Council archive · source document
Attachment 15- Amended Water Supply and Sewerage Analysis MCU12/0208
Very large file (11.7 MB): the original may take a few minutes to open or download. The page text below is quick to read.
Noosa on Weyba
Water Supply and Sewerage Analysis
5.3 Noosa on Weyba Network
A network of trunk mains and smaller reticulations mains is required to maintain Unitywater’s DSS within the
Noosa on Weyba development. A hydraulic model was developed based on the results of the MWH report.
The network pressures identified in the MWH report have been adopted for the analysis of the Noosa on
Weyba development.
A primary connection to the existing 600mm diameter trunk main along Eenie Creek Road via a 250 mm
diameter main along Walter Hay Drive is proposed. This main will provide the bulk of flow to the development
and is required to maintain non-residential fire flows (30l/s) to the development.
A second 200 mm diameter connection to the existing mains at Lake Entrance Boulevard should be
considered. This main would assist in the provision of flow to the western properties within the Noosa on
Weyba development. It is not critical to maintain supply pressures as per the DSS to the proposed
development. However, the main would reduce dead ends in the proposed network. An internal 200 mm
diameter distribution main is proposed to convey flow to each precinct within the development. Some smaller
150 mm diameter mains will be required to maintain the fire flow DSS. The rest of the network would
comprise 100mm diameter mains as required to service properties. Due to the mains proposed to service the
development, the ownership and operation of the proposed infrastructure would be granted to Unitywater.
Figure 1 (Appendix A), illustrates the NIDMA network and the proposed mains (150mm and greater) to
service the Noosa on Weyba development. Final alignment and configuration of the network will be
determined during the determination of the final development of the lot layouts.
Northbrook Corporation Pty. Ltd. Version 4 17 September 2013
5101-19 Commercial in Confidence Page 8
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Attachment 15- Amended Water Supply and Sewerage Analysis MCU12/0208Related documentApplication case desk ↗
About this file
- File size
- 11.7 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.