NOOSA COUNCIL
APPROVED PLANS
OPW13/1028 28 JAN 2014
[OCR of page images]
DRAWING SIZE — A2
FILLING NOTES:
—THE SHE IS 10 BE SCRAPED CLEAR OF ALL ORGANIC MATERIAL AND
DEBRIS.
~ THE SUBGRADE IS TO BE ROLLED WITH A VIBRATING STEEL DRUM
ROLLER TO ACHIEVE A MINIMUM RELATIVE FIELD DENSITY OF 95% THE
COMPACTION IS TO BE SUFFICIENT TO ACHIEVE A BLOW COUNT OF 7
BLOWS PER 300mm WITH AN APPROVED PERTH SANO PENETROMETER
FOR A DEPTH OF 1.0m BELOW EXCAVATED LEVEL COPIES OF
COMPACTION TEST RESULTS SHALL BE PRESENTED TO SCG CONSULTING
ENGINEERS FOR APPROVAL.
— THE FILL MATERIAL CLEAN GRANULAR MATERIAL (LE. SAND TO A
CLAYEY SAND IN ACCORDANCE WITH ASI726) BE FREE OF ANY
ORGANIC MATERIAL AND HAVE A CLAY CONTENT OF LESS THAN 12%
(PLASTICITY INDEX LESS THAN 25% UNEAR SHRINKAGE OF 15%). THE
PROPOSED MATERIAL IS 70 BE INSPECTED BY SCG CONSULTING
ENGINEERS PRIOR TO ITS REMOVAL TO ENSURE ITS COMPATABILITY.
~ THE FILL IS TO BE PLACED AND COMPACTED IN ACCORDANCE WITH
AS3798-1996 TO A LEVEL SUFFICIENT TO ACHIEVE A LEVEL 1
CERTIFICATION WITH A MINIMUM RELATIVE FIELD DENSITY OF 95%,
COPIES OF COMPACTION TEST RESULTS SHALL BE PRESENTED TO SCG
CONSULTING ENGINEERS FOR APPROVAL.
= FILUNG AND CONPACTING ADJACENT EXISITING STRUCTURES IS TO BE
IN STRICT ACCORDANCE WITH THE ASSOCIATED DETAILS AND
SPECIFCATIONS,
— AREAS WHERE EXISTING STRUCTURES OR TREES ARE REMOVED SHALL
BE BACKFILLED WITH THE APPROVED FILL MATERIAL COMPACTED IN
ACCORDANCE WITH AS2870~1996 TO ACHIEVE A MINIMUM RELATIVE.
FIELD DENSITY OF 95%.
— ANY LOOSE OR SOFT MATERIAL UNCOVERED IN THE SITE
PREPARATION SHALL BE REMOVED AND REPLACED WITH THE APPROVED
FILL MATERIAL COMPACTED IN ACCORDANCE WITH AS2870~1996 TOD
ACHIEVE A MINIMUM RELATIVE FIELD DENSITY OF 95%.
= SITE DRAINAGE AND SILT PROTECTION MEASURES NUST BE ISTALLED
PRIOR TO CONSTRUCTION COMMENCING,
GENERAL:
1, DO NOT SCALE FROM THIS DRAWNG.
2 ALL DIMENSIONS IN MILLINETRES
3. SETTING OUT DIMENSIONS ARE TO BE OBTAINED FROM THE ARCHITECTURAL
ORAWINGS,
4, ANY DISCREPANCIES BETWEEN THESE DRAWING AHD THE ARCHITECTURAL
DRAWINGS ARE TO BE REFERRED TO THE ENGINEER IMMEDIATELY,
5, THE BUILDER IS RESPONSIBLE FOR LOCATING ALL EXISTING SERVICES
WATHIN AND ADJACENT THE ALLOTMENT ANO SHALL ENSURE THAT ALL NEW
we ARE IN ACCORDANCE WITH THE ATTACHED CRITICAL DEPTH LINE
IAGRAM.
6. THE BUILDER MUST PROTECT ALL EXISTING NEIGHBOURING
STRUCTURES/BULDINGS THROUGHOUT THE WORKS, PARTICULARLY DURING
EARTHWORKS, REFERENCE SHOULD BE MADE TO OUR CRITICAL DEPTH UNE
DIAGRAM OR SEEK GUIDANCE DIRECTLY FROM THIS OFFICE
FOOTPATHS AND DRIVEWAYS:
CONTRACTOR TO LOCATE ALL SERVICES PRIOR TO
COMMENCING WORKS ON SITE. ALL SERVICES ARE
TO BE PROTECTED IN ACCORDANCE WITH THE
AUTHORITY RESPONSIBLE FOR THE SERVICE
WHERE NO RETAINING THE GARDEN
WALL IS TO BE GROUT FILLED WITH
Nt2-1200 CIRS VERT & HORIZ.
250
NATURAL GROUND [:
WATERPROOF WALL, ——om]
OMIT WHERE J
NO_RETAININGT
Ni20-400,
HORIZONTALLY
VERTICAL
R MAX. RETAINED
al
(WAX)
1200
(wis)
600
1000
300
BASE WOTH B
FOOTING DEPTH
ALL 'HIDEPTH 0"
1200 || 450
1600 || 750
2000 || 750
FOOTING BEAM
SLITTM TOP & BOTTOM
R6 UGS 900 CIRS
aN,
ROS,
‘.
SS,
N
SR ne ey,
i
A,
FILLED a
ALLOTMENT 2°
RV a
S,
\.
yea oa = ae
(—-----ane-- eee.
"_AIEIGHBOURING \
‘
f ~ ,
“ALLOTMENT A
MP \
\
IRVTTRN
LAID ON SIDE IN
PLACE OF BOTTOM
WALL EXTEND 100
200(H) TRENCH GRATE T
Revision
Description
Date
UTIMBER RETAINING
Uo” WALL AS SPECIFIED
\
‘
‘
‘
1
‘
\
\
‘
‘
‘
1
‘
‘
‘
BOUNDARY
eegrsesesd UA
‘
‘
\
‘
‘
‘
‘
1
‘
‘
‘
\
‘
‘
1
‘
\
‘
\
‘
‘
\
‘
\
\
\
100% DRAIN iA
FROM TRENCH fy
GRATE CONNECT 4 ii
TO 1508 UPVC
—
~~
GRATE
IRYTTNS
1508 UPVC |
1 IN 200
GRADE
TIMBER RETAINING WALL
BOTTOM WALER
___REPLACED WITH TRENCH
SWP’s TO BE LOCATED
ADJACENT TO LOW POINT IN
NEIGHBORING ALLOTMENT TO
CAPTURE PONDING CAUSED BY
RETAINING WALL CONSTRUCTION
REFER DETAIL.
LAID ON SIDE
PAST POSTS
SWP ~ TYPICAL DETAIL
R6 UGATURES @
SOOMM CENTRES.
1. EXSTING FOOTPATHS 70 BE SAW CUT PRIOR TO REMOVAL
2 CROSSINGS ARE NOT DESIGNED FOR COMMERCIAL VEHICLES:
3. CONCRETE DRIVEWAY TO BE 125mm THK, EXCLUDING ANY FINISHED
TREATMENTS, EG, STAMPING
4, CONCRETE SURFACE TOLERANCE +5.0mm OVER 3.0m,
5. CONCRETE N25 IN ACCORDANCE WITH AS 1379 AND AS 3600
6, REINFORCEMENT FABRIC TO AS 1304, PLACED CENTRAL SLAB DEPTH.
7, EXPANSION JORTS TO BE 10mm MDE WET TOOLED WITH EVERY 2ND MESH
WRE CUT ALONG JOINT.
8. ONE ACCESS POINT PERMITTED FOR EACH ALLOTMENT.
9, FOR CURVED DRIVEWAYS, KAXIMUM GRADES APPLY TO INSIDE EDGE OF
CURVE
10, AUL SERVICES TO BE LOCATED AND PROTECTED AS REQUIRED PRIOR 10
WORK COMMENCING
PAVEMENT NOTES:
1, PRIOR TO PLACEMENT OF PAVEMENT MATERIAL THE SUBGRADE IS 70 BE
STRIPPED TO LEVEL. ANY ORGANIC MATTER OR DEBRIS IS TO BE REMOVED
AND REPLACED WTH APPROVED COMPACTED MATERIAL, THE SUBGRADE
SHALL BE PROOF ROLLED TO A MINIMUM OF 98% DRY DENSITY AS
DETERMINED BY COMPACTION TESTING IN ACCORDANCE WITH AS1289
PAVEMENT MATERIALS SHALL COMPLY WITH THE FOLLOWING MAIN ROADS
DEPARTMENT SPECIFICATION MRSIE.05:
— BASE COURSE TO CONSIST OF AGGREGATE TYPE 2.3, GRADING B OR C
PAVEMENT MATERIAL SHALL BE EXTENDED A MINIMUM OF 150MM BEYOND
THE EDGE OF DRIVE AND SHALL BE A MINIMUM OF 100MM THICK ULN.O,
4, BASE ANO SUB-BASE COURSES ARE TO BE COMPACTED IN LAYERS NOT
EXCEEDING 1SOmvn IN THICKNESS 10 ACHEVE 95% DRY DENSITY OR GREATER
WMH ONE TEST PER 200mm THICKNESS OF EACH LAYER,
SECTION X—X
TYPICAL SECTION ~ GWE
PROVIDE FULL HL_MOVENENT JOINTS AT 8.0M CTRS
FINISHED SITE DRAINAGE IN
ACCORDANCE WITH HYDRAULICS
CONSULTANTS DOCUMENTATION.
‘SLB2 MESH
MIDDLE
NOMINAL
KERB UNE
‘WET TOOLED
CONTROL JOINT.
DRIVEHAY/TERRACE SLAB
AS PER PLAN
ee
(CONTROL SCZ Le
LLL Lhe
LOWER SLAB MESH TO
MAINTAIN 40mm TOP COVER
SAW CUT AND
5. ALL CONPACTION TESTING RESULTS TO BE PRESENTED TO THE ENGINEER BREAKOUT
FOR APPROVAL PRIOR TO PROCEEDING TO THE NEXT STAGE OF BACK OF KERB
CONSTRUCTION,
BARRIER, SEMI-MOUNTABLE, MONTABLE
KERB & CHANNEL OR INVERT CROSSING
CUT EVERY SECOND WIRE
SOmm CLEAR ALONG LINE
OF JOIN
T.d_ TOOLED JOINT
TYPICAL SECTION
NOOSA COUNCIL
APPROVED PLANS
OPW13/1028 28 JAN 2014
'ssue: APPROVAL,
REE CONSULTING | ENGINEERS
structural - civil - geolechnical
ABN 40 098 481 899
U1/11 PROJECT AVENUE, NOOSAVILLE QLD.4566
Ph (07) 5455 5604 Fax (07) 5455 5696
Ri R_DETAI
(SCALE 1:20)
Title:
OPERATIONAL WORKS DETAILS
Project 43 Elizabeth Street,
Noosaville
Date: Nov 2013,
Drg No, 23299-OW3} #&