                                                                                                                         PROPOSED ACOUSTIC FENCE                                                                                                                                                                                                                                                 GENERAL NOTES:
                                                                                                                                                                                                                                                                                                                                                                                                 G1.    All measurements and areas noted are approximate. allow to site measure all

                                                                                                                      AT NOOSA CIVIC, WALTER HAY DRIVE                                                                                                                                                                                                                                           G2.
                                                                                                                                                                                                                                                                                                                                                                                                 G3.
                                                                                                                                                                                                                                                                                                                                                                                                        Setting out dimensions and sizes of members or elements shall not be obtained by scaling the drawings.
                                                                                                                                                                                                                                                                                                                                                                                                        During construction, the structure shall be maintained in a stable condition. Construction loads must not
                                                                                                                                                                                                                                                                                                                                                                                                        exceed the safe load capacity of the structure at any time during construction. Stability of excavation in the
                                                                                                                                                                                                                                                                                                                                                                                                        vicinity of neighboring buildings is the responsibility of the builder. If in doubt ask.
                                                                                                                         FOR FOR STOCKWELL PTY LTD                                                                                                                                                                                                                                               G4.    All workmanship and materials shall be in accordance the requirements of the current editions including
                                                                                                                                                                                                                                                                                                                                                                                                        amendments of the relevant SAA codes of practice, except as varied by the contract documents and of the
                                                                                                                                                                                                                                                                                                                                                                                                        by-laws of the local government authority.

                                                                                                                              JOB No. 1856                                                                                                                                                                                                                                                       G5.    Setting out dimensions and sizes of members or elements shall not be obtained by scaling the drawings.
                                                                                                                                                                                                                                                                                                                                                                                                        All dimensions shown on the engineering drawings shall be checked by the contractor before
                                                                                                                                                                                                                                                                                                                                                                                                        commencement of fabrication or site works.
                                                                                                                                                                                                                                                                                                                                                                                                 G6.    Registered surveyor to provide boundary setout pegs prior to commencement of works.
                                                                                                                                                                                                                                                                                                                                                                                                 G7.    Permanent, imposed and other loads (dead & live) for this project have been determined in accordance with
                                                                                                                                                                                                                                                                                                                                                                                                        AS1170.1 - 2002
                                                                                                                                                                                                                                                                                                                                                                                                 G8.    Builder to confirm all existing services prior to commencement of works.
                                                                                                                                  SCHEDULE OF DRAWINGS                                                                                                                                                                                                                                           G9.    Site Soil Classification "Class M" as per Geotechical Investigations Report GI 2351-A Dated Dec 2015
                                                                                                                    DWG                DESCRIPTION                                                                                                                                                                                                                                               G10.   Design assumes soil shear capacity cu > 150kpa ("Very Stiff" Sandy Clay as per geotech report)
                                                                                                                                                                                                                                                                                                                                                                                                 G11.   If rock is encountered during excavation BSCE engineer to be notified immediately for footing redesign.
                                                                                                              PLAN - SHEET             Description
                                                                                                              1856-ST01                Locality Plan & General Construction Notes                                                                                                                                                                                                                CONCRETE NOTES:
                                                                                                              1856-ST02                Acoustic Fence Site Layout Plan                                                                                                                               CAUTION - EXISTING SERVICES
                                                                                                                                                                                                                                                                                                     THE CONTRACTOR IS TO DETERMINE THE EXACT LOCATION OF                                        C1.    All workmanship and materials shall be in accordance with the requirements of the relevant current
                                                                                                              1856-ST03                Typical Acoustic Fence Section & Details Sheet 1 Of 1                                                                                                         ALL EXISTING SERVICES IN THE VICINITY OF THE PROPOSED
                                                                                                                                                                                                                                                                                                     WORKS PRIOR TO THE START OF ANY CONSTRUCTION. THE                                                  Australian Standard codes (AS3600, AS2870 & AS1379) & MRTS70, building by-laws and the ordinances of
                                                                                                              1856-ST04                Workplace Health & Safety Notes                                                                                                                               COST OF ANY RECTIFICATION WORKS DUE TO DAMAGE OF                                                   the relevant local authority.
                                                                                                                                                                                                                                                                                                     EXISTING SERVICES SHALL BE BORNE BY THE CONTRACTOR.
                                                                                                                                                                                                                                                                                                                                                                                                 C2.    Concrete Specification:


                                                                                                                                                                                                                                                                                                                                                                                                                                                           MAX.              MAX.                 MIN.
                                                                                                                                                                                                                                                                                                                                                                                                                                        CONC              SLUMP           AGGREGATE              COVER
                                                                                                                                                                                                                                                                                                                                                                                                           ELEMENT
                                                                                                                                                                                                                                                                                                                                                                                                                                        GRADE              (mm)            SIZE (mm)              (mm)

                                                                                                                                                                                                                                                                                                                                                                                                  BORED PIERS                              N32          100 (+20/-10)             20                 75

                                                                                                                                                                                                                                                                                                                                                                                                 C3.    No concrete to be poured when site temperature exceeds 35° C or falls below 5° C
                                                                                                                                                                                                                                                                                                                                                                                                 C4.    No penetrations, recesses or chases other than those shown on the structural drawings shall be made in
                                                                                                                                                    PROPOSED                                                                                                                                             EXISTING NOOSA CIVIC                                                                           concrete members without the approval of the Engineer.
                                                                                                                                                    SITE LOCATION.                                                                                                                                                                                                                               C5.    Builder to ensure bored holes are free of loose material and water with a firm compacted base prior to
                                                                                                                                                                                                                                                                                                                                                                                                        concrete placement.
                                                                                                                                                                                                                                                                                                                                                                                                 C6.    Place concrete within 1 hour of batching discharge directly to holes.
                                                                                                                                                                                                                                                                                                                                                                                                 C7.    Concrete not to be re-worked following placement, tamped without delay.

                                                                                                                                       T                                                                      LOT 21                                                                       INDICATES 1800mm HIGH
                                                                                                                                   E                                                                         SP246584                                                                      TIMBER FRAME ACOUSTIC
                                                                                                                                RE
                                                                                                                           ST                                                                                                                                                              BARRIER TO BOUNDARY.
                                                                                                                                                                                                                                                                                                                                                                                                 STEELWORK NOTES:
                                                                                                                       E
                                                                                                                R   EN                                                                                                                                                                                                                                                                           S1.    All steelwork shall comply with the requirements of:-
                                                                                                                                                                                                                                                                                                                                                                                                        AS4100 - Steel Structures
                                                                                                                                                                                                                                                                                                                                                                                                        AS2312 - Guide to the Protection of Iron and Steel.
                                                                                                                                                                                                                                                                                                                                                                                                        AS1214 - Hot Dip Galvanising of Threaded Fasteners
                                                                                                                                                                                                                                                                                                                                                                                                 S2.    Plates, cleats, braces and all other hot rolled sections shall be grade 300 material U.N.O. and power
                                                                                                                                                                                                                                                                                                                                                                                                        brushed to ST2 and primed with an approved metal protective coating.
                                                                                                                                                                           HO




                                                                                                                                                                                                                                                                                                                                                                                                 S3.    All steel columns to be UC sections , hot dip galvanised. U.N.O.
                                                                                                                                                                              FM




                                                                                                                                                                                                                                                                            LO                                                                                                                   S4.    Bolts nominated by diameter, ultimate strength and method of tightening (eg M12 4.6/s = 12mmø,
                                                                                                                                                                                                                                                                               T
                                                                                                                                                                                AN




                                                                                                                                                                                                                                                                       SP
                                                                                                                                                                                                                                                                            246 19                                                                                                                      commercial bolt, snug tight).
                                                                                                                                                                                                                                                                               584
                                                                                                                                                                                  N




                                                                                                                                                                                                                                                                                                                                                                                                 S5.    All bolts to be installed with one hardened washer under the turned part. (see AS1720.1 section 4)
                                                                                                                                                                                    DR




                                                                                                                                                                                                                                                                                                                                                                                                 S6.    All external steel members and components including bolts and washers to be Hot Dipped galvanised.
                                                                                                                                                                                      IV




                                                                                                                                                                                                                     INDICATES OPTIONAL 1800mm HIGH
                                                                                                                                                                                       E




                                                                                                                                                                                                                     TIMBER FRAME ACOUSTIC BARRIER                                                                                                                                               FENCE NOTES:
                                                                                                                                                                                                                     TO BOUNDARY.                                                                            LO
                                                                                                                                                                                                                                                                                                           SP T 18                                                                               W1.    Wind Loads: p.ult = 2.01kPa or 2.91kPa (corner). p.serv = 0.85kPa or 1.23kPa (corner). Based on Region B
                                                                                                                                                                                                                                                                                                             246                                                                                        V1000 (ult), V25 (serv), Cat 2, Mt = 1.0, Ms = 1.0, Cfig = 1.25 or 1.8 (at corners)
                                                                                                                                                                                                                                                                                                                584
a:\1856 - noosa civic noosaville\acad structural\1856-lot_21_noosa_civic_acoustic_fence.dwg




                                                                                                                                                                                                                                                                                                                                                                                                 W2.    Timber battens are min. F5 strength grade, H4 treated if in contact with ground, H3 treated otherwise. All
                                                                                                                                                                                                                                                                                                                                                                                                        timbers to be free of defects and comply with MRTS15 Cl.7.4.2 and TMR Drawing SD1606
                                                                                                                                                                                                                                                                                                                                                                                                 W3.    Ply panels to be min 27mm thick with surface density to comply with approved acoustic report.
                                                                                                                 PROPERTY DESCRIPTION                                                                                                                                                                                                  LO                                                        W4.    Screws to be self tapping 14 gauge type 17 hex head as specified in MRTS15
                                                                                                                                                                                                                                                                                                                                     SP T 17                                                     W5.    All fasteners and fixings to be hot dip galvanized unless noted otherwise.
                                                                                                                 LOT 21 on SP246584 |            AREA: 3825m²                                                                                                                                                                          246
                                                                                                                                                                                                                                                                                                                                           584                                                   W6.    All steel used to be heavy hot dip galvanized, clear of all zinc deposits and welding slag.
                                                                                                                                                                                                                                                                                                                                                                                                 W7.    Noise fence to be constructed in accordance with the requirements of MRTS15

                                                                                                                                                                                               LOCALITY PLAN
                                                                                                                                                                                               NOT TO SCALE
                                                                                                                                                                                                                                                                                                                                                                                                   PROJECT:                                                                                               JOB NUMBER
                                                                                              REV DATE DESCRIPTION                                           BY    CHKD             DETAILS                                             SCALE                                                APPROVED                                                                                              PROPOSED ACOUSTIC FENCE                                                                                   1856
                                                                                               1   27-08-20   FOR APPROVAL                                   NN       CL                                                                                                                                                                                                                           AT NOOSA CIVIC, WALTER HAY DRIVE
                                                                                               2   21-10-20   REVISED ISSUE                                  JP       CL    DATUM               AHD                                                                                                                                                                                                                                                                                                 SHEET:         OF
                                                                                                                                                                           DESIGN                CL
                                                                                                                                                                                                                                                                                            .................                                                                                      FOR STOCKWELL PTY LTD                                                                                       1         4


                                                                                                                                                                                                                                                                                        Director: CAMERON LANDRETH                                                                                 DRAWING TITLE:                                                                                   DRAWING NUMBER           REV
                                                                                                                                                                           DRAWN                NN                                 AS NOTED
                                                                                                                                                                                                                                                                                              (RPEQ 19358)                                                                                        LOCALITY PLAN & GENERAL CONSTRUCTION
                                                                                                                                                                           DESIGN CHECK          CL
                                                                                                                                                                                                                                                                                        DRAWING STATUS
                                                                                                                                                                                                                                                                                                                                      p 07 5443 8285                                                                                                                                                      ST01                2
                                                                                                                                                                                                          This drawing is not to be copied or amended without written permission from                                                 e [email protected] w www.barlowshelley.com.au    NOTES
                                                                                                                                                                           DATE                AUG 2020   Barlow Shelley Consulting Engineers                                                FOR APPROVAL                             a PO Box 899 Maroochydore 4558    ABN 89 215 591 077
Full text of the other 3 pages

Page 2

                                                                                                                                                    FH




                                                                                                                                  HOF
                                                                                                                                   MA
                                                                                                                                    NN
                                                                                                                                                                                                                                                                                 INDICATES LOCATION




                                                                                                                                        DRI
                                                                                                                                                                                                                                                                                 OF FIELD INLET PITS.




                                                                                                                                         VE
                                                                                                                                                                                                                                                                                               13950
                                                                                                                                                                                                                                                                                                                           18700
                                                                                                                                                                                                                                                           1  6450                                                                                     6700




                                                                                                                                                                                                                                                                                                                                                                             17
                                                                                                                                                                                                                                                                                                                                                                                20
                                                                                                                                                                                                                                                                                                                                                                                  0
                                                                                                                                                                                                                                                                                                                                                                                                      INDICATES LOCATION
                                                                                                                                                                                                                                                                                                                                                                                                      STORM WATER PIPE.




                                                                                                                                                                                                                                                                                                                                                                                               7900
                                                                                                                                                                                                                                                                                                                                            1800mm HIGH TIMBER
                                                                                                                                                                                                                                                                                                                                            FRAME ACOUSTIC
                                                                                                                                                                                                                                                                                                                                            BARRIER TO BOUNDARY.
                                                                                                                                                                                  FH




                                                                                                                                                                                                                                                                                                                                                                                              8570
                                                                                                                                                                                                                                                                                                         LOT 21
                                                                                                                                                                                                                                                                                                        SP246584

                                                                                                                                                                                                                           E




                                                                                                                                                                                                                                                                                                                                                                                  00
                                                                                                                                                                                                                                                                                                                                                                                 186
                                                                                                                                                                                                                                                                                                       OPTIONAL 1800mm HIGH
                                                                                                                                                                                                                             FH                                                                        TIMBER FRAME ACOUSTIC
                                                                                                                                                                                                                                                                                                       BARRIER TO BOUNDARY.


                                                                                                                                                                                                                                                                                                                                                                        130
                                                                                                                                                                                                                                                                                                                                                                            00
                                                                                                                                                                                        HO




                                                                                                                                                                                                                                                                                                                      00
                                                                                                                                                                                                                                                                                                                   511
                                                                                                                                                                                            FM
                                                                                                                                                                                                AN
                                                                                                                                                                                                   N
                                                                                                                                                                                                     DR
                                                                                                                                                                                                         IV




                                                                                                                                                                                       FH
                                                                                                                                                                                                           E




                                                                                                                                                                                                                                                                                                                                                      LOT 19
                                                                                                                                                                                                                                                                                                                                                     SP246584
                                                                                                                                                                                                                                                                                   M
                                                                                                                                                                                                                                                                                 W
                                                                                                                                                                                                                                                                                         M
                                                                                                                                                                                                                                                                                     W


                                                                                                                                                                                                                    ACOUSTIC FENCE SITE LAYOUT
                                                                                                                                                                                                                   SCALE 1:500 @ A3
a:\1856 - noosa civic noosaville\acad structural\1856-lot_21_noosa_civic_acoustic_fence.dwg




                                                                                                                                                                                                                                                                                                                                                                                                                           NOTE 1:
                                                                                                                                                                                                                                                                                                                                                                                                                           NOISE FENCE MATERIALS & ASSEMBLY SHALL BE IN ACCORDANCE
                                                                                                                                                                                                                                                                                                                                                                      WIND LOADS: TO AS 1170.2                             WITH "TRANSPORT AND MAIN ROADS SPECIFICATIONS:
                                                                                                                                                                                                                                                                                                                                                                      Vsite ULT = 53m/s = V250                             MRTS15 - NOISE FENCES
                                                                                                    CAUTION - EXISTING SERVICES                                                                                                                                                                                                                                       Vsite SERV = 38m/s = V20                             STD DWG 1606 - NOISE BARRIERS - RHS POSTS, PLYWOOD PANELS.
                                                                                                    THE CONTRACTOR IS TO DETERMINE THE EXACT LOCATION OF
                                                                                                    ALL EXISTING SERVICES IN THE VICINITY OF THE PROPOSED
                                                                                                                                                                                                                                                                                                                                                                      P.ULT = 1.57KPA OR 3.02KPA (CORNER/ENDS).
                                                                                                    WORKS PRIOR TO THE START OF ANY CONSTRUCTION. THE                                                                                                                                                                                                                 P.SERV = 0.81KPA OR 1.55KPA (CORNER/ENDS).           NOTE 2:
                                                                                                    COST OF ANY RECTIFICATION WORKS DUE TO DAMAGE OF
                                                                                                                                                                                                                                                                                                                                                                      TERRAIN CAT = 2, MT = 1.0, MD = 0.95, MS = 1.0,      THESE PLANS ARE TO BE READ IN CONJUNCTION WITH
                                                                                                    EXISTING SERVICES SHALL BE BORNE BY THE CONTRACTOR.
                                                                                                                                                                                                                                                                                                                                                                      Cpn = 1.248, 1.8 AT CORNERS & 2.4 AT ENDS.           THE ACOUSTIC DESIGN REPORT SPECIFICATIONS.


                                                                                                                                                                                                                                                                                                                                                                                              PROJECT:                                                                      JOB NUMBER
                                                                                              REV DATE DESCRIPTION                            BY   CHKD              DETAILS                                              SCALE                                                          APPROVED                                                                                             PROPOSED ACOUSTIC FENCE                                                           1856
                                                                                               1   27-08-20   FOR APPROVAL                    NN     CL                                                                                                                                                                                                                                       AT NOOSA CIVIC, WALTER HAY DRIVE
                                                                                               2   21-10-20   REVISED ISSUE                   JP     CL     DATUM           AHD                                                                                                                                                                                                                                                                                        SHEET:        OF
                                                                                                                                                            DESIGN           CL
                                                                                                                                                                                            0             5.0             10              15             20               25m        .................                                                                                        FOR STOCKWELL PTY LTD                                                              2        4


                                                                                                                                                                                                                                                                                Director: CAMERON LANDRETH                                                                                    DRAWING TITLE:                                                           DRAWING NUMBER         REV
                                                                                                                                                            DRAWN           NN
                                                                                                                                                                                                                        SCALE 1:500 A3                                                   (RPEQ 19358)                                                                                         ACOUSTIC FENCE SITE LAYOUT PLAN
                                                                                                                                                            DESIGN CHECK     CL
                                                                                                                                                                                                                                                                                DRAWING STATUS
                                                                                                                                                                                                                                                                                                                                   p 07 5443 8285                                                                                                                         ST02                 2
                                                                                                                                                                                            This drawing is not to be copied or amended without written permission from                                                            e [email protected] w www.barlowshelley.com.au
                                                                                                                                                            DATE           AUG 2020         Barlow Shelley Consulting Engineers                                                        FOR APPROVAL                                a PO Box 899 Maroochydore 4558    ABN 89 215 591 077

Page 3

                                                                                                                                                                                                                                                                                                                                                                                                     POST IDENTIFICATION TO BE VISIBLE
                                                                                                                                                                                                                                                                                                                                                                                                     ON REAR OUTSIDE FACE.
                                                                                                                                                                  PALINGS AS SPEC'D.

                                                                                                                                                                                                                                                                                                   ℄     END SPANS 1.5m             ℄   END SPANS 1.5m     ℄          INTERNAL SPAN 2.4m TYP                  ℄        INTERNAL SPAN 2.4m TYP                ℄    2.4m CRS
                                                                                                                                                                                                                                                                                                          END 2 BAYS                     END 2 BAYS                                                                                                               TYPICAL


                                                                                                                                                                                                                                                                                                                                                      BOUNDARY FACE                                                                                                                        SET OUT LINE

                                                                                                                                                                                                                                                                                              REFER TO CLEAT PLATE                                                                                TIMBER RAILS AS SPEC'D
                                                                                                                                           POST AS                                                                                                                                            DETAIL FOR RAIL FIXINGS
                                                                                                                                                                  RAILINGS AS SPEC'D. FIXED TO POST
                                                                                                                                            SPEC'D.
                                                                                                        1.80m HIGH FENCE




                                                                                                                                                                  CLEAT WITH NO. 14 TYPE 17 BATTEN
                                                                                                                                                                  SCREWS. REFER TO POST CLEAT
                                                                                                                                                                                                                                                                                                                                                             BARRIER ASSEMBLY PLAN LAYOUT NOT TO SCALE.
                                                                                                                                                                  DETAIL FOR NO. OF SCREWS REQUIRED.




                                                                                                                                                                                                                                                                                                                                                                                                                                                                      EXTERNAL TIMBER DURABILITY:
                                                                                                                                                                                                                                                                                                                                                                                                                                                                      ALL EXTERNAL TIMBER TO BE DURABILITY CLASS 1 OR
                                                                                                                                                                                                                                                                                                                                                                                                                                                                      BETTER IN ACCORDANCE WITH AS1720.1 AND AS1720.2.
                                                                                                                                                                         200x50 PINE SLEEPER (MIN.
                                                                                                                                                                                                                                                                                                                                                                                                                                                                      ALTERNATIVELY THE TIMBER CAN BE H4 TREATED IN
                                                                                                                                                                         H4 TREATED) FIXED WITH
                                                                                                                                                                                                                                                                                                                                                                                                                                                                      ACCORDANCE WITH AS1604.
                                                                                                                                                                         2x NO. 14 TYPE 17 BATTEN
                                                                                                                                                                         SCREWS EACH POST
                                                                                                                                               FSL



                                                                                                                                                                                                                                                                                                                                    8mm 6cfw CAP PLATE                                                                                                  45
                                                                                                                                                                                                                                                                                                                                    14Ø HOLE (CENTRAL) FOR HOT DIP GALV.                                                                                                     20 MIN. LAP
                                                                                                                                                                                                                                                                                                                                                                                                                                               30                30
                                                                                                        FOOTING DEPTH AS SPEC'D




                                                                                                                                                                                                                                                                                                                                    PLUG WITH SILICON DURING INSTALL
                                                                                                                                                                                                                                                                                                            225




                                                                                                                                                                                                                                                                                                                          20 MIN.
                                                                                                                                                                                                                                                                                                            75

                                                                                                                                                                                                                                                                                                                                    225x75x8 PLATE.




                                                                                                                                                                                                                                                                                                                          35
                                                                                                                                                                                                                                                                                    75


                                                                                                                                                                                                                                                                                                                                    6fw ALL SIDES TO RHS POST.                                                                                   FENCE
                                                                                                                                                                                                                                                                                              38

                                                                                                                                                                                                                                                                                                                  15      20        1x 8Ø HOLE FOR CONT. RAILS,                                                     3.15Ø RING SHANK GALV.       RAIL            3.15Ø RING SHANK
                                                                                                                                                                                                                                                                                                    26                              2x 10Ø HOLES (AS SHOWN)                                                         NAILS 75mm LONG                              GALV. NAILS 45mm LONG
                                                                                                                                                                                                                                                                                                                                    FOR RAIL ENDS.



                                                                                                                                                                           225 SQ x10 BASE PLATE
                                                                                                                                                                                                                                                                                                                                                                                                       PALING LAP DETAIL 1:10 @ A3
                                                                                                                                         300




                                                                                                                                                                           6CFW TO POST BASE
                                                                                                                                                                       FOOTINGS TO BE FOUND
                                                                                                                                                                                                                                                                                       POST CLEAT DETAIL                                                                                               CONTRACTOR TO CONFIRM PALING DENSITY COMPLIES WITH APPROVED ACOUSTIC REPORT.
                                                                                                                                                      AS SPEC'D
                                                                                                                                                                       INTO GROUND WITH MINIMUM
                                                                                                                                                                       BEARING CAPACITY OF 50kPa
                                                                                                                                                                                                                                                                                        SCALE 1:10 @ A3                                                                                                REFER TO TYPICAL TIMBER SPECIES DENSITY INFORMATION IN AS1720.
                                                                                                                                                                                                                                                                                                                                                                                                       REFER TO ARCHITECTURAL SPECIFICATIONS FOR ALL SET OUT DIMENSIONS, FINISHING,
                                                                                                                                                                                                                                                                                                                                                                                                       FLASHING, SURFACE FALLS AND WATER PROOFING. etc


                                                                                                   2.4m HIGH FENCE 1:20 @ A3
a:\1856 - noosa civic noosaville\acad structural\1856-lot_21_noosa_civic_acoustic_fence.dwg




                                                                                                                                                                                                                                                                                                                                              NOISE BARRIER SCHEDULE
                                                                                                   REFER TO ARCHITECTURAL SPECIFICATIONS FOR ALL SET OUT DIMENSIONS,
                                                                                                                                                                                                                                                                                                                       POST
                                                                                                   FINISHING, FLASHING, SURFACE FALLS AND WATER PROOFING. etc                                                         FENCE                          POST                                POST SIZE                                      POST BAYS               POST                 FOOTING              FOOTING                                                                             PALING           PALING
                                                                                                                                                                                                                                                                                                                       BAYS                                                                                                        RAIL SIZE                  RAIL SPACING
                                                                                                                                                                                                                      HEIGHT                       SIZE (INT.)                             (END)                                          (END)                LENGTH                 DEPTH               DIAMETER                                                                             SIZE           OVERLAP
                                                                                                                                                                                                                                                                                                                       (INT.)

                                                                                                                                                                                                                                                                                                                                                                                                                               100 x 50 F8 PINE RAILS
                                                                                                                                                                                                                                                     150 x 50 x 4.0                     150 x 50 x 4.0                                     1.5m WITHIN                                                                                                       3 RAILS @ 750 CRS MAX
                                                                                                                                                                                                                                                                                                                                                                                                                                (MIN 2x POST SPANS)                                         100 x 25 x 1800
                                                                                                                                                                                                                           1.80m                     Gr350 H.D.G.                     Gr350 H.D.G. RHS,                 2.40m             3.0m OF END             3.00m                  1.50m                  350Ø                                            SPACING TYPICAL.                               MIN 40%
                                                                                                                                                                                                                                                                                                                                                                                                                               200 x 50 PINE SLEEPER                                         MIN F8 H'WD
                                                                                                                                                                                                                                                         RHS                         WITHIN 3.0m OF END                                   (END 2 BAYS)                                                                                                        (EXCL. PINE SLEEPER)
                                                                                                                                                                                                                                                                                                                                                                                                                                    (H4 TREATED)



                                                                                                                                                                                                                                                                                                                                                                                                                    PROJECT:                                                                                       JOB NUMBER
                                                                                              REV DATE DESCRIPTION                                                BY      CHKD            DETAILS                                             SCALE                                                      APPROVED                                                                                                   PROPOSED ACOUSTIC FENCE                                                                             1856
                                                                                               1    27-08-20                      FOR APPROVAL                    NN        CL                                                                                                                                                                                                                                      AT NOOSA CIVIC, WALTER HAY DRIVE
                                                                                               2    21-10-20                      REVISED ISSUE                   JP        CL   DATUM                AHD                                                                                                                                                                                                                                                                                                      SHEET:        OF
                                                                                                                                                                                 DESIGN                CL
                                                                                                                                                                                                                                                                                                       .................                                                                                            FOR STOCKWELL PTY LTD                                                                                3        4


                                                                                                                                                                                                                                                                                               Director: CAMERON LANDRETH                                                                                           DRAWING TITLE:                                                                             DRAWING NUMBER         REV
                                                                                                                                                                                 DRAWN                NN                                 AS NOTED
                                                                                                                                                                                                                                                                                                          (RPEQ 19358)                                                                                              TYPICAL ACOUSTIC FENCE SECTION & DETAILS
                                                                                                                                                                                 DESIGN CHECK          CL
                                                                                                                                                                                                                                                                                                   DRAWING STATUS
                                                                                                                                                                                                                                                                                                                                                         p 07 5443 8285                                                                                                                                           ST03                 2
                                                                                                                                                                                                                This drawing is not to be copied or amended without written permission from                                                              e [email protected] w www.barlowshelley.com.au   SHEET 1 OF 1
                                                                                                                                                                                 DATE                AUG 2020   Barlow Shelley Consulting Engineers                                                      FOR APPROVAL                                    a PO Box 899 Maroochydore 4558    ABN 89 215 591 077

Page 4

                                                                                                                                                                      WORKPLACE HEALTH & SAFETY NOTES
                                                                                                                               THESE WORK HEALTH & SAFETY NOTES MUST BE PROVIDED TO ALL OWNERS, BUILDING CONTRACTORS, SUB-CONTRACTORS, CONSULTANTS, RENOVATORS, OPERATORS, MAINTENANCE PERSONNEL, DEMOLITION CONTRACTORS, & ALL
                                                                                                                                  OTHERS ASSOCIATED WITH PERFORMING WORK ON/OR WITHIN THE BUILDING & SURROUNDS. THE WORK HEALTH & SAFETY NOTES ARE TO BE FULLY READ & UNDERSTOOD BY ALL PERSONS PRIOR TO COMMENCING ANY WORK.
                                                                                              1. FALLS, SLIPS, TRIPS                                                                 BUILDING COMPONENTS                                                                                                                                                                                7. CONFINED SPACES
                                                                                                                                                                                     DURING CONSTRUCTION, RENOVATION OR DEMOLITION OF THIS BUILDING,                                              THESE SHOULD BE FULLY MAINTAINED IN ACCORDANCE WITH MANUFACTURER'S
                                                                                              A. WORKING AT HEIGHTS                                                                                                                                                                               SPECIFICATIONS & NOT USED WHERE FAULTY OR ( IN THE CASE OF ELECTRICAL                   EXCAVATIONS
                                                                                                                                                                                     PARTS OF THE STRUCTURE INCLUDING FABRICATED STEELWORK, HEAVY
                                                                                                 DURING CONSTRUCTION                                                                 PANELS & MANY OTHER COMPONENTS WILL REMAIN STANDING PRIOR TO OR                                              EQUIPMENT ) NOT CARRYING A CURRENT ELECTRICAL SAFETY TAG. ALL                           CONSTRUCTION OF THIS BUILDING & SOME MAINTENANCE ON THE BUILDING
                                                                                                   WHEREVER POSSIBLE, COMPONENTS FOR THIS BUILDING SHOULD BE                                                                                                                                      SAFETY GUARDS OR DEVICES SHOULD BE REGULARLY CHECKED & PERSONAL                         WILL REQUIRE EXCAVATION & INSTALLATION OF ITEMS WITHIN EXCAVATIONS.
                                                                                                                                                                                     AFTER SUPPORTING PARTS ARE IN PLACE. CONTRACTORS SHOULD ENSURE                                                                                                                                       WHERE PRACTICAL, INSTALLATION SHOULD BE CARRIED OUT USING METHODS
                                                                                                   PREFABRICATED OFF-SITE OR AT GROUND LEVEL TO MINIMISE THE RISK OF                 THAT TEMPORARY BRACING OR OTHER REQUIRED SUPPORT IS IN PLACE AT ALL                                          PROTECTIVE EQUIPMENT SHOULD BE USED IN ACCORDANCE WITH
                                                                                                   WORKERS FALLING MORE THAN TWO METRES. HOWEVER, CONSTRUCTION OF                                                                                                                                 MANUFACTURER'S SPECIFICATION.                                                           WHICH DO NOT REQUIRE WORKERS TO ENTER THE EXCAVATION. WHERE THIS
                                                                                                                                                                                     TIMES WHEN COLLAPSE WHICH MAY INJURE PERSONS IN THE AREA IS A                                                                                                                                        IS NOT PRACTICAL, ADEQUATE SUPPORT FOR THE EXCAVATED AREA SHOULD
                                                                                                   THIS BUILDING WILL REQUIRE WORKERS TO BE WORKING AT HEIGHTS WHERE A               POSSIBILTY. MECHANICAL LIFTING OF MATERIALS & COMPONENTS DURING
                                                                                                   FALL IN EXCESS OF TWO METRES IS POSSIBLE & INJURY IS LIKELY TO RESULT                                                                                                                                                                                                                  BE PROVIDED TO PREVENT COLLAPSE. WARNING SIGNS & BARRIERS TO
                                                                                                   FROM SUCH A FALL. THE BUILDER SHOULD PROVIDE A SUITABLE BARRIER
                                                                                                                                                                                     CONSTRUCTION, MAINTENANCE OR DEMOLITION PRESENTS A RISK OF FALLING                                         6. HAZARDOUS SUBSTANCES                                                                   PREVENT ACCIDENTAL OR UNAUTHORISED ACCESS TO ALL EXCAVATIONS
                                                                                                                                                                                     OBJECTS. CONTRACTORS SHOULD ENSURE THAT APPROPRIATE LIFTING                                                ASBESTOS IN EXISTING BUILDINGS                                                            SHOULD BE PROVIDED.
                                                                                                   WHEREVER A PERSON IS REQUIRED TO WORK IN A SITUATION WHERE FALLING                DEVICES ARE USED, THAT LOADS ARE PROPERLY SECURED & THAT ACCESS TO
                                                                                                   MORE THAN TWO METRES IS A POSSIBILITY.                                            AREAS BELOW THE LOAD IS PREVENTED OR RESTRICTED.
                                                                                                                                                                                                                                                                                                  BUILDING CONSTRUCTED PRIOR TO 1990
                                                                                                                                                                                                                                                                                                  WHEREVER POSSIBLE, COMPONENTS FOR THIS BUILDING SHOULD BE PARKING                       ENCLOSED SPACES
                                                                                                   DURING OPERATION OR MAINTENANCE                                               3. TRAFFIC MANAGEMENT
                                                                                                                                                                                                                                                                                                  IF THIS BUILDING WAS CONSTRUCTED PRIOR TO 1990 & THEREFORE MAY                          ENCLOSED SPACES WITHIN THIS BUILDING MAY PRESENT A RISK TO PERSONS
                                                                                                   CLEANING & MAINTENANCE OF WINDOWS, WALLS, ROOF OR OTHER                                                                                                                                        CONTAIN ASBESTOS EITHER IN CLADDING MATERIAL OR IN FIRE RETARDENT                       ENTERING FOR CONSTRUCTION, MAINTENANCE OR ANY OTHER PURPOSE. THE
                                                                                                   COMPONENTS OF THIS BUILDING WILL REQUIRE PERSONS TO BE SITUATED                   MAJOR ROAD, NARROW ROAD, OR STEEPLY SLOPING ROAD                                                             INSULATION MATERIAL. THE BUILDER SHOULD CHECK &, IF NECESSARY, TAKE                     DESIGN DOCUMENTATION CALLS FOR WARNING SIGNS & BARRIERS TO
                                                                                                   WHERE A FALL FROM A HEIGHT IN EXCESS OF TWO METRES IS POSSIBLE.                   WHEREVER POSSIBLE, COMPONENTS FOR THIS BUILDING SHOULD BE PARKING                                            APPROPRIATE ACTION BEFORE DEMOLISHING, CUTTING, SANDING, DRILLING OR                    UNAUTHORISED ACCESS. THESE SHOULD BE MAINTAINED THROUGHOUT THE
                                                                                                   WHERE THIS TYPE OF ACTIVITY IS REQUIRED, SCAFFOLDING, LADDERS OR                  OF VEHICLES OR LOADING/UNLOADING OF VEHICLES ON THIS ROADWAY MAY                                             OTHERWISE DISTURBING THE EXISTING STRUCTURE.                                            LIFE OF THE BUILDING. WHERE WORKERS ARE REQUIRED TO ENTER ENCLOSED
                                                                                                   TRESTLES SHOULD BE USED IN ACCORDANCE WITH RELEVANT CODES OF                      CAUSE A TRAFFIC HAZARD. DURING CONSTRUCTION, MAINTENANCE OR                                                                                                                                          SPACES, AIR TESTING EQUIPMENT & PERSONAL PROTECTIVE EQUIPMENT
                                                                                                   PRACTICE, REGULATIONS OR LEGISLATION. WHERE CLEANING & MAINTENANCE                DEMOLITION OF THIS BUILDING DESIGNATED PARKING FOR WORKERS &                                                 BUILDING CONSTRUCTED PRIOR TO 1986                                                      SHOULD BE PROVIDED.
                                                                                                   OF ANY COMPONENTS OF/OR INSTALLATIONS WITHIN THIS BUILDING MEANS                  LOADING AREAS SHOULD BE PROVIDED. TRAINED TRAFFIC MANAGEMENT                                                 IF THIS BUILDING WAS CONSTRUCTED PRIOR TO 1986 & THEREFORE IS LIKELY
                                                                                                   THAT THE USE OF LADDERS OR TRESTLES ARE NOT APPROPRIATE,                          PERSONNEL SHOULD BE RESPONSIBLE FOR THE SUPERVISION OF THESE                                                 TO CONTAIN ASBESTOS EITHER IN CLADDING MATERIAL OR IN FIRE RETARDENT                    SMALL SPACES
                                                                                                   SCAFFOLDING, FALL BARRIERS OR PERSONAL PROTECTIVE EQUIPMENT (PPE)                 AREAS.                                                                                                       INSULATION MATERIAL. THE BUILDER SHOULD CHECK &, IF NECESSARY, TAKE                     SOME SMALL SPACES WITHIN THIS BUILDING WILL REQUIRE ACCESS BY
                                                                                                   SHOULD BE USED IN ACCORDANCE WITH RELEVANT CODES OF PRACTICE,                                                                                                                                  APPROPRIATE ACTION BEFORE DEMOLISHING, CUTTING, SANDING, DRILLING OR                    CONSTRUCTION OR MAINTENANCE WORKERS. THE DESIGN DOCUMENTATION
                                                                                                   REGULATIONS & LEGISLATION. ANCHORAGE POINTS FOR PORTABLE SCAFFOLD                 RESTRICTED ON-SITE LOADING/UN-LOADING                                                                        OTHERWISE DISTURBING THE EXISTING STRUCTURE.                                            CALLS FOR WARNING SIGNS & BARRIERS TO UNAUTHORISED ACCESS. THESE
                                                                                                   OR FALL ARREST DEVICES ARE TO BE INSTALLED ON/WITHIN THE BUILDING FOR             CONSTRUCTION OF THIS BUILDING WILL REQUIRE LOADING & UNLOADING OF                                                                                                                                    SHOULD BE MAINTAINED THROUGHOUT THE LIFE OF THE BUILDING. WHERE
                                                                                                   USE BY MAINTENANCE WORKERS. ANY PERSONS ENGAGED TO WORK ON THE                    MATERIALS ON THE ROADWAY. DELIVERIES SHOULD BE WELL PLANNED TO                                               POWDERED MATERIALS                                                                      WORKERS ARE REQUIRED TO ENTER SMALL SPACES THEY SHOULD BE
                                                                                                   BUILDING AFTER THE COMPLETION OF CONSTRUCTION WORK SHOULD BE                      AVOID CONGESTION OF LOADING AREAS & TRAINED TRAFFIC MANAGEMENT                                               MANY MATERIALS USED IN THE CONSTRUCTION OF THIS BUILDING CAN CAUSE                      SCHEDULED SO THAT ACCESS IS FOR SHORT PERIODS. MANUAL LIFTING &
                                                                                                   INFORMED ABOUT THE ANCHORAGE POINTS.                                              PERSONNEL SHOULD BE USED TO SUPERVISE LOADING/UNLOADING AREAS.                                               HARM IF INHALED IN POWDERED FORM. PERSONS WORKING ON OR IN THE                          OTHER MANUAL ACTIVITY SHOULD BE RESTRICTED IN SMALL SPACES.
                                                                                                                                                                                     BUSY CONSTRUCTION & DEMOLITION SITES PRESENT A RISK OF COLLISION                                             BUILDING DURING CONSTRUCTION, OPERATIONAL MAINTENANCE OR
                                                                                              B. SLIPPERY OR UNEVEN SURFACES                                                         WHERE DELIVERIES & OTHER TRAFFIC ARE MOVING WITHIN THE SITE. A                                               DEMOLITION SHOULD ENSURE GOOD VENTILATION & WEAR PERSONAL                             8. PUBLIC ACCESS
                                                                                                 FLOOR FINISHES                                                                      TRAFFIC MANAGEMENT PLAN SUPERVISED BY TRAINED TRAFFIC MANAGEMENT                                             PROTECTIVE EQUIPMENT INCLUDING PROTECTION AGAINST INHALATION WHILE                     PUBLIC ACCESS TO CONSTRUCTION & DEMOLITION SITES & TO AREAS UNDER
                                                                                                   SPECIFIED FINISHES MUST BE SELECTED TO MINIMISE THE RISK OF FLOORS &              PERSONNEL SHOULD BE ADOPTED FOR THE WORK SITE.                                                               USING POWDERED MATERIAL OR WHEN SANDING, DRILLING, CUTTING OR                          MAINTENANCE CAUSES RISK TO WORKERS & PUBLIC. WARNING SIGNS & SECURE
                                                                                                   PAVED AREAS BECOMING SLIPPERY WHEN WET OR WHEN WALKED ON WITH                                                                                                                                  OTHERWISE DISTURBING OR CREATING POWDERED MATERIAL.                                    BARRIERS TO UNAUTHORISED ACCESS SHOULD BE PROVIDED. WHERE
                                                                                                   WET SHOES/FEET. ANY CHANGES TO THE SPECIFIED FINISH SHOULD BE MADE            4. SERVICES                                                                                                                                                                                             ELECTRICAL INSTALLATIONS, EXCAVATIONS, PLANT OR LOOSE MATERIALS ARE
                                                                                                   IN CONSULTATION WITH THE DESIGNER OR, IF THIS IS NOT PRACTICAL,                   RUPTURE OF SERVICES DURING EXCAVATION OR OTHER ACTIVITY CREATES A                                            TREATED TIMBER                                                                         PRESENT THEY SHOULD BE SECURED WHEN NOT FULLY SUPERVISED.
                                                                                                   SURFACES WITH AN EQUIVALENT OR BETTER SLIP RESISTANCE SHOULD BE                   VARIETY OF RISKS INCLUDING RELEASE OF HAZARDOUS MATERIAL. EXISTING                                           THE DESIGN OF THIS BUILDING INCLUDES PROVISION FOR THE INCLUSION OF
                                                                                                   USED. THE OWNER IS RESPONSIBLE FOR THE SELECTION OF SURFACE FINISHES              SERVICES ARE LOCATED ON OR AROUND THIS SITE. WHERE KNOWN, THESE                                              TREATED TIMBER WITHIN THE STRUCTURE. DUST OR FUMES FROM THIS                          9. OPERATIONAL USE OF BUILDING
                                                                                                   IN THE PEDESTRIAN TRAFFICABLE AREAS OF THIS BUILDING. SURFACES                    ARE IDENTIFIED ON THE PLANS BUT THE EXACT LOCATION & EXTENT OF                                               MATERIAL CAN BE HARMFUL. PERSONS WORKING ON OR IN THE BUILDING                         RESIDENTIAL BUILDINGS
                                                                                                   SHOULD BE SELECTED IN ACCORDANCE WITH AS HB 197:1999 & AS/NZ 4586:2004.           SERVICES MAY VARY FROM THAT INDICATED. SERVICES SHOULD BE LOCATED                                            DURING CONSTRUCTION, OPERATIONAL MAINTENANCE OR DEMOLITION SHOULD
                                                                                                                                                                                                                                                                                                                                                                                         WHERE THE BUILDING HAS BEEN DESIGNED AS A RESIDENTIAL BUILDING, & AT A
                                                                                                                                                                                     USING AN APPROPRIATE SERVICE ( SUCH AS DIAL BEFORE YOU DIG ),                                                ENSURE GOOD VENTILATION & WEAR PERSONAL PROTECTIVE EQUIPMENT
                                                                                                                                                                                                                                                                                                                                                                                         LATER DATE IS USED OR INTENDED AS A WORKPLACE, THE PROVISIONS OF THE
                                                                                                   STEPS, LOOSE OBJECTS & UNEVEN SURFACES                                            APPROPRIATE EXCAVATION PRACTICE SHOULD BE USED &, WHERE NECESSARY,                                           INCLUDING PROTECTION AGAINST INHALATION OF HARMFUL MATERIAL WHEN
                                                                                                                                                                                                                                                                                                                                                                                         WORK HEALTH & SAFETY ACT 2011 OR SUBSEQUENT REPLACEMENT ACT SHOULD
                                                                                                   DUE TO DESIGN RESTRICTIONS FOR THIS BUILDING, STEPS &/OR RAMPS ARE                SPECIALIST CONTRACTORS SHOULD BE USED.                                                                       SANDING, DRILLING, CUTTING OR USING TREATED TIMBER IN ANY WAY THAT
                                                                                                                                                                                                                                                                                                                                                                                         BE APPLIED TO THE NEW USE.
                                                                                                   INCLUDED IN THE BUILDING WHICH MAY BE A HAZARD TO WORKERS CARRYING                                                                                                                             MAY CAUSE HARMFUL MATERIAL TO BE RELEASED. DO NOT BURN TREATED
                                                                                                   OBJECTS OR OTHERWISE OCCUPIED. STEPS SHOULD BE CLEARLY MARKED                     SITES WITH UNDERGROUND POWER                                                                                 TIMBER.
                                                                                                                                                                                                                                                                                                                                                                                         NON-RESIDENTIAL BUILDINGS - END USE UNKNOWN
                                                                                                   WITH BOTH VISUAL & TACTILE WARNINGS DURING CONSTRUCTION,                          UNDERGROUND POWER LINES ARE LOCATED IN OR AROUND THIS SITE. ALL                                                                                                                                     THE BUILDING HAS BEEN DESIGNED TO REQUIREMENTS OF THE CLASSIFICATION
                                                                                                   MAINTENANCE, DEMOLITION & AT ALL TIMES WHEN THE BUILDING OPERATES AS              UNDERGROUND POWER LINES MUST BE DISCONNECTED OR CAREFULLY                                                    VOLATILE ORGANIC COMPOUNDS                                                             IDENTIFIED ON THE DRAWINGS. THE SPECIFIC USE OF THE BUILDING IS NOT
                                                                                                   A WORKPLACE. BUILDING OWNERS & OCCUPIERS SHOULD MONITOR THE                       LOCATED & ADEQUATE WARNING SIGNS USED PRIOR TO ANY CONSTRUCTION,                                             MANY TYPES OF GLUE, SOLVENTS, SPRAY PACKS, PAINTS, VARNISHES & SOME
                                                                                                                                                                                                                                                                                                                                                                                         KNOWN AT THE TIME OF THE DESIGN & A FURTHER ASSESSMENT OF THE
                                                                                                   PEDESTRIAN ACCESS WAYS & IN PARTICULAR, ACCESS TO AREAS WHERE                     MAINTENANCE OR DEMOLITION COMMENCING.                                                                        CLEANING MATERIALS HAVE DANGEROUS EMISSIONS. AREAS WHERE THESE
                                                                                                                                                                                                                                                                                                                                                                                         WORKPLACE HEALTH & SAFETY ISSUES SHOULD BE UNDERTAKEN AT THE TIME
                                                                                                   MAINTENANCE IS ROUTINELY CARRIED OUT TO ENSURE THAT SURFACES HAVE                                                                                                                              ARE USED SHOULD BE KEPT WELL VENTILATED WHILE THE MATERIAL IS BEING
                                                                                                                                                                                                                                                                                                                                                                                         OF FIT-OUT FOR THE END-USER.
                                                                                                   NOT MOVED OR CRACKED SO THAT THEY BECOME UNEVEN & PRESENT A TRIP                  SITES WITH OVERHEAD POWER LINES                                                                              USED & FOR A PERIOD AFTER INSTALLATION. PERSONAL PROTECTIVE
                                                                                                   HAZARD. SPILLS, LOOSE MATERIAL, STRAY OBJECTS OR ANY OTHER MATTER                 OVERHEAD POWER LINES ARE NEAR OR ON THIS SITE. THESE POSE A RISK OF                                          EQUIPMENT MAY ALSO BE REQUIRED. THE MANUFACTURER'S
                                                                                                   THAT MAY CAUSE A SLIP OR TRIP HAZARD SHOULD BE CLEANED OR REMOVED                                                                                                                              RECOMMENDATIONS FOR USE MUST BE CAREFULLY CONSIDERED AT ALL TIMES.                     NON-RESIDENTIAL BUILDINGS - END USE KNOWN
                                                                                                                                                                                     ELECTROCUTION IF STRUCK OR APPROACHED BY LIFTING DEVICES OR OTHER                                                                                                                                   THIS BUILDING HAS BEEN DESIGNED FOR THE SPECIFIC USE AS IDENTIFIED ON
                                                                                                   FROM ACCESS WAYS. CONTRACTORS SHOULD BE REQUIRED TO MAINTAIN A                    PLANT & PERSONS WORKING ABOVE GROUND LEVEL. WHERE THERE IS A                                                                                                                                        THE DRAWINGS. WHERE A CHANGE OF USE OCCURS AT A LATER DATE A
                                                                                                   TIDY WORK SITE DURING CONSTRUCTION, MAINTENANCE OR DEMOLITION TO                  DANGER OF THIS OCCURING, POWER LINES SHOULD BE, WHERE PRACTICAL,                                             SYNTHETIC MINERAL FIBRES                                                               FURTHER ASSESSMENT OF THE WORKPLACE HEALTH & SAFETY ISSUES SHOULD
                                                                                                   REDUCE THE RISK OF TRIPS & FALLS IN THE WORKPLACE. MATERIALS FOR                  DISCONNECTED OR RELOCATED. WHERE THIS IS NOT PRACTICAL ADEQUATE                                              FIBREGLASS, ROCKWOOL, CERAMIC & OTHER MATERIAL USED FOR THERMAL
                                                                                                   CONSTRUCTION OR MAINTENANCE SHOULD BE STORED IN DESIGNATED AREAS                                                                                                                                                                                                                      BE UNDERTAKEN.
                                                                                                                                                                                     WARNING IN THE FORM OF BRIGHT COLOURED TAPE OR SIGNAGE SHOULD BE                                             OR SOUND INSULATION MAY CONTAIN SYNTHETIC MINERAL FIBRE WHICH MAY
                                                                                                   AWAY FROM ACCESS WAYS & WORK AREAS.                                               USED OR A PROTECTIVE BARRIER PROVIDED.                                                                       BE HARMFUL IF INHALED OR IF IT COMES IN CONTACT WITH THE SKIN, EYES OR
                                                                                                                                                                                                                                                                                                  OTHER SENSITIVE PARTS OF THE BODY. PERSONAL PROTECTIVE EQUIPMENT                      10. OTHER HIGH RISK ACTIVITY
                                                                                              2. FALLING OBJECTS                                                                 5. MANUAL TASKS                                                                                                  INCLUDING PROTECTION AGAINST INHALATION OF HARMFUL MATERIAL SHOULD                     ALL ELECTRICAL WORK SHOULD BE CARRIED OUT IN ACCORDANCE WITH THE
a:\1856 - noosa civic noosaville\acad structural\1856-lot_21_noosa_civic_acoustic_fence.dwg




                                                                                                                                                                                                                                                                                                  BE USED WHEN INSTALLING, REMOVING OR WORKING NEAR BULK INSULATION                      FOLLOWING CODE OF PRACTICE:
                                                                                                   LOOSE MATERIALS OR SMALL OBJECTS                                                  COMPONENTS WITHIN THIS DESIGN WITH A MASS IN EXCESS OF 25KG SHOULD                                                                                                                                  MANAGING ELECTRICAL RISKS AT THE WORKPLACE, AS/NZ 3012 & ALL LICENSING
                                                                                                                                                                                                                                                                                                  MATERIAL.
                                                                                                   CONSTRUCTION, MAINTENANCE OR DEMOLITION WORK ON OR AROUND THIS                    BE LIFTED BY TWO OR MORE WORKERS OR BY MECHANICAL LIFTING DEVICE.                                                                                                                                   REQUIREMENTS.
                                                                                                   BUILDING IS LIKELY TO INVOLVE PERSONS WORKING ABOVE GROUND LEVEL OR               WHERE THIS IS NOT PRACTICAL, SUPPLIERS OR FABRICATORS SHOULD BE                                                                                                                                     ALL WORK USING PLANT SHOULD BE CARRIED OUT IN ACCORDANCE WITH THE
                                                                                                   ABOVE FLOOR LEVELS. WHERE THIS OCCURS ONE OR MORE OF THE                          REQUIRED TO LIMIT THE COMPONENT MASS. ALL MATERIAL PACKAGING,                                                TIMBER FLOORS
                                                                                                                                                                                                                                                                                                  THIS BUILDING CONTAINS TIMBER FLOORS WHICH HAVE AN APPLIED FINISH.                     FOLLOWING CODE OF PRACTICE:
                                                                                                   FOLLOWING MEASURES SHOULD BE TAKEN TO AVOID OBJECTS FALLING FROM                  BUILDING & MAINTENANCE COMPONENTS SHOULD CLEARLY SHOW THE TOTAL                                                                                                                                     MANAGING RISKS OF PLANT AT THE WORKPLACE.
                                                                                                   THE AREA WHERE THE WORK IS BEING CARRIED OUT OVER PERSONS BELOW.                  MASS OF PACKAGES & WHERE PRACTICAL ALL ITEMS SHOULD BE STORED ON                                             AREAS WHERE FINISHES ARE APPLIED SHOULD BE KEPT WELL VENTILATED
                                                                                                                                                                                                                                                                                                  DURING SANDING & APPLICATION, & FOR A PERIOD AFTER INSULATION.                         ALL WORK SHOULD BE CARRIED OUT IN ACCORDANCE WITH THE FOLLOWING
                                                                                                   1. PREVENT OR RESTRICT ACCESS TO AREAS BELOW WHERE THE WORK IS                    SITE IN A WAY WHICH MINIMISES BENDING BEFORE LIFTING. ADVICE SHOULD BE                                                                                                                              CODE OF PRACTICE:
                                                                                                       BEING CARRIED OUT.                                                            PROVIDED ON SAFE LIFTING METHODS IN ALL AREAS WHERE LIFTING MAY                                              PERSONAL PROTECTIVE EQUIPMENT MAY ALSO BE REQUIRED. THE
                                                                                                                                                                                                                                                                                                  MANUFACTURER'S RECOMMENDATIONS FOR USE MUST BE CAREFULLY                               MANAGING NOISE & PREVENTING HEARING LOSS AT WORK.
                                                                                                   2. PROVIDE TOEBOARDS TO SCAFFOLDING OR WORK PLATFORMS.                            OCCUR. CONSTRUCTION, MAINTENANCE & DEMOLITION OF THIS BUILDING WILL                                                                                                                                 DUE TO THE HISTORY OF SERIOUS INCIDENTS IT IS RECOMMENDED THAT
                                                                                                   3. PROVIDE PROTECTIVE STRUCTURES BELOW THE WORK AREA.                             REQUIRE THE USE OF PORTABLE TOOLS & EQUIPMENT.                                                               CONSIDERED AT ALL TIMES.
                                                                                                                                                                                                                                                                                                                                                                                         PARTICULAR CARE BE EXERCISED WHEN UNDERTAKING WORK INVOLVING STEEL
                                                                                                   4. ENSURE THAT ALL PERSONS BELOW THE WORK AREA HAVE PERSONAL                                                                                                                                                                                                                          CONSTRUCTION & CONCRETE PLACEMENT. ALL THE ABOVE APPLIES.
                                                                                                       PROTECTIVE EQUIPMENT
                                                                                                                                                                                                                                                                                                                                                                       PROJECT:                                                                 JOB NUMBER
                                                                                              REV DATE DESCRIPTION                             BY   CHKD            DETAILS                                        SCALE                                                APPROVED                                                                                       PROPOSED ACOUSTIC FENCE                                                       1856
                                                                                               1    27-08-20   FOR APPROVAL                    NN    CL                                                                                                                                                                                                                AT NOOSA CIVIC, WALTER HAY DRIVE
                                                                                               2    21-10-20   REVISED ISSUE                   JP    CL    DATUM           AHD                                                                                                                                                                                                                                                              SHEET:        OF
                                                                                                                                                           DESIGN           CL
                                                                                                                                                                                                                                                                       .................                                                                               FOR STOCKWELL PTY LTD                                                          4        4


                                                                                                                                                                                                                                                                   Director: CAMERON LANDRETH                                                                          DRAWING TITLE:                                                       DRAWING NUMBER         REV
                                                                                                                                                           DRAWN           NN
                                                                                                                                                                                                                                                                         (RPEQ 19358)                                                                                  WORKPLACE HEALTH & SAFETY NOTES
                                                                                                                                                           DESIGN CHECK     CL
                                                                                                                                                                                                                                                                   DRAWING STATUS
                                                                                                                                                                                                                                                                                                            p 07 5443 8285                                                                                                                     ST04                 2
                                                                                                                                                                                     This drawing is not to be copied or amended without written permission from                                            e [email protected] w www.barlowshelley.com.au
                                                                                                                                                           DATE           AUG 2020   Barlow Shelley Consulting Engineers                                                FOR APPROVAL                        a PO Box 899 Maroochydore 4558    ABN 89 215 591 077

Used in these records

About this file

File size
758 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

1856-Lot_21_Noosa_Civic_Acoustic_Fence Rev_2.pdf · 758 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.