1     INTRODUCTION

SCG Consulting Engineers has performed a limited site investigation and established a site classification in
accordance with AS 2870-2011 and made recommendations based upon the classification for a building to be
constructed at the above site. This report does not include an assessment of Slope Stability, Landslide Risk, or
specifications for damp proofing, termite protection or moisture barriers.

This soil test and footing report relates only to the above property and the proposed construction as described
below:

                        Proposed Construction                        Residential Dwelling
                            External Walls                             Masonry/Timber
                            Internal Walls                                  Timber
                            Ground Floor                               Slab on Ground
                             Upper Floor                                    Timber
                           Building Platform                              Cut Fill Pad
                         Masonry Articulation                       Required @ 8 m centres

          This report must be read and considered as a whole. All of our recommendations, foundation
          plans, sections and appendices must be read, considered and followed by all people involved
          in this project including the client to ensure adequate long term performance of the footing
          system constructed on this site. A copy of this report must remain with the client or final
          owner of the building upon completion of the proposed works. If you are unsure of any
          of the requirements herein, you must seek clarification from this office.


2     SITE CLASSIFICATION

After considering the results of our field investigation performed on we have classified this site in accordance with
AS 2870-2011 as:

                                                      Class P

The classification has been calculated from test work performed on the soil profile encountered on the day of our
fieldwork and consideration of AS2870-2011. Any disturbance of the soil profile may result in a change to the
classification.

The ‘P’ classification relates to the loose sands and poor bearing capacity encountered during our testing on site.
Please refer to our definitions list appended to this report for further descriptions of these characteristics.

The abnormal moisture conditions are due to poor drainage within the allotment, the presence and proximity of
trees to the allotment and existing trees located on the proposed construction area that will be removed.

With respect to potential surface movements through seasonal moisture variations, the site could be considered
equivalent to a class S site.

The site preparation details that follow have allowed for the influence of the earthworks described in section 5.0
below.

Site Classification: The site classification is calculated in accordance with the “AS2870-2011 Residential Slabs
and Footings-Construction” and relates to the estimation of Ys, “The characteristic surface movement” within
reactive soil profiles. The limits used for this classification are as follows:

                             Predicted Surface Movement           Classification

                             Ys = <=20mm                          S       Slight
                             Ys = >20 – 40mm                      M       Moderate
                             Ys = >40 – 60mm                      H1      High-1
                             Ys = 60 – 75mm                       H2      High-2
                             Ys = > 75mm                          E       Extreme
                             Problem sites                        P       Problem




     SCG Consulting Engineers                               1                                     SCG Ref: 28045(S)

Used in these records

About this file

File size
1.9 MB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

SCG 28045(S).pdf · 1.9 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.