Noosa on Weyba Water Network Performance Assessment
Table 2-1: EP Summary for Proposed Noosa on Weyba Development
Quantity EP Density Adopted EP
Residential Lots 494 lots 3.3 EP x lot 1,630.2
Mixed Use Residential 339 lots 2.3 EP x lot 779.7
(Townhouses/Units/Retirement (assumed 2 bedroom
Village) unit)
Retail Space 600 m2 100 EP per ha 6
Total 2,415.9
The water supply demands as flows for the proposed development were supplied by Cardno and
confirmed by MWH. A Peak Hour demand of 31 L/s and a fire flow demand of 51 L/s (30 L/s + 2/3
maximum hour) at the development site were confirmed. Table 2-2 details the demand distribution into
the H2OMAP Water model. The location of proposed development connections are shown in Figure 2-1.
Table 2-2: Model Demand for Proposed Noosa on Weyba Development
Option 1 Option 2 Option 3
Model Junction ID /
Description Peak Fire Peak Fire Peak Fire
Hour Flow Hour Flow Hour Flow
(L/s) (L/s) (L/s) (L/s)^ (L/s) (L/s)
NOOSA_ON_WEYBA_CONN1, 31.32 50.88 31.32 50.88 31.32 50.88
proposed development
connection #1
NOOSA_ON_WEYBA_CONN2, - - 3 32 - -
proposed development
connection #2
^ Both fire flow demands do not occur simultaneously
3 Standards of Service
The standards of service for water supply applicable to this investigation are as follows:
• Minimum residual pressure >= 22 m
• Fire flow demand assessed at 2/3 PH demand
• Minimum pressure under fire flow demand at hydrant = 12 m
• Maximum velocity = 2.5 L/s
The above standards have been been adopted from the Unitywater Desired Standards of Service.
Status: Draft 22/06/2012
Project number: Page 3 Our ref: Noosa on Weyba WS Assessment.docx
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Attachment 15- Amended Water Supply and Sewerage Analysis MCU12/0208Related documentApplication case desk ↗
About this file
- File size
- 11.7 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.