NOOSA COUNCIL EQUIPMENT SCHEDULE
APPROVED PLANS LOCATION
STN
No
SITE I.D. EXIST REC INSTALL SIZE & DESCRIPTION IIN COMP ID
PLANT
No.
MODEL ID QTY LCC REMARKS
OPW20/0145.01 25 FEB 2021 WALTER HAY DR 3 U2220500 * C + I PILLAR CI1 LVLP400CFS 1
URD CIVIL WORKS SCHEDULE (ROAD CROSSINGS) * S/L FUSE ASSY801-1 1
* S/L FUSE HOLDER ASSY1043-3 1
CONDUIT LENGTH (m) BENDS (<°/No) X-SECTION (m) * EARTH ASSY1037-1 1
STATIONS DRAW KERB
LOCATION EXCAV/ COVER TRENCH WIRE REMARKS
FROM-TO 40 No 100C No 100 No 125 No 40 No 100C No 100 No 125 No MARK 4 - * TYPE 4 S/L PIT & JUNCTION BOX (FUSED) ASSY831-1 1
TAPE STRIP DETAIL
7 U761293 * * EXISTING SUPPLY PILLAR PI1 EX. EX. MAKE 3-WAY
WALTER HAY DR 2 - 3 30 1 30 1 30 4 SP1 180 2 BY UNDERBORE
* PHASE BAR 06508 4 DISCONNECT EARTH
4 - 5 25 1 25 1 25 4 25 SP2 150 2
* M12 x 50mm 00413 4
PRIVATE RD 19 - 20 45 1 45 1 45 4 45 SP2 270 2 IN 1.2m EGX EASEMENT
* 240 LUG SET LVSPL240 1
22 - 23 35 1 35 2 35 4 35 SP3 245 2 IN 1.2m EGX EASEMENT
* 185 LUG SET LVSPL185 1
25 - 26 30 1 30 1 30 4 30 SP2 180 2 IN 1.2m EGX EASEMENT
9 U2220501 * 11kV STRAIGHT JOINT SJ1 11ST24/24X 1
27 - 28 25 1 25 1 25 4 25 SP2 150 2 IN 1.2m EGX EASEMENT
10 U2220502 * 11kV STRAIGHT JOINT SJ1 11ST24/24X 1
30 - 32 35 1 35 1 35 4 35 SP2 210 2 IN 1.2m EGX EASEMENT
12 LP2220504 * LINK PILLAR (185-240 7F) LP1 LVSP14-6 1
HOFMANN DR 33 - 37 45 1 45 1 45 1 45 4 45 SP2-SL 315 2
* 185 LUG SET LVSPL185 1
42 - 43 25 1 25 O 25 2
* S/L FUSE ASSY801-1 1
45 - 52 30 1 30 1 30 4 30 SP3 180 2
* S/L FUSE HOLDER ASSY1043-3 1
55 - 56 20 1 20 O 20 2
* EARTH ASSY1037-1 1
60 - 61 25 1 25 1 25 4 SP1 150 2 BY UNDERBORE
14 SC2220505 * 500kVA PADMOUNT TRANSFORMER TR1 S25118 1
PRIVATE RD (SOUTH) 38 - 39 25 1 25 1 25 4 25 SP2 150 2
* CULVERT & BASE C&B 1
49 - 50 25 1 25 1 25 4 25 SP2 150 2
* PMT INSTALLATION PMTINSTALL 1
TOTALS 90 375 410 1500 365 2375 28
* PMT COMMISSION PMTCOM 1
* HV FUSES DSHVF5SLK 1
URD CIVIL WORKS SCHEDULE (ALONG FOOTPATHS)
* LV FUSES DSLVF31 3
CONDUIT LENGTH (m) BENDS (<°/No) X-SECTION (m) * HV TERMINATIONS 2DBSTA24D 2
STATIONS DRAW KERB
LOCATION EXCAV/ COVER TRENCH WIRE REMARKS * LV TERMINATIONS LTSA24D 3
FROM-TO 40 No 100C No 100 No 125 No 40 No 100C No 100 No 125 No MARK
TAPE STRIP DETAIL * COMMON EARTHING DSSQPMCEG 1
WALTER HAY DR 3 - 4 30 1 30 1 30 1 30 4 30 SP2-SL 210
15 SC761294 * 500kVA PADMOUNT TRANSFORMER TR1 1
4 - 3L 5 1 5 O 5
* LV FUSES DSLVF31 2
7 - 14 10 1 10 2 10 4 10 SP3 70
* LV TERMINATION LTSA24D 2
15 - 35 20 1 20 2 20 4 20 SP3 140 TYPE 4 S/L PIT & JUNCTION BOX (FUSED)
17 - * PT1 ASSY831-1 1
34 - 35 15 1 15 2 15 4 15 SP3 105 NON-STANDARD ALIGNMENT
72 U761295 * EXISTING SUPPLY PILLAR PI1 EX. EX. DISCONNECT EARTH
72 - 73 35 1 35 1 35 4 35 SP2 210
* PHASE BAR 06508 4 MAKE 3-WAY
17 - 17L 5 1 5 O 5
* M12 x 50mm 00413 4
PRIVATE ROAD 14 - 22 80 1 80 2 80 4 80 SP3 560 IN 1.2m EGX EASEMENT
* 240 LUG SET LVSPL240 1
21 - 30 370 1 370 1 370 4 370 SP2 2220 IN 1.2m EGX EASEMENT SUPPLY PILLAR (240-240-240 6F)
PRIVATE RD 19 U2220506 * PI1 LVSP9-6 1
30 - 40 20 1 20 1 20 1 20 4 20 SP2-SL 140 IN 1.2m EGX EASEMENT
8 U2220503 * C + I PILLAR CI1 LVLP400CFS 1
31 - 32 30 1 30 1 30 4 30 SP2 180 IN 1.2m EGX EASEMENT
* EARTH ASSY1037-1 1
HOFMANN DR 32 - 33 60 1 60 1 60 4 60 SP2 360
20 U2220507 * C + I PILLAR CI1 LVLP400CFS 1
33 - 34 10 1 10 2 10 4 10 SP3 70
* EARTH ASSY1037-1 1
32 - 32L 5 1 5 O 5 SUPPLY PILLAR (240-240-240 6F)
23 U2220509 * PI1 LVSP9-6 1
36 - 36L 5 1 5 O 5
24 U2220508 * C + I PILLAR CI1 LVLP400CFS 1
37 - 37L 5 1 5 O 5
* EARTH ASSY1037-1 1
37 - 38 30 1 30 1 30 1 30 4 30 SP2-SL 210 LINK PILLAR (240-240 6F)
26 U2220510 * LP1 LVSP14-6 1
E
37 - 73 30 1 30 1 30 4 30 SP2 180
* EARTH ASSY1037-1 1
40 - 42 45 1 45 1 45 1 45 4 45 SP2-SL 315
29 U2220511 * C + I PILLAR CI1 LVLP400CFS 1 E
41 - 41L 5 1 5 O 5
* EARTH ASSY1037-1 1
43 - 43L 5 1 5 O 5 SUPPLY PILLAR (240-240-240 7F)
30 U2220512 * PI1 LVSP9-6S 1
42 - 44 45 1 45 1 45 4 25 20 SP2 270 E
31 U2220513 * C + I PILLAR CI1 LVLP400CFS 1
44 - 44L 5 1 5 O 5
* EARTH ASSY1037-1 1
44 - 45 25 1 25 1 25 1 25 4 25 SP2-SL 175
HOFFMAN DR 73 U2220515 * C + I PILLAR CI1 LVLP400CFS 1
49 - 52 35 1 35 1 35 4 35 SP2 210
* EARTH ASSY1037-1 1
52 - 53L 5 1 5 O 5 SUPPLY PILLAR (240-240-240 6F)
32 U2220514 * PI1 LVSP9-6 1
52 - 53 15 1 15 1 15 2 15 4 15 SP3-SL 120
36 - * TYPE 4 S/L PIT PT1 ASSY833-1 1
53 - 55 30 1 30 1 30 1 30 4 30 SP2-SL 210 JUNCTION BOX (NO FUSE)
* ASSY833-5 1
55 - 57 30 1 30 1 30 4 30 SP2 180
37 - * TYPE 4 S/L PIT PT1 ASSY833-1 1
56 - 56L 5 1 5 O 5 JUNCTION BOX (NO FUSE)
* ASSY833-5 1
58 - 57L2 5 1 5 O 5
41 - * TYPE 4 S/L PIT PT1 ASSY833-1 1
61 - 63 115 1 115 1 115 4 95 20 SP2 690 JUNCTION BOX (NO FUSE)
* ASSY833-5 1
PRIVATE RD (SOUTH) 38 - 49 215 1 215 1 215 4 215 SP2 1290 IN 1.2m EGX EASEMENT
42 - * TYPE 4 S/L PIT PT1 ASSY833-1 1
TOTALS 250 1295 1445 5180 525 825 8170 43 - * TYPE 4 S/L PIT PT1 ASSY833-1 1
* JUNCTION BOX (NO FUSE) ASSY833-5 1
44 - * TYPE 4 S/L PIT PT1 ASSY833-1 1
45 U2220516 * C + I PILLAR CI1 LVLP400CFS 1
* S/L FUSE ASSY801-1 1
* S/L FUSE HOLDER ASSY1043-3 1
* EARTH ASSY1037-1 1
45A U2220569 * 11kV STRAIGHT JOINT SJ1 11ST24/24X 1
53 U2220517 * C + I PILLAR CI1 LVLP400CFS 1
* S/L FUSE ASSY801-1 1
CONSTRUCTION ISSUE
* S/L FUSE HOLDER ASSY1043-3 1
* EARTH ASSY1037-1 1
54 SC846991 * 500kVA PADMOUNT TRANSFORMER TR1 EX. EX.
* LV FUSES DSLVF31 1
* LV TERMINATION LTSA24D 1
55 - * TYPE 4 S/L PIT PT1 ASSY833-1 1
56 - * TYPE 4 S/L PIT PT1 ASSY833-1 1
CERTIFICATE OF COMPLIANCE CERTIFICATE OF COMPLIANCE 58 - * TYPE 4 S/L PIT PT1 ASSY833-1 1
59 U2059121 * * EXISTING SUPPLY PILLAR PI1 EX. EX.
DESIGN DOCUMENTATION IN ACCORDANCE WITH THE REQUIREMENTS OF DESIGN DOCUMENTATION IN ACCORDANCE WITH THE REQUIREMENTS OF * SUPPLY PILLAR (240-240 7F) PI1 LVSP4-6S 1
COMPLIANCE OF AS/NZS 1158 COMPLIANCE OF AS/NZS 1158
60 U2220518 * SUPPLY PILLAR (240-240-240 6F) PI1 LVSP9-6 1
* Refer AS1158.1.1:2005 Appendix D for information regarding V category 61 U2220519 * C + I PILLAR CI1 LVLP400CFS 1
* Refer AS1158.1.1:2005 Appendix D for information regarding V category
* Refer AS1158.3.1:2005 Appendix E for information regarding P category * EARTH ASSY1037-1 1
* Refer AS1158.3.1:2005 Appendix E for information regarding P category
* PerfectLite 5.06 computer software used 62 U2059120 * EXISTING SUPPLY PILLAR EX. EX. EX.
* PerfectLite 5.06 computer software used
* * 16mm LUG SET EX. EX. EX.
ITEM PROJECT SPECIFICATION
ITEM PROJECT SPECIFICATION 63 U2220520 * C + I PILLAR CI1 LVLP400CFS 1
LIGHTING CATEGORY * EARTH ASSY1037-1 1
LIGHTING CATEGORY
64 SC1405163 * 500kVA PADMOUNT TRANSFORMER TR1 EX. EX.
Road Name WALTER HAY DR / HOFMANN DR Road Name WALTER HAY DR / HOFMANN DR * LV FUSES DSLVF31 1
Nominated Lighting Category V5 * LV TERMINATION LTSA24D 1
Road Surface Reflection Characteristic R3 Nominated Lighting Category V5
65 LP2220521 * LINK PILLAR (240-240 7F) LP1 LVSP14-6 1
Road Surface Reflection Characteristic R3 * S/L FUSE ASSY801-1 1
INSTALLATION GEOMETRY
Road Reserve Lighting Design Width 49m / 22m INSTALLATION GEOMETRY * S/L FUSE HOLDER ASSY1043-3 1
Mounting Height 10.5m - 12.0m Road Reserve Lighting Design Width 49m / 22m * EARTH ASSY1037-1 1
Overhang 0.5m - 2.0m Mounting Height 10.5m - 12.0m 66 U20159123 * * EXISTING SUPPLY PILLAR EX. EX. EX.
Overhang 0.5m - 2.0m 67 U2220522 * SUPPLY PILLAR (240-240-240 7F) PI1 LVSP9-6S 1
Lighting Arrangement ARR1 , ARR3
Lighting Arrangement ARR1 , ARR3 68 U2059124 * * EXISTING SUPPLY PILLAR PI1 EX. EX.
Pole Setback 1m BoK
* SUPPLY PILLAR (240-240 7F) PI1 LVSP4-6S 1
Upcast Angle 0 degrees Pole Setback 1m BoK
Upcast Angle 0 degrees 71 U2220523 * C + I PILLAR CI1 LVLP400CFS 1
LUMINAIRE/LAMP 1 DETAILS * EARTH ASSY1037-1 1
Lamp Type / Wattage LUMINAIRE/LAMP 1 DETAILS PRIVATE RD (SOUTH) SUPPLY PILLAR (240-240-240 7F)
L170A L80A 38 U2220524 * PI1 LVSP9-6S 1
Lamp Type / Wattage L80A 39 U2220525 * C + I PILLAR CI1 LVLP400CFS 1
Luminaire Identification Philips RoadFlair Philips RoadFlair * S/L FUSE ASSY801-1 1
Luminaire Identification Philips RoadFlair * S/L FUSE HOLDER ASSY1043-3 1
Lamp Flux (Lumens) 20400 9600 * EARTH ASSY1037-1 1
Lamp Flux (Lumens) 9600 46 U2220526 * C + I PILLAR CI1 LVLP400CFS 1
BRP393 LED204NW BRP391 LED96NW
I-Table Number (.cie) * S/L FUSE ASSY801-1 1
170W DWV 80W DWV
I-Table Number (.cie) BRP391 LED96NW 80W DWV
* S/L FUSE HOLDER ASSY1043-3 1
Lighting Tariff 2 2
Lighting Tariff * EARTH ASSY1037-1 1
Power Factor HPF (> 0.95) HPF (> 0.95) 2
47 U2220527 * C + I PILLAR CI1 LVLP400CFS 1
Start/Run Currents (Amps) 0.708 0.333 Power Factor HPF (> 0.95)
* S/L FUSE ASSY801-1 1
IP Rating IP66 IP66 Start/Run Currents (Amps) 0.333
* S/L FUSE HOLDER ASSY1043-3 1
IP Rating IP66
ILLUMINANCE BASED DESIGN - CATEGORY V TECHNICAL PARAMETER * EARTH ASSY1037-1 1
COMPLIANCE - "design area" ie. intersection of x and x roads ILLUMINANCE BASED DESIGN - CATEGORY V TECHNICAL PARAMETER COMPLIANCE 48 U2220528 * C + I PILLAR CI1 LVLP400CFS 1
- "design area" ie. intersection of x and x roads * S/L FUSE ASSY801-1 1
Point Horizontal Illuminance (Eph) 3.5 lux * S/L FUSE HOLDER ASSY1043-3 1
Point Horizontal Illuminance (Eph) 3.5 lux * EARTH ASSY1037-1 1
Illuminance (Horizontal Uniformity) Cat V
8 49 U2220529 * LINK PILLAR (240-240 7F) LP1 LVSP14-6 1
(UE1) Illuminance (Horizontal Uniformity) Cat V
8
(UE1) * S/L FUSE ASSY801-1 1
* S/L FUSE HOLDER ASSY1043-3 1
* EARTH ASSY1037-1 1
DATE 23.10.2019 04.11.2019 25.05.2020 02.09.2020 06.01.2021 SITE CONTACT DETAILS COUNCIL STANDARD ALIGNMENTS WORKS COORDINATOR PETER EUSTACE & ASSOCIATES WORKSPLAN VERSION 5.5
APPROVED KRIS BOVEINIS Peter Eustace & Associates
ISSUED FOR COUNCIL OPW
ISSUE FOR TENDER ONLY.
Energex OH
NOT FOR CONSTRUCTION.
CONSULTING NAME 2.95m RP PARENT PROJECT NO. SCALE: N.T.S.
C TENDER ONLY. NOT FOR
ISSUE FOR ENERGEX &
A APPROVAL ONLY. NOT
TBC Energex UG 0-0.9m RP WORK REQUEST See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.