             293.65
                   Site Area                                598

% impervious                                                      Effective DCIA = 75% DCIA             ICIA +25% ineffective DCIA
                                                                                              129.375                                174.975
                   Impervious                            50.9%                                  21.6%                                  29.3%
                   Pervious                              49.1%




Proposed Site
                                         Proposed                 Directly connected (m²)               Indirectly connected (m²)
Wyandra St         Roof                                   282.9                                 282.9                                      0
                   Impervious Ground                     113.61                                 47.14                                  66.47
                   Driveway                               53.21                                     0                                  53.21
                   Total Imp                             449.72
                   Total Per                             148.28
                   Site Area                                598

% impervious                                                      Effective DCIA = 75% DCIA             ICIA +25% ineffective DCIA
                                                                                               247.53                                 202.19
                                                         75.2%                                  41.4%                                  33.8%
                                                         24.8%

Used in these records

About this file

File size
3.2 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

SWMP.pdf · 3.2 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.