Referral Agency Response - 28 Eenie Creek Road, Noosaville

Attached to the e-mail MCU23/0135 - Energex Referral agency response - 28 Eenie Creek Rd, Noosaville.

of 4

Page text shows just the words. Original shows the document exactly as it was published.

27 November 2023




Noosa Council
PO Box 141
Tewantin QLD 4565
Attention: Nadine Gorton
Via email: [email protected]


                Cc    Stockwell Development Group Pty Ltd
                      PO Box 3144
                      South Brisbane QLD 4101
                      Attention: Kelly Alcorn
                      Via email: [email protected]

Dear Sir/Madam,

Referral Agency Response – Development Permit for a Material Change
of Use – Shopping Centre (Extension to Existing Shops and Food and
Drink Outlets) at 28 Eenie Creek Road, Noosaville (Lot 1 on SP322201)

Council Ref: MCU23/0135
Applicant Ref: 21-0694P/13
Our Ref: 13353163-15128046

We refer to the abovementioned Development Application, which has been
referred to Energex Limited pursuant to section 54 of the Planning Act 2016.

In accordance with Schedule 10, Part 9, Division 2 of the Planning
Regulation 2017, the application has been assessed against the purposes of
the Electricity Act 1994 and Electrical Safety Act 2002. This notice is
provided in accordance with section 56 of the Planning Act 2016.

Should the Assessment Manager decide to approve the proposed Material
Change of Use, Energex advises the following in relation to the proposed
development:
                                                                               Enquiries
                                                                               Benjamin Freese
   1. The development is to be carried out in accordance with the plans
                                                                               Mobile
      identified below. Any changes to these plans should be resubmitted       0455 403 399
      to Energex for further review and comment.                               Email
                                                                               benjamin.freese@
                                 Approved Plans                                energyq.com.au

        Title                   Plan Number        Issue    Date               Corporate Office
        Title Sheet and         A-DA-0000          A        9 October 2023     26 Reddacliff Street,
        Development Site Plan                                                  Newstead QLD 4006
                                                                               GPO Box 1461
        Ground Floor Plan       A-DA-1000          A        9 October 2023     Brisbane Qld 4001
                                                                               Telephone (07) 3664 4000
        Basement Floor Plan     A-DA-1010          A        9 October 2023
                                                                               Facsimile (07) 3025 8301
        Level One/Roof Floor    A-DA-1020          A        9 October 2023     www.energex.com.au
        Plan
                                                                               Energex Limited
                                                                               ABN 40 078 849 055


Reference: 13353163-15128046
Log in to download the original file

Referral Agency Response - 28 Eenie Creek Road, Noosaville.pdf · 196 KB (small file)

Full text of the other 3 pages

Page 2

                                                       2




    2. The conditions of any easements in favour of Energex must be maintained at all
       times.

    3. Access to the easement and access along the easement must be available to
       Energex personnel and heavy equipment at all times.

    4. Any costs or damages incurred by Energex as a result of the carrying out the
       development are to be met by the Applicant/Developer.

    5. Any future works on an Energex easement or in the vicinity of Energex assets
       are to be carried out in accordance with Energex Standard Guideline UG-03/12.
       A copy of this guideline is attached for reference.

Should you require further information regarding this matter, please contact the
undersigned on 0455 403 399 or [email protected] faithfully,



Benjamin Freese
Town Planner

Encl.      Energex Standard Guideline UG-03/12




Reference: 13353163-15128046

                                      Have you seen our fact sheets?
        See the ‘considerations when developing around electricity infrastructure’ section of our website
                                    www.energex.com.au/referralagency

Page 3

                                                   3




                              Standard Guidelines UG-03/12

When considering Works either on Energex easements or in the vicinity of Energex assets,
please be aware of the following general conditions:

•   No civil works are to occur within 3 metres of the cable centreline unless otherwise
    approved by the Senior Project Engineer- underground.

•   Where large excavations are taking place in the vicinity of our cables, there should be no
    greater than a 45 degree batter to the cables (i.e. if excavating to a 5 metre depth- need to
    maintain a 5 metre horizontal clearance to the edge of the cable trench).

•   Excavations in excess of 5 metres in depth must have a minimum horizontal separation,
    from the excavation to cable centreline, at least equal to the excavation depth.

•   If the easement is to be re-surfaced, the developer must consider that Energex require
    timely access to the cables, especially under network emergency conditions. Re-enforced
    concrete pavements (or similar) over the easement are generally NOT allowed as they will
    impede timely access to the cables. Energex will consider surfaces that are easier to
    remove. (e.g.- asphalt, etc) over the easement up to a thickness of 100mm. please submit
    detailed plans of any proposal for consideration by Energex.

•   The easement may be excavated at any time (and without notice for emergency situations)
    to maintain/repair existing cables and install new cables if required. Access across/along
    the easement could be prohibited for an indeterminate length of time, possibly weeks for
    new cable installations while the works are undertaken.

•   Natural ground levels on the easement shall not be changed without Energex approval.

•   Final ground levels should slope gently to the edge of the easement, surrounding area or
    kerb such that pooling of water on the easement is avoided.

•   Stockpiling of spoil on the easement is prohibited.

•   Any proposed underground services are to be kept out of the easement and are to only
    cross the easement as near as possible to right angles to the cables.

•   Any excavation for services across Energex transmission cables should be no deeper than
    the barrier boards protecting these cables. Under no circumstances should barrier boards
    be removed and the backfill around the cables disturbed.

•   Any excavation under Energex cables should be referred to the senior project engineer-
    underground to determine if cables need to be supported during excavation. Energex will
    be required to fill back around the cables on completion of the works.

•   When directional drilling across Energex cables a trench should be dug beside the cables
    to sight the location of the drilling head as it passes over/under the cables. There should be
    a minimum 500mm separation between the drilling head and cables.

•   Any further proposal for works or development on the easement including those involving
    changes in ground level and retaining wall designs around cables must have prior approval
    from Energex. Please submit the relevant civil design to Energex for approval.




Reference: 13353163-15128046

                                  Have you seen our fact sheets?
    See the ‘considerations when developing around electricity infrastructure’ section of our website
                                www.energex.com.au/referralagency

Page 4

                                                   4




•   Access to the easement and access along the easement must be available to Energex
    personnel and heavy equipment at all times. Energex will require the Developer / owner to
    supply and install gates where fencing prohibits access to and along the easement area.
    To enable travel along the easement at anytime the gates must be series locked with an
    Energex padlock. Both the padlock and a design drawing of an acceptable gate will be
    provided by Energex.

•   Any costs or damages incurred by Energex as a result of the works on the easement are to
    be met by the property Developer / owner.

•   Landscaping on the easement is generally not permitted.




Reference: 13353163-15128046

                                  Have you seen our fact sheets?
    See the ‘considerations when developing around electricity infrastructure’ section of our website
                                www.energex.com.au/referralagency

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.