Central Bioretention Basin
Critical Section
CROSS SECTION DETAILS 10% AEP 1% AEP
POINT CH Z n wA wP n x wA wA wP n x wA
1 ‐4.2 100.95 0.060
2 ‐4.2 100.35 0.060 0.00 0.04 0.00 0.00 0.09 0.00
3 ‐3 100.05 0.060 0.23 1.24 0.01 0.29 1.24 0.02
4 3 100.05 0.060 2.06 6.00 0.12 2.36 6.00 0.14
5 6.6 100.95 0.060 0.24 1.42 0.01 0.31 1.62 0.02
wA wP n x wA wA wP n x wA
TOTAL 2.533472 8.69928 0.152008 2.958498 8.950312 0.17751
S
0.005 R n Q R n Q
0.291228 0.060 1.31 0.330547 0.060 1.67
Flow 1.31 1.67
WSL 100.394 100.443
Calculated by Manning's Equation 1.31 1.67
Vel (m/s) 0.52 0.56
Basin Section
101
100.9
100.8
100.7
Height (m AHD)
100.6
100.5
100.4
100.3
100.2
100.1
100
-6 -4 -2 0 2 4 6 8
Width (m)
Existing Sur face 10 % AEP 1% A EP
As indicated in results above velocities are only slightly above 0.5m/s (by 0.02m/s and 0.06m/s
during the major storm). This is within the requirements for the major storm (less than 2m/s) but
only slightly above for the minor storm. However, scour or damage of vegetation is unlikely as the
results do not take into account the backflow effect caused by the outlet pit and weir which will
reduce velocities through the basin. Therefore the design of the basin is appropriate to cater for
inflow velocity.