Design Check and Summary (Derived from Table 22 of the WBD Bioretention Technical Design Guidelines, 2012)
      Item                               Description                                                                Detail                                                      Recommendation
                                                                         Northern Basin           Central Basin                Southern Basin       Unit
1. Treatment
(a)       Catchment area                                                        2.5                     5.5                            5             ha
(b)         Filter media area( excluding batters                              525                       180                  305                     m2                                       2
                                                                                                                                                              Single or multiple cells < 800m each
            Confirm water quality performance meets the design        Refer to Section 4.5 of latest issue of SWMP Report (No. 16‐001014‐
(c)
            objectives                                                                                   01)
            Confirm hydrologic performance meets relevant frequent       Under the SPP, 2014 frequent flow objectives are no longer a
(d)
            flow objectives                                                                    requirement for SEQ.
2. Design Inflows
(a)         Minor design storm entering system                               10% AEP                10% AEP                       10% AEP          AEP (%)
                                                                                                                                                      3
(b)         Minor storm peak flow rate                                         1.08                   1.31                          2.08            m /s
(c)          Major design storm entering system                              1% AEP                  1% AEP                        1% AEP           ARI
                                                                                                                                                      3
(d)        Major storm peak flow rate                                          1.51                    1.67                          2.69           m /s
3. Depth Profile
(a)          Bioretention drainage profile type                        Type 3 Conventional     Type 3 Conventional           Type 3 Conventional    Type
                                                                                                                                                              See section 3.2.2.3 and 3.2.2.4 for "Type 1"
                                                                                                                                                              ≥ 150 mm for"Type 2"
(b)          Minimum drainage layer depth                                      300                     300                           300            mm
                                                                                                                                                              ≥ 300 mm for "Type 3"
                                                                                                                                                              Not needed for "Type 4"
(c)          Maximum drainage layer depth                                      400                     300                           400            mm        Same as minimum except for"Type 2"
                                                                                                                                                              See Section 3.2.2.4 for"Type 1"
(d)          Transition layer depth                                            100                     100                           100            mm
                                                                                                                                                              ≥ 100 mm for "Type 2':"Type 3" and "Type 4"

(e)          Saturated zone depth for Type 1 bioretention systems              N/A                     N/A                           N/A            mm        See section 3.2.2.4

(f)          Filter media layer depth                                          400                     400                           400            mm        ≥ 400mm (≥ 700mm with trees)
(g)          Extended detention depth                                          300                     300                           300            mm        ≤ 300mm
             Maximum water level depth above extended detention for
(h)                                                                           1100                     450                           446            mm
             major storm event
(i)          Freeboard to top of embankment                                    300                       0                           554            mm        Multiple, see section 3.2.3.6

(j)          Total system profile depth [3(c)+3(d)+3(f)+3(h)+3(i)]            2500                    1550                          2100            mm        = 4(j)
             Liner type                                               Bidum A12 Geotextile Bidum A12 Geotextile Bidum A12 Geotextile                          Subject to drainage profile type and in‐situ
(k)
             (i) Permeable (ii) Impermeable (iii) None to base               Fabric                Fabric                Fabric                               soils/groundwater (see section 3.2.4)
                                                                      Geotechnical Engineer Geotechnical Engineer Geotechnical Engineer
(l)          AASS/PASS assessed and appropriately managed
                                                                            to assess             to assess             to assess
            Presence of dispersive soils assessed and appropriately   Geotechnical Engineer Geotechnical Engineer Geotechnical Engineer
(m)
            managed                                                         to assess             to assess             to assess
4. Design Levels
(a)          Outlet invert level                                                98                    99.25                        100.15          m AHD
(b)          Overflow pit invert level                                          98                    99.25                        100.15          m AHD
(c)          Minimum drainage layer level                                      98.3                   99.25                         100.9          m AHD
(d)          Filter media surface level                                        99.1                  100.05                         101.7          m AHD
(e)          Overflow pit crest level                                     99.4 (Orifice)             100.35                          102           m AHD
(f)          Overflow weir level                                              100.4                   100.5                         102.7          m AHD
(g)          Maximum design water level                                       100.1                  101.03                        102.45          m AHD
(h)          Top of embankment/batter level                                   100.8                   100.8                          103           m AHD
(i)          Inlet/inflow invert level                                         99.1                  100.05                         101.7          m AHD
(j)          Total level difference [4(h)‐4(c)]                                 2.5                    1.55                           2.1            m        = 3(j)
                                                                                                                                                              "Type 1"‐impermeable liner extends
                                                                                                                                                              ≥ 300 mm above HAT
(k)          Highest astronomical tide level                                Non‐Tidal               Non‐Tidal                     Non‐Tidal        m AHD      "Type 2'; "Type 3"and "Type 4"‐ ba se of
                                                                                                                                                              transition layer ≥ 300 mm above HAT

                                                                      Geotechnical Engineer Geotechnical Engineer Geotechnical Engineer
(l)          Groundwater level                                                                                                                     m AHD      Varies with drainage profile type, see Table 8
                                                                            to assess             to assess             to assess
5. Layout
(a)          Maximum filter media length                                        40                      31                            20             m        ≤ 40m
(b)          Maximum filter media width.                                        19                       8                            15             m        ≤ 20m (preferred ≤ 15m)
(c)          Maximum batter slope                                            1:3 V:H                 1:4 V:H                       1:4 V:H          V:H
(d)         Maximum wall height (where applicable)                             N/A                     1.8                            1              m
            Provision for services (water, sewer, gas,                 No Services Through     No Services Through           No Services Through
(e)
            telecommunications, stormwater)                                   Basin                   Basin                         Basin
(f)         Maintenance access provided                                        Yes                     Yes                           Yes
            Flood storage volume above extended detention (where                                                                                          3
(g)                                                                           1,030                   4,620                          221             m
            bioretention combined with flood storage)
6. Inlet Design
            Inlet/inflow type
(a)                                                                     Pipe & Sheet Flow       Pipe & Sheet Flow             Pipe & Sheet Flow
            (i) pipe (ii) channel (iii) sheet flow (iv) other
                                                                         No Diversion ‐          No Diversion ‐                No Diversion ‐
(b)          Diversion/surcharge type (where applicable)
                                                                       Detention Proposed      Detention Proposed            Detention Proposed
              Coarse sediment removal
(c)                                                                     Sediment Forebay               GPT                           GPT
             (i) forebay (ii) inlet pond (iii) swale (iv) other
                                                                                                                                                          2
(d)          Coarse sediment removal area                                 6m3 required          *2.6m3 required               *2.4m3 required        m
(e)          Coarse sediment removal depth                                    0.2m              *2.6m3 required               *2.4m3 required        m2
(f)          Coarse sediment clean‐out frequency                                 1                       1                             1                      < once per year

(g)          Flow distribution type                                   Multiple Inflow Points           N/A                           N/A                      Required if filter media area > 400 m 2

                                                                          Refer to Energy         Refer to Energy         Refer to Energy
(h)          Confirm scour protection at inflow
                                                                      Dissipator Calculations Dissipator Calculations Dissipator Calculations

(i)          Minor storm flow velocity over filter                              0.4                    0.58                          0.43           m/s       < 1.0m/s
(j)        Major storm flow velocity over filter                               0.46                    0.63                          0.47           m/s       < 1.0m/s
7. Underdrainage (outlet design)
(a)          Filter media saturated hydraulic conductivity                     200                     200                           200           mm/hr      100 ‐ 300 mm/hr
(b)        Maximum filter infiltration capacity                               0.051                   0.017                          0.03           m3/s
           Underdrain capacity                                                                                                                        3
(c)                                                                           0.068                   0.022                         0.032           m /s      > 7(b)
           (taking into account blockage factors)
8. Overflow Design (outlet design)
(a)          Overflow pit type                                              Field Inlet             Field Inlet                  Field Inlet
(b)          Overflow pit dimensions                                        900 x 900               600 x 600                   1200 x 1200
(c)          Overflow weir length                                                4                       5                             6             m
             Overflow pit capacity (taking into account blockage                                                                                      3
(d)                                                                            0.46                    0.23                          1.25           m /s      > 2(b)
             factors)
             Overflow pit plus overflow weir capacity (taking into                                                                                    3
(e)                                                                            2.92                     2.1                          6.51           m /s      > 2(d)
             account blockage factors)
(f)          Outlet pipe size                                                  375                     825                           900            mm

                                                                          Refer to Energy         Refer to Energy         Refer to Energy
(g)          Appropriate outlet scour protection provided
                                                                      Dissipator Calculations Dissipator Calculations Dissipator Calculations
9. Vegetation Design
           Planting style
(a)        (i) small scale urban (ii) med‐large scale urban                 (ii) or (iii)           (ii) or (iii)                 (ii) or (iii)
           (iii) bushland
                                                                      No Bioretention Trees No Bioretention Trees No Bioretention Trees
(b)          Trees and shrubs to be included (yes/no)
                                                                            proposed              proposed              proposed
(c)          Species diversity (number of species)                             Yes                   Yes                   Yes                              Refer Table 19
                                                                      Refer to Landscaping Refer to Landscaping Refer to Landscaping
(d)          Species selection                                                                                                          refer to plan: ____ ≥ 50% coverage with plants from Table 20
                                                                              Plans                 Plans                 Plans
                                                                      Refer to Landscaping Refer to Landscaping Refer to Landscaping               2        May vary between plant species, refer to plan if
(e)          Planting density                                                                                                                   /m
                                                                              Plans                 Plans                 Plans                             required
                                                                      Refer to Landscaping Refer to Landscaping Refer to Landscaping
(f)          Mulch type and depth                                                                                                                           See section 3.6.7 and section 4.4.4
                                                                              Plans                 Plans                 Plans
                                                                                                                                                              Matthew Starr (RPEQ 9485)
Log in to download the original file

16-001014-02A (Ultimate SCMMP).pdf · 14.7 MB (very large file)

Very large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.