Acoustic Report · MCU15/0122
Attached to the e-mail MCU15/0122 Development Application- Acoustic report Email 4 of 5.
Proposed Medical Centre, Noosaville
Acoustic Barriers
Figure 6 Acoustic Barrier Locations
4.2 Mechanical Plant Noise
4.2.1 Air Conditioners
The general criteria in Section 2.3 and the measured ambient noise levels in
Section 3 provide site-specific criteria for noise from air conditioners as shown in
Table 3.
Table 3 Site-Specific Criteria for Air Conditioning Plant
General Criterion Measured LA90 Site-Specific
Criterion
Day (7 am-6 pm) ≤ background level 36 dB 36 + 5 = 41 dB(A)
LA90 + 5dB(A)
Evening (6 pm- ≤ background level 29 dB 29 + 5 = 34 dB(A)
10 pm) LA90 + 5dB(A)
Night (10 pm-6 am) ≤ background level 29 dB 29 + 3 = 32 dB(A)
LA90 + 3dB(A)
www.roadpro.net.au 5 November 2015 Page 7 of 8