               WASTEWATER DESIGN STATEMENT
                       ON-SITE EFFLUENT DISPOSAL AREAS FOR UNSEWERED BLOCKS




     Job No:                                    EWD 4896

     Client:                                    Browyn Smidt & Kenneth Clucas

     Address:                                   8 Hinterland Close Tinbeerwah                QLD        Post Code 4563

     RP/SP Description:                         Lot 8 on RP162815

     Plumbing Application Number:




    I certify that I am the responsible person for the design of the On-site Sewerage Facility including the
    Effluent Disposal Area submitted with the above application. It is in accordance with AS 1547 – 2012, The
    Queensland Plumbing and Wastewater Code and Council Policy. I will inspect installation works and supply
    Certificate of Compliance on completion of works.



                           Designer            Andrew Smith
                           Name:


                           Signature:


                           Date:               24/01/2024




                             Commercial in Confidence. The contents of this document must not be copied, used,
Enviro Water Design©                                                                                                           Page 1 of 5
                               distributed, disclosed or published without the consent of Enviro Water Design©
Log in to download the original file

Appendix D - Effluent Disposal System.pdf · 1.7 MB (small file)

Full text of the other 10 pages

Page 2

                                                                                                    QBCC: 15336345 ABN: 35 622 809 376




    1. INTRODUCTION & BRIEF
         The Owners are proposing a three (3) bedroom dwelling to be serviced by an Aerated On-site
         Sewerage Facility supplying advanced secondary treated effluent to above ground irrigation.


    2. SITE INVESTIGATION
         Ground Drill
                Soil Category            5                        Percolation                   0.06 - 0.12 mm/day
                Structured               Moderately               DIR                           3
                Soil Type:               Light Clays              Site Classification          “M-P”




    3. EFFLUENT DISPOSAL AREA
         The effluent disposal area is to be fixed heavy droplet wobbler sprinklers onto existing vegative area.
         Place a clay bund mounding around the upper sides of the disposal area to divert stormwater around
         the area. Install 9 turf heavy droplet wobblers with a maximum throw of 3m radius.


    4. TOTAL DISPERSAL AREA FOR IRRIGATION
                 Bedrooms 3                                      People                        5 persons
                 Water Supply                 Rain               Daily flow per person 120 Litres per day
                 Total Daily Flow Loading                     = 600 Litres per day



          Therefore Total Disposal Area                      System Design Flow = 600L = 200
                                                                    DIR            3

          In this case adopt 254 square meters of irrigation area due to the size of the wobblers.




                             Commercial in Confidence. The contents of this document must not be copied, used,
Enviro Water Design©                                                                                                         Page 2 of 5
                               distributed, disclosed or published without the consent of Enviro Water Design©

Page 3

                                                                                                   QBCC: 15336345 ABN: 35 622 809 376




    5. SURFACE HORIZONTAL SEPARATION DISTANCE REQUIREMENTS
     Feature                                                        Primary         Secondary          Advanced Secondary

     Permanent watercourses (lake/stream/river)                        50m               30m                    10m

     Intermittent watercourses (dams/channels/weirs)                   50m               30m                    10m

     Bore (human and or domestic consumption)                          50m               30m                    10m

     EMT boundary unlined open storm water                             50m               30m                    10m
     drainage

     Property boundaries/paths/walkways                                      2m down slope 4m upslope boundary

     Dwellings/play areas                                               10m         10m spray/2m down slope 4m up slope
                                                                                               sub/covered

     Swimming pool (water edge)                                         6m                6m                    6m

     In ground water tank                                              15m                6m                    6m



    6. VERTICAL SEPARATION DISTANCE REQUIREMENTS
     Depth of unsaturated soil to                                  Primary          Secondary          Advanced Secondary

     Permanent water table                                             1.2m             0.6m                    0.3m

     Bedrock                                                           1.2m             0.6m                    0.3m



    EFFLUENT QUALITY
    Effluent quality requirements must be confirmed with the relevant local council before proceeding and
    when tested shall comply with the following:

     Effluent Quality                                              Primary          Secondary          Advanced Secondary

     Biochemical Oxygen Demand (mg / litre)                          120-240             <20                    <10

     Total Suspended Solids (mg / litre)                              65-180             <30                    <10

     Thermotolerant Coliforms (organisms / 100mL)                                       <200                    <10




                            Commercial in Confidence. The contents of this document must not be copied, used,
Enviro Water Design©                                                                                                        Page 3 of 5
                              distributed, disclosed or published without the consent of Enviro Water Design©

Page 4

                                                                                                   QBCC: 15336345 ABN: 35 622 809 376




    7. DESIGN RECOMMENDATIONS
    Water conservation implementation will reduce the hydraulic load on the Land Application Facility and
    subsequently improve its performance and serviceable life.
    Effluent quality from the treatment plant must comply with the criteria presented in the Plumbing and
    Drainage Act, Queensland Plumbing and Wastewater Code and AS/NZS 1547-2012 On-Site Domestic
    wastewater Management and be confirmed with the regulatory authority.


    8. INSTALLATION NOTES
    All installation works, components and fittings must comply with AS/NZS 3500, AS/NZS 1547-2012 On-Site
    Domestic Wastewater Management, Plumbing and Drainage Act, Queensland Plumbing and Wastewater
    code, the EPA, Health Act, The Integrated Planning Act and Local Authority.
    Land Application Facilities and treatment systems/service plants (wastewater treatment unit and disposal
    areas) must be located with good and clear access for servicing and maintenance requirements.
    The exiting ground proposed for use as the Land Application Area shall be lightly scarified along the contour
    to a maximum depth of 200mm prior to the construction and/or installation of the land Application Area.
    Care should be taken with the layout and construction of supply line trenching/pipe work, as with all
    drainage, plumbing and electrical trenches to inhibit surface water infiltration along and into the Land
    Application Area. All supply line excavations and trenching shall be backfilled with interceptors.
    Correct pipe layout and Land Application Area construction/installation is an essential part of our
    recommendations and design. If the site is not prepared in accordance with our design, or is prepared
    inadequately or is prepared poorly, inefficiencies may occur and we do not take responsibility for the
    consequences in such cases and we will make an additional charge if as a result, more testing, re-designing
    or re-writing of the report is necessary.
    All irrigation areas are to have bunded walls for retention to the perimeter of the designated area.



    THE LAND APPLICATION AREA SHALL:
            not be located on land prone to water logging or subject to floodwater inundation
            be sited to be open to prevailing winds and not totally shaded from sunlight
            be protected from roof water discharge, surface water flow and/or seepage
            have no runoff or seepage of the applied effluent beyond the designated area
            be regularly inspected and maintained
            have the mandatory signage prominently displayed
            have boundaries clearly delineated.

    It is essential that all associated storm water flows from this and neighboring allotments, driveways, roads,
    tanks and roofs be diverted away and well clear of the proposed Land Application Area.
    Enviro Water Design requires an inspection for certification to be carried out prior to commissioning, and
    preferable during construction, to ensure code compliance and that ‘Best practice’ principles have been
    utilized.




                            Commercial in Confidence. The contents of this document must not be copied, used,
Enviro Water Design©                                                                                                        Page 4 of 5
                              distributed, disclosed or published without the consent of Enviro Water Design©

Page 5

                                                                                                  QBCC: 15336345 ABN: 35 622 809 376




    PLANTING REGIME
    No plantings to be within 3m of the trench / beds. However, further qualified advice from local
    nurserymen and the local regulatory authority should be preferred when choosing plants so as not to have
    any root invasion of the system.
    A good grass cover over the trench / bed System is required to improve the efficiency of the system with
    the uptake of nutrient and natural transpiration processes. Grasses should be kept well mown and raked
    for better evaporative and transpiration processes (avoid throwing grass clippings onto the Land
    Application Area). Shrubs should be kept well pruned for better evaporative and transpiration processes.
    Do not plant shrubs or trees within the surface water diversion drains, as these drains need to be kept free
    of obstruction and trash for maximum diversion efficiency.
    Depending on the dose loading of the system future planting may need to be placed to the low side of the
    land application facility.


    SEPARATION DISTANCE REQUIREMENTS
    One of the most important parameters to consider in the location of Land Application Areas is the
    separation distances, both vertical and horizontal (Queensland Plumbing and Wastewater Code). Poorly or
    inappropriately selected ground may contribute to the pollution of surface water and groundwater,
    ponding and eutrophication.




                           Commercial in Confidence. The contents of this document must not be copied, used,
Enviro Water Design©                                                                                                       Page 5 of 5
                             distributed, disclosed or published without the consent of Enviro Water Design©

Page 6

                                                                                                                                                                                  WASTE WATER
                                                                                                                                                                                   SITE PLAN




                                                                                                                                                                 HIN




                                                                                                                                                                                                                  N
                                                                                                                                                                  TE
                                                                                                      BATH
                                                                                                                    BED 3       BATH

                                                                                                                                                BED 2
                                                                                    LIVING
                                                                 ALFRESCO




                                                                                                                                                                   LAR
                                                                            ENS




                                                                                                                                                                      N
                                                                                                                    KITCHEN
                                                                                                                                          PTY
                                                                                                                                                LDY
                                                                                             LIVING
                                                                                                                                        PWD
                                                              BED 1




                                                                                                                                                                       DC
                                                                                                                                                        GARAGE

                                                                                                                                       OFFICE


                                                                                             ALFRESCO


                                                        SPA




                                                                             BBQ AREA

                                                                                                             POOL




                                                                                                                                                                         LO
                                                                                                                                                                          SE
                                ST
                                  OR
                                    MW
                                      AT
                                        ER                                                                   26
                                                                                                                    50
                                                                                                                            0

                                             EA
                                                  SE
                                                       ME
                                                            NT
                                                                                                                                                         KOALA
                                                                                                                                                        HABITAT                                                                               www.envirowaterdesign.com.au
                                                                                                                                                                                                                                                    M: 0427 287 600
                                                                                                                                                                                                                        E: [email protected] - A: PO Box 639, Hervey Bay Qld 4655
                                                                                                                                                                                                                                      QBCC 15336345 ABN 35 622 809 376
                                                                                                                                                                                                                      PROJECT:

                                                                                                                                                                                                                            PROPOSED RESIDENCE
                                                                                                                                                                                                                      CLIENT:

                                                                                                                                                                                                                           BROWYN SMIDT & KENNETH CLUCAS
CLIENT:-    __________
                                                                                                                                                                                                                      REAL PROPERTY DESCRIPTION:
                                                                                                                                                                                ALL CONSTRUCTION WORK TO BE                 LOT 8 ON RP162815
CLIENT:-    __________
                                                                                                                                                                                 CARRIED OUT BY A QUALIFIED,                8 HINTERLAND CLOSE
DATE:-      __________                                                                                                                                                               LICENSED INSTALLER                     TINBEERWAH
                                                                                                                                                                                                                      DRAWN:                        DESIGNED:                   QBCC


BUILDER:- _ _ _ _ _ _ _ _ _ _                                                                                                                                                     CONTRACTOR TO VERIFY ALL               M.ALLWOOD                              A.SMITH                    15336345
                                                                                                                                                                              MEASUREMENTS ON-SITE PRIOR TO THE       SCALE:                       DATE:                        JOB NO.


DATE:-      __________                                                                                                                                                                                                           1:500                     24/01/2024                      EWD4896
                                                                                                                                                                              COMMENCEMENT OF ANY SUCH WORKS.
                                                                                                                                                                                                                        THESE DESIGNS ARE COPYRIGHT AND ARE NOT TO BE USED   SHEET SIZE:     SHEET:
                                                                                                                                                                                                                       OR REPRODUCED WHOLLY OR IN PART WITHOUT THE WRITTEN
                                                                                                                                                                                                                                 CONSENT OF 'ENVIRO WATER DESIGN'                 A3           1 OF 6

Page 7

                                                                                                                                 HIN
                                                                                                                                                                                                           254 SQM OF




                                                                                                                                             TE
                                                            BATH



                                                                                                                                                                                                      IRRIGATION DISPOSAL
                                                                          BED 3     BATH

                                                                                                    BED 2
                                          LIVING
                       ALFRESCO




                                                                                                                                                                                                         AREA OBTAINED




                                                                                                                                                       RL
                                                                                                                                                                                                       DESIGNED UTILIZING STANDARD
                                                                                                                                                                                                        WATER REDUCTION FIXTURES




                                                                                                                                                          A
                                  ENS
                                                                                                                                                                                                          ON RAIN WATER SUPPLY
                                                                                                                                                                                                           FOR CAT 5 LIGHT CLAY




                                                                                                                                                               ND
                                                                          KITCHEN
                                                                                              PTY
                                                                                                    LDY
                                                   LIVING
                                                                                            PWD
                    BED 1


                                                                                                                   GARAGE

                                                                                           OFFICE                                             AN APPROVED AWTS TO BE
                                                                                                                                              INSTALLED AND MAINTAIN
                                                   ALFRESCO
                                                                                                                                              AN ADVANCED SECONDARY
              SPA                                                                                                                             QUALITY EFFLUENT




                                                                                                                                                                  C




                                                                                                                                                                                                                                    N
                                   BBQ AREA

                                                                   POOL




                                                                                                                                                                              LO
                                                                                                                                     32mmOD LILAC CODED PN12.5 POLY
                                                                                                                                     PUMP LINE FROM THE AWTS TO THE
                                                                                                            1000



                                                                                                                                     LAND APPLICATION AREA
                                                                                                             0




                                                                                                                                                          BUND WALL / WATER
                                                                                                                                                          DIVERSION DRAIN.




                                                                                                                                                                                   SE
                                         INDEXING VALVE TO BE INSTALLED TO ENABLE
                                                     EQUAL EFFLUENT DISTRIBUTION.
                                                                                                                                                                         00                                                NOTE :
                                                                                                                                                                      20
                                                                                                                                                                              9 HEAVY DROPLET FIXED WOBBLERS WITH
     NOTE :                                                                                                                                                                   A MAXIMUM PLUME HEIGHT OF 500mm AND          NO VEGITATION TO BE REMOVED IN
                                                                                                                                                                              A MAXIMUM DIAMETER OF 6m
                                                                                                                                                                              TO BE INSTALLED IN AN EXISTING
                                                                                                                                                                                                                           THE KOALA HABITAT AREA FOR THE
     ENSURE WHILST CONSTRUCTING THAT                                                                                                                                          VEGATIVE AREA                                PURPOUS OF LAA INSTALLATION
     SUFFICIENT BUND WALLS AND GROUND WATER
     DIVERSION DRAINS ARE INSTALLED. DISPOSAL
     AREA MUST HAVE GRASS PLANTED TO OBTAIN
     FINAL CERTIFICATION
                                                                                                                                600




                                                                                                                                                                         0
                                                                                                                                     0




                                                                                                                                                                       600
     DESIGN NOTES                                                                                                                               600
                                                                                                                                                   0                                       CLIENT:-    __________
     THIS ON-SITE SEWERAGE FACILITY IS DESIGNED IN                                                                                                                                         CLIENT:-    __________
     ACCORDANCE WITH THE AS1547-2012 ON-SITE                                                                                                                     0
                                                                                                                                                                600
     DOMESTIC WATER MANAGEMENT AND THE QLD                                                                                                                                                 DATE:-      __________
                                                                                                                                                                                                                                                            www.envirowaterdesign.com.au
     PLUMBING & WASTE WATER CODE VERSION1:2019                                                                                                                                             BUILDER:- _ _ _ _ _ _ _ _ _ _
                                                                                                                                                                                                                                                                  M: 0427 287 600
                                                                                                                                                                                                                                      E: [email protected] - A: PO Box 639, Hervey Bay Qld 4655
                                                                                                                                                                                                                                                    QBCC 15336345 ABN 35 622 809 376
                                                                                                                   RETENTION MOUND
     AN APPROVED WASTE WATER TREATMENT SYSTEM                                                                                                                                              DATE:-      __________

AS
                                                                                                                                                                                                                                    PROJECT:

                                                                                                                                                                                                                                          PROPOSED RESIDENCE
     MAINTAINING A MINIMUM ADVANCED SECONDARY                                                                                                                                                                                       CLIENT:




     EM
     QUALITY EFFLUENT TO BE INSTALLED                                                                                                                                                                                                    BROWYN SMIDT & KENNETH CLUCAS




                                                                                                               WASTE WATER
                                                                                                                                                                                                                                    REAL PROPERTY DESCRIPTION:
                                                                                                                                                                                       ALL CONSTRUCTION WORK TO BE

          EN
                                                                                                                                                                                                                                          LOT 8 ON RP162815
     ALL WORKS TO BE INSPECTED BEFORE COVERING                                                                                                                                          CARRIED OUT BY A QUALIFIED,                       8 HINTERLAND CLOSE
     OR BACKFILLING                                                                                                                                                                         LICENSED INSTALLER                            TINBEERWAH


                     T
                                                                                                                 DESIGN
                                                                                                                                                                                                                                    DRAWN:                        DESIGNED:                   QBCC


                                                                                                                                                                                        CONTRACTOR TO VERIFY ALL                       M.ALLWOOD                              A.SMITH                    15336345
     DESIGNER TO BE NOTIFIED UPON COMPLETION OF                                                                                                                                     MEASUREMENTS ON-SITE PRIOR TO THE               SCALE:                       DATE:                        JOB NO.


     IRRIGATION DISPERSAL AREA FOR AN INSPECTION                                                                                                                                    COMMENCEMENT OF ANY SUCH WORKS.
                                                                                                                                                                                                                                               1:250                     24/01/2024                      EWD4896

     TO CERTIFY                                                                                                                                                                                                                       THESE DESIGNS ARE COPYRIGHT AND ARE NOT TO BE USED
                                                                                                                                                                                                                                     OR REPRODUCED WHOLLY OR IN PART WITHOUT THE WRITTEN
                                                                                                                                                                                                                                                                                           SHEET SIZE:     SHEET:


                                                                                                                                                                                                                                               CONSENT OF 'ENVIRO WATER DESIGN'                 A3           2 OF 6

Page 8

                                                                                                                                                                                                    INT
                                                                      VP

                                                               BATH
                                                                                  BED 3           BATH

                                                                                                                               BED 2
                                           LIVING                     IO
                   ALFRESCO




                                                                                                                                                                                                       ER
                                                                                                 IO



                                                                                                                                IO   EJ
                                                                                                                                      S & EJ
                                                                                                                                      EJ
                                                                                          PROVIDE MIN. 300mm OF COVER           IO
                                                                                                                                     IO
                                                                                                 OVER DRAINAGE LINES

                  **SITE SOIL PROFILE
                 CLASSIFICATION -'M - P'**




                                                                                                                                                                                                                                                              LA
                NOTE:

                SWIVAL AND EXPANSION JOINTS WILL
                BE REQUIRED AS PER THE AS2870-2011.
                                                                                                                                          DN100mm UPVC SEWER LINE LAID
                REFER TO THE ATTACHED SCHEMATIC
                                                                                                                                              AT A MINIMUM 1.65% GRADE




                                                                                                                                                                                                                                                           N
                FOR INSTALLATION DETAILS.


                                     ENS
                                                                                                                                                                         IO S & EJ
                                                                                  KITCHEN                                                                                EJ ORG      EJ
                                                                                                                PTY
                                                                                                                               LDY
                                                      LIVING
                                                                                                              PWD                                                                                              CLIENT:-                  __________
                                                                                                                     IO
                BED 1           IO                                                                                                                                       IO S & EJ
                                                                                                                                                                                     IO
                                             VP
                                                                                                                          IO                                             EJ
                                                                                                                                                                               EJ
                                                                                                                                                                                                               CLIENT:-                  __________

                                                                                                                                                             GARAGE                                            DATE:-                    __________
                                                                                                            OFFICE
                                                                                                                                                                                                               BUILDER:- _ _ _ _ _ _ _ _ _ _

                                                      ALFRESCO                                                                                                                                                 DATE:-                    __________
                                                                                                                                                                                           S & EJ
          SPA                                                                                                                                                                             IO
                                                                                                                                                                              250
                                                                                                                                                                                 0

SEWER DRAINAGE DESIGN
                                  BBQ AREA
DRAINAGE LENGTH OUTSIDE OF DWELLING
                 = 22.816M
[email protected]%    = 377MM OF FALL                                           POOL                                                                                                                                             www.envirowaterdesign.com.au
                                                                                                                                                                                                                                  M: 0427 287 600
MINIMUM COVER                                                                                                                                                                                         E: [email protected] - A: PO Box 639, Hervey Bay Qld 4655

AT HEAD OF LINE  = 300MM                                                                                                                                                                                            QBCC 15336345 ABN 35 622 809 376

DN 100MM OD PIPE = 110MM
                                                                                                                                                                                                    PROJECT:

                                                                                                                                                                                                          PROPOSED RESIDENCE

NOTE:
                                                                                                                                                                                                    CLIENT:

                                                                                                                                                                                                         BROWYN SMIDT & KENNETH CLUCAS

BOTTOM OF INLET TO THE WASTE WATER SYSTEM
                                                       SEWER DESIGN
                                                                                                                                                                                                    REAL PROPERTY DESCRIPTION:
                                                                                                                                                         ALL CONSTRUCTION WORK TO BE                      LOT 8 ON RP162815
TANK TO BE A MINIMUM 787MM BELOW FINISHED                                                                                                                 CARRIED OUT BY A QUALIFIED,                     8 HINTERLAND CLOSE
GROUND LEVEL OUTSIDE OF DWELLING. SEWER
                                                                                                                                                              LICENSED INSTALLER                          TINBEERWAH
DRAINAGE TO BE LAID AT A MINIMUM 1.65% GRADE


                                                         CONCEPT
ALLOWING 300MM OF COVER AT THE HIGHEST
                                                                                                                                                                                                    DRAWN:                        DESIGNED:                   QBCC



POINT. ( A LASER LEVEL IS HIGHLY RECOMMENDED)                                                                                                            CONTRACTOR TO VERIFY ALL                      M.ALLWOOD                              A.SMITH                    15336345

SEWER DRAINAGE IS A CONCEPT ONLY AND WILL BE                                                                                                         MEASUREMENTS ON-SITE PRIOR TO THE              SCALE:                       DATE:                        JOB NO.

                                                                                                                                                                                                               1:125                     24/01/2024                      EWD4896
AS CONSTRUCTED ON-SITE AS PER LOCAL                                                                                                                  COMMENCEMENT OF ANY SUCH WORKS.
AUTHORITY REQUIREMENTS.                                                                                                                                                                               THESE DESIGNS ARE COPYRIGHT AND ARE NOT TO BE USED   SHEET SIZE:     SHEET:
                                                                                                                                                                                                     OR REPRODUCED WHOLLY OR IN PART WITHOUT THE WRITTEN
                                                                                                                                                                                                               CONSENT OF 'ENVIRO WATER DESIGN'                 A3           3 OF 6

Page 9

DIAGRAMMATIC SECTIONAL VIEW
                                                                             Fixed heavy droplet
                                                                             wobbler sprinkler




    FIXED WOBBLER                             Lilac coded 25 O.D.
                                              Rural B irrigation line


       IRRIGATION
         SYSTEM                                                CLIENT:-    __________

                                                               CLIENT:-    __________

                                                               DATE:-      __________

                                                               BUILDER:- _ _ _ _ _ _ _ _ _ _
NOTE:                                                          DATE:-      __________                                      www.envirowaterdesign.com.au
                                                                                                                                 M: 0427 287 600
                                                                                                     E: [email protected] - A: PO Box 639, Hervey Bay Qld 4655
                                                                                                                   QBCC 15336345 ABN 35 622 809 376


ALL WORK TO BE IN ACCORDANCE WITH THE                                                              PROJECT:

                                                                                                         PROPOSED RESIDENCE
                                                             ALL CONSTRUCTION WORK TO BE
AS1547-2012.
                                                                                                   CLIENT:


                                                              CARRIED OUT BY A QUALIFIED,               BROWYN SMIDT & KENNETH CLUCAS

CONSTRUCT A DIVERSION MOUND OR DRAIN ON THE                       LICENSED INSTALLER               REAL PROPERTY DESCRIPTION:


                                                                                                         LOT 8 ON RP162815

UPPER SIDES OF THE LAND APPLICATION AREA TO                   CONTRACTOR TO VERIFY ALL
                                                                                                         8 HINTERLAND CLOSE
                                                                                                         TINBEERWAH
                                                          MEASUREMENTS ON-SITE PRIOR TO THE
DIVERT GROUND WATERS FROM WASHING THROUGH
                                                                                                   DRAWN:                        DESIGNED:                   QBCC

                                                          COMMENCEMENT OF ANY SUCH WORKS.             M.ALLWOOD                              A.SMITH                    15336345

THE AREA.
                                                                                                   SCALE:                       DATE:                        JOB NO.

                                                                                                               NTS                      24/01/2024                      EWD4896
                                                                                                     THESE DESIGNS ARE COPYRIGHT AND ARE NOT TO BE USED   SHEET SIZE:     SHEET:
                                                                                                    OR REPRODUCED WHOLLY OR IN PART WITHOUT THE WRITTEN
                                                                                                              CONSENT OF 'ENVIRO WATER DESIGN'                 A3           4 OF 6

Page 10

                                                                                                                                                                                                                                                                                                                                                                                     DOWNPIPE



                                                                                                                                                    TYPICAL DRAINAGE                                                                                                                                                                                                                 PROVIDE VISUAL TERMITE BARRIER
                                                                                                                                                                                                                                                                                                                                                                                     TO AS 3660.1

                                                                                                                                                  UNDER FOOTING 'E-D SITES'
                                                                                                                                                                                                                                                                     SLAB TO ENGINEERS                                        SLAB TO ENGINEERS
                                                                                                                                                                                                                                                                      SPECIFICATION                                              SPECIFICATION
                                                                                                                                                                                                                                                                                                                                                                                     EXPANSION JOINT


                                                                 FIN                                                                                                                                                                                                                                                                                                                 GROUND LEVEL
                                                                       ISH
                                                                          ED
                                                                               FLO
                                                                                   OR                                                                                                                                                                                                                                                                                                ALLOWANCE FOR PIPEWORK
                                                                                          LEV                                                                                                                                                                                                                                                                                        TO MOVE INDEPENDENT TO
                                                    INSPECTION                               EL                                                                                                                                                                             VERTICAL EXPANSION JOINT IF REQUIRED
                                                                                                                                                                                                                                                                                                                                                                                     FOOTINGS & STRUCTURE
                                                    OPENING                                                                                                                                                                                                             -   MAY BE REPLACED WITH SWIVEL/EXPANSION COMBINATION IF
                    GR                                                                                                                                                                                                                                                      DISTANCE BETWEEN BOTTOM OF SLAB & TOP OF PIPE IS ≤ 500mm
                       O    UN                                                                                                                                                                                                                                          -   WHERE DRAINAGE PIPE IS PENETRATING THROUGH CONCRETE                                                 STORMWATER DRAINAG
                                                                                                                                                                                                                                                                                                                                                                                                       E PIPE
                                 DL                                                                                                                                                                                                                                         BEAMS, VERTICAL EXPANSION JOINTS ARE NOT REQUIRED
                                   EVE                                       INSPECTION                                                                                                                                                                                 -   JOINTS NOT REQUIRED ON VERTICAL DROPS LESS THAN 400mm
                                        L                                    OPENING
                                                                  EXPANSION                                                                                                               SWIVEL / KNUCKLE      15° BEND
                                                                  JOINT                                                                                                                               JOINT

                                            SWIVEL / KNUCKLE
                                            JOINT                                          EXPANSION
                                                                                                                                                                                    EXPANSION                                                        CLAY PLUG UNDER FOOTING
                                                                                           JOINT
                                                                 OVERFLOW RELIEF                                                                                                        JOINT
                                                                 GULLY                                                                                                                                                                                                                                                                                                    45°
                                                                                                                                                                                                                                                                                                                                             RESTRICTED ZONE OF INFLUENCE
                                                                                                                                                                                                                                                                                                                                             NO EXCAVATION IS TO INTRUDE ON HATCHED AREA
                                         EXPANSION
                                                                                                                                                                               MINIMUM
                                         JOINTS
                                                                                                                                                                           1.65% GRADE
                                                                                                                                                                                                                 45°
  MINIMUM       EXPANSION                                                                                                                                                                                            RESTRICTED ZONE OF INFLUENCE
                                                                                                                                                                                                                                                                                                                                           TYPICAL STORMWATER ELEVATION
  1.65% GRADE   JOINT                                                                                                                                                                                  NO EXCAVATION IS TO INTRUDE ON HATCHED AREA
                                      SWIVEL / KNUCKLE
                                      JOINT




                                                                                                                                          INSPECTION

TYPICAL ELEVATED PIPEWORK                                                                                          EXPANSION
                                                                                                                   JOINT
                                                                                                                                          OPENING

                                                                                                                                                                                                                                                                   EXPANSION
                                                                                                                                                                                                                                                                   JOINT


                                                                                                                               SWIVEL / KNUCKLE
                                                                                                                               JOINT
                                                                                                                                                                                                                                               SWIVEL / KNUCKLE
                                                                                                                                                                                                                                               JOINT




                                                         EXPANSION                                SWIVEL / KNUCKLE EXPANSION
   SWIVEL / KNUCKLE
                                                         JOINT                                            COMBOJOINT
   JOINT
                                                                                                                                                                                                                                                                                                                                                                                 CLIENT:-                  __________

 AS 2870—2011                                                                                                                                                                                                                                                                                                                                                                    CLIENT:-                  __________

 5.6.4 Plumbing requirements                                                                                                                                  TYPICAL SEPTIC TANK DETAIL                                                                                                                                                                                         DATE:-                    __________
 Buildings on highly or extremely reactive sites shall be provided with a system of plumbing
 detailed in accordance with the following:                                                                                                                                                                                                                                                       EXTENT OF SLAB                                                                 BUILDER:- _ _ _ _ _ _ _ _ _ _
 (a) Penetrations of the edge beams of a raft and perimeter strip footings shall be avoided                                                                                                                                                                                                                                                                                      DATE:-                    __________
 where practicable, but where necessary shall be detailed to allow for movement.                                                                                                                                                                                                                   STRUCTURAL FOOTING
 Closed-cell polyethylene lagging shall be used around all stormwater and sanitary                                                                                                       TYPICAL DRAINAGE
 plumbing drain pipe penetrations through footings. The lagging shall be a minimum
 of 20 mm thick on Class H1 sites and 40 mm thick on Class H2 and Class E sites.
                                                                                                                  SLAB TO ENGINEERS
                                                                                                                     SPECIFICATION                                                       THROUGH FOOTING
 Vertical penetrations do not require lagging.                                                                                                                                                                                                                                                       LAGGING AS SPECIFIED
 NOTE: Sleeves allowing equivalent movements may be used as an alternative to the lagging.
                                                                                                                                                                                                                                                                                                             EXPANSION

 (b) Drains attached to or emerging from underneath the building shall incorporate                                                                                                                                                                                                                           JOINT

 flexible joints immediately outside the footing and commencing within 1 m of the                                                                                                  15° BEND     SWIVEL / KNUCKLE
                                                                                                                                                                                                JOINT
 building perimeter to accommodate a total range of differential movement in any                                                                                                                                                                                                      15° BEND
                                                                                                                                                                                                                                                                                                                                           MINIMUM
 direction equal to the estimated characteristic surface movement of the site (ys). In the                                                         LAGGING AS SPECIFIED
                                                                                                                                                                                                                                                                                                 SWIVEL / KNUCKLE
                                                                                                                                                                                                                                                                                                 JOINT                                     1.65% GRADE

 absence of specific design guidance, the fittings or other devices that are provided to                                                                                                                      EXPANSION
                                                                                                                                                                                                              JOINT                                                                                                                                                                           www.envirowaterdesign.com.au
 allow for the movement shall be set at the mid-position of their range of possible                                                                                                                                                                                                                                                         EXPANSION                                               M: 0427 287 600
 movement at the time of installation, so as to allow for movement equal to 0.5ys in                                                                                                                                                                                                                                                        JOINT
                                                                                                                                                                                                                                                                                                                                                                        E: [email protected] - A: PO Box 639, Hervey Bay Qld 4655
 any direction from the initial setting. This requirement applies to all stormwater and                                                                                                                                                                                                                                                                                               QBCC 15336345 ABN 35 622 809 376
 sanitary plumbing drains and discharge pipes.                                                                                                                                                                       MINIMUM
                                                                                                                                                                                                                     1.65% GRADE                                                                                                                                      PROJECT:

                                                                                                                                                                                                                                                                                                                                                                            PROPOSED RESIDENCE
 (c) On-site wastewater treatment units and associated land application areas shall be                                                                                                   45°
 located to minimize soil moisture increase within the foundation.                                                                                                                                                                                                                                                                                                    CLIENT:
                                                                                                                                                         RESTRICTED ZONE OF INFLUENCE


 (d) Drainage under a slab shall be avoided where practicable.
                                                                                                                                                         NO EXCAVATION IS TO INTRUDE ON HATCHED AREA
                                                                                                                                                                                                                                                                               TYPICAL DRAINAGE PLAN                                                                       BROWYN SMIDT & KENNETH CLUCAS
 NOTES:
                                                                                                                                                                                                                                                                                     TOP VIEW
                                                                                                                                                                                                                                                                                                                                                                     REAL PROPERTY DESCRIPTION:

 1 Pipes may be encased in concrete or in recesses in the slab when provided with flexible                                                                                                                                                                                                                                                                                  LOT 8 ON RP162815
 joints at the exterior of the slab.
 2 Methods used should comply with the AS/NZS 3500 series.
                                                                                                                                                                                                                                                                                                                                                                            8 HINTERLAND CLOSE


                                                                                                                              SEWER DRAINAGE
                                                                                                                                                                                                                                                                                                                                                                            TINBEERWAH
 (e) Cold water pipes and heated or hot water pipes shall not be installed under a slab,                                                                                                                                                                                                                                                                              DRAWN:                        DESIGNED:                   QBCC
 unless the pipes are installed within a conduit so that if the pipe leaks water it will be                                                                                                                                                                                                                                                                              M.ALLWOOD                              A.SMITH                    15336345
 noticed above the slab or outside the slab and will not leak unnoticed under the slab.


                                                                                                                      SWIVEL & EXPANSION JOINT DETAIL
 NOTE: Water service pipes installed under concrete slabs should comply with the relevant                                                                                                                                                                                                                                                                             SCALE:                       DATE:                        JOB NO.

 requirements of AS/NZS 3500.1. Heated water service pipes installed under concrete slabs                                                                                                                                                                                                                                                                                         NTS                      24/01/2024                      EWD4896
 should comply with the relevant requirements of AS/NZS 3500.4.
                                                                                                                                                                                                                                                                                                                                                                        THESE DESIGNS ARE COPYRIGHT AND ARE NOT TO BE USED   SHEET SIZE:     SHEET:
                                                                                                                                                                                                                                                                                                                                                                       OR REPRODUCED WHOLLY OR IN PART WITHOUT THE WRITTEN
                                                                                                                                                                                                                                                                                                                                                                                 CONSENT OF 'ENVIRO WATER DESIGN'                 A3           5 OF 6

Page 11

      GENERAL NOTES:                                                                                                                                 ABBREVIATIONS
1.   All Plumbing and drainage works are to be carried out in accordance with the Plumbing and Drainage                       AAV      AIR ADMITTANCE VALVE            ORG     OVERFLOW RELIEF GULLY
                                                                                                                              AC       AIR CONDITIONER                 PLV     PRESSURE LIMITING VALVE
     Act 2018, the Plumbing and Drainage Regulation 2019 and all relevant Australian Standards and
                                                                                                                              AES      ADVANCED ENVIRO SEPTIC          PM      POST MIX
     Codes.                                                                                                                   AT       ABLUTION TROUGH                 RCP     REINFORCED CONCRETE PIPE
2.   These drawings are to be read in conjunction with Architects/ Designers, other consultants drawings                      AP       ACCESS PANEL                    RL      REDUCED LEVEL
                                                                                                                              BN       BASIN                           RPZD    REDUCED PRESSURE ZONE DEVICE
     and Building and Plumbing approvals.                                                                                     BTH      BATH                            S       SINK
3.   Plumbing and drainage work is not to commence until contractor is in possession of Council stamped                       BS       BAR SINK                        SB      SHOWER BATH
                                                                                                                              BT       BUCKET TRAP                     SHR     SHOWER
     approved plans and Compliance Permit.
                                                                                                                              BWU      BOILING WATER UNIT              SL      SURFACE LEVEL
4.   The location of existing services on site have not been confirmed. The contractor must verify all                        C/A      CEILING ABOVE                   SJ      SWIVAL JOINT
     locations of services before commencement of work.                                                                       C/B      CEILING BELOW                   SP      SAMPLE POINT
                                                                                                                              CI       CAST IRON                       ST      STACK
5.   The contractor is to verify that invert and surface levels and required cover over all pipes are correct                 COS      CLEAR OUT TO SURFACE            SW      STORMWATER
     and achievable before commencing work.                                                                                   C/O      COMBI OVEN                      T/A     TO ABOVE
                                                                                                                              CD       CONDENSATE DRAIN                T/B     TO BELOW
6.   Where the contractor deviates from the positions or locations nominated or adds additional fixtures or                   CI       CAST IRON                       TD      TUNDISH
     makes other changes from the original design, the contractor will be responsible for the resubmission                    CS       CLEANERS SINK                   TG      TEST GATE
     of any documents, and any additional fees.                                                                               CU       COPPER                          TYP     TYPICAL
                                                                                                                              CV       CONTROL VALVE                   TW      TEMPERED WATER
7.   The contractor is to compile as constructed drawings of the works during construction and to provide                     CW       COLD WATER                      TMV     THERMOSTATIC MIXING VALVE
     a copy of the updated drawings to the Architect/ designer at the completion of the contract.                             CWD      COLD WATER DROPPER              TV      TEMPERING VALVE
                                                                                                                              CWR      COLD WATER RISER                U       URINAL
8.   All materials are to comply and be installed in accordance with the relevant Australian Standards and                    CWEV     COLD WATER EXPANSION VALVE      U/B     UNDER BENCH
     manufacturer's instructions.                                                                                             DCV      DOUBLE CHECK VALVE              U/GRD   UNDERGROUND
                                                                                                                              DF       DRINKING FOUNTAIN               UNO     UNLESS NOTED OTHERWISE
9.   All levels shown are Australian Height Datum (AHD) unless otherwise noted.                                               DG       DISCONNECTOR GULLY              U/S     UNDER SLAB
10. All sanitary drainage to be 100mm PVC installed at minimum grade of 1.65% (1:60) unless otherwise                         DP       DOWN PIPE                       VB      VANITY BASIN
                                                                                                                              DW       DISHWASHER                      VC      VENT COWL
    noted.                                                                                                                    DIS/WC   DISABLED WATER CLOSET           VCP     VITRIFIED CLAY PIPE
11. All existing services which are no longer required are to be removed or sealed off in an approved                         EJ       EXPANSION JOINT                 VP      VENT PIPE
    manner.                                                                                                                   EPD      ELEVATED PIPE DROPPER           VPR     VENT PIPE RISER
                                                                                                                              EXT      EXISTING                        WC      WATER CLOSET
12. All inspection openings under concrete are to be taken to surface level with approved flush mounted                       F/A      FROM ABOVE                      WM      WASHING MACHINE
    removable caps.                                                                                                           F/B      FROM BELOW                      WP      WASTE PIPE
                                                                                                                              FF       FROG FLAP                       WS      WATER SERVICE
13. All water pipe sizes nominated are Nominal Size (DN). Refer to AS/NZS 3500.1:2018 Table 1.1 for                           FFL      FINISHED FLOOR LEVEL            WU      WALL HUNG URINAL
    equivalent pipe sizes.                                                                                                    FH       FIRE HYDRANT
                                                                                                                              FHR      FIRE HOSE REEL
14. All hose taps are to be fitted with appropiate backflow devices                                                           FSD      FIRE SERVICE DROPPER
15. Locations of control valves are shown diagrammatically only. Determine location on site in an                             FSR      FIRE SERVICE RISER
                                                                                                                              FU       FIXTURE UNITS
    accessible position.                                                                                                      FW       FLOOR WASTE
16. All stormwater is to be graded at 1% (1:100) unless otherwise noted.                                                      FWG      FLOOR WASTE GULLY
                                                                                                                              GAL      GALVANIZED
17. Advanced enviro-septic system is to be installed in strict accordance with manufacturer's written                         GIT      GREASE INTERCEPTOR TRAP
    instructions.                                                                                                             GRD      GROUND
                                                                                                                              GW       GLASS WASHER
                                                                                                                              HC       HOSE COCK
     LEGEND                                                                                                                   HD       HOUSE DRAIN
                                                                                                                              HDPE     HIGH DENSITY POLYETHYLENE
                                                                                            ALL CONSTRUCTION WORK TO BE       H/L      HIGH LEVEL
                                       SANITARY DRAINAGE & SANITARY PLUMBING
                                                                                                                              HW       HOT WATER
          SW       SW        SW        STORMWATER DRAINAGE                                   CARRIED OUT BY A QUALIFIED,
                                                                                                                              HWD      HOT WATER DROPPER
                                       COLD WATER SERVICE                                        LICENSED INSTALLER
                                                                                                                              HWR      HOT WATER RISER
                                       HOT WATER SERVICE                                                                      HWF      HOT WATER FLOW
                                       TEMPERED WATER SERVICE                                CONTRACTOR TO VERIFY ALL         HWR      HOT WATER RETURN
                                       FIRE SERVICE                                      MEASUREMENTS ON-SITE PRIOR TO THE    HWU      HOT WATER UNIT
                                       WASTEWATER EFFLUENT LINE                          COMMENCEMENT OF ANY SUCH WORKS.      IC       INSPECTION CHAMBER
                                       RAIN/TANK WATER SERVICE                                                                IJ       INSPECTION JUNCTION
      OOO          OOO       OOO
                                                                                                                              IV       INVERT LEVEL
                                       VENT PIPE                                                                                                                                                         www.envirowaterdesign.com.au
                                                                                                                              IO       INSPECTION OPENING
                                       PIPE RISER OR DROPPER                                                                  IOS      INSPECTION OPENING TO SURFACE
                                                                                                                                                                                                               M: 0427 287 600
                                                                                                                                                                                   E: [email protected] - A: PO Box 639, Hervey Bay Qld 4655
                                       SANITARY PLUMBING FIXTURE                                                              IM       ICE MACHINE                                               QBCC 15336345 ABN 35 622 809 376
                                       WATER CLOSET FEATURE                                                                   IW       ICE WELL                                  PROJECT:
                                       CAPPED SANITARY SERVICE                                CLIENT:-     __________         JU       JUMP UP                                         PROPOSED RESIDENCE
                                       MIXED WATER SERVICE                                                                    L/L      LOW LEVEL
                                                                                                                                                                                 CLIENT:
          TW       TW        TW        TRADE WASTE                                                                            LT       LAUNDRY TROUGH
          NS       NS        NS        NEW COUNCIL SEWER                                      CLIENT:-     __________         LV       LANDING VALVE
                                                                                                                                                                                      BROWYN SMIDT & KENNETH CLUCAS
      G        G         G       G     GAS SERVICE LINE                                                                       M        WATER METER                               REAL PROPERTY DESCRIPTION:

          EG       EG        EG        EXISTING GAS SERVICE LINE                              DATE:-       __________         MH       MANHOLE                                         LOT 8 ON RP162815
     ETW           ETW           ETW   EXISTING TRADE WASTE DRAINAGE                                                          MW       MIXED WATER                                     8 HINTERLAND CLOSE
          S        S         S         EXISTING COUNCIL SEWER DRAIN                           BUILDER:- _ _ _ _ _ _ _ _ _ _   MWD      MIXED WATER DROPPER
                                                                                                                                                                                       TINBEERWAH
          cw       cw        cw        EXISTING COLD WATER                                                                    MWR      MIXED WATER RISER
                                       EXISTING HOT WATER                                                                     NRV      NON RETURN VALVE                          DRAWN:                        DESIGNED:                   QBCC
          hw       hw        hw                                                               DATE:-       __________                                                               M.ALLWOOD                              A.SMITH                    15336345
          W        W         W         EXISTING COUNCIL WATER MAIN                                                            NTS      NOT TO SCALE
          d        d         d         EXISTING COUNCIL STORMWATER DRAINAGE                                                   OD       OUTSIDE DIAMETER                          SCALE:                       DATE:                        JOB NO.


          sd       sd        sd        EXISTING SANITARY DRAINAGE                                                                                                                            NTS                      24/01/2024                      EWD4896
          SW       SW        SW        STORMWATER BY CIVIL CONTRACTOR                                                                                                              THESE DESIGNS ARE COPYRIGHT AND ARE NOT TO BE USED   SHEET SIZE:     SHEET:
                                                                                                                                                                                  OR REPRODUCED WHOLLY OR IN PART WITHOUT THE WRITTEN
                                                                                                                                                                                            CONSENT OF 'ENVIRO WATER DESIGN'                 A3           6 OF 6