7550B_39 The Anchorage Jetty_Construction Issue · OPW19/0099

Attached to the e-mail Operational Works Application OPW19/0099 - DA form 1 - Plans - Form 15 - 39 The Anchorage Noosaville.

of 8

Text shows just the words. Original shows the document exactly as it was published.

                                                                                                                                                    GENERAL                                                                                                            DIMENSIONS/LEVELS                                                                                                  CONSTRUCTABILITY CONSTRAINTS:
                                                                                                                                                    G1    STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE                         L1. CONSTRUCTION SHALL BE SET OUT USING SURVEY BENCHMARKS PROVIDED BY COUNCIL.                                                                CC1. CONSTRUCTABILITY CONSTRAINTS:
                                                                                                                                                          SPECIFICATION, ARCHITECTURAL, AND OTHER CONSULTANTS' DOCUMENTS.
                                                                                                                                                                                                                                            L2. ALL LEVELS AND SETOUT POINTS ARE SHALL BE CONFIRMED ON SITE BY REGISTERED                                                                      A)   PROTECT ALL EXISTING INFRASTRUCTURE (EG CULVERT CROSSING, PAVEMENTS,
                                                                                                                                                    G2    REFER TO THE ARCHITECTURAL DRAWINGS FOR SETOUT. NO DIMENSIONS SHALL BE            SURVEYOR PRIOR TO CONSTRUCTION. ADVISE ANY DISCREPANCY BEFORE PROCEEDING.                                                                               FENCING & ELECTRICAL POLES/WIRES) FROM ANY DAMAGE.
                                                                                                                                                          OBTAINED BY SCALING FROM DRAWINGS.
                                                                                                                                                                                                                                            L3. DIMENSION STANDARDS:                                                                                                                        B)      ALLOW OF LIKELIHOOD OF FLOW WITHIN THE WATERWAY: EXISTING WATERWAY ARE
                                                                                                                                                    G3    UNLESS OTHERWISE NOTED (UNO), ALL LEVELS ARE IN METRES AND ALL DIMENSIONS ARE IN      - REDUCED LEVELS, CHAINAGES AND COORDINATES ARE ALL IN METRES.                                                                                      FLOODED MULTIPLE TIMES PER YEAR. PROTECT CONSTRUCTION EQUIPMENT AND
                                                                                                                                                          MILLIMETRES.                                                                          - CIVIL DRAWINGS (SKC SERIES): ALL OTHER DIMENSIONS ARE IN METRES (m).                                                                              WORKS.
                                                                                                                                                                                                                                                - STRUCTURAL DRAWINGS (SKS SERIES): ALL OTHER DIMENSIONS ARE IN MILLIMETRES (mm).
                                                                                                                                                    G4    THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE STABILITY OF THE                                                                                                                                                        CC2. NO WORK TO COMMENCE ON SITE UNTIL:
                                                                                                                                                          STRUCTURE UNTIL ITS COMPLETION AND SHALL ENSURE THAT NO PART OF THE STRUCTURE     L4. ALL LEVELS ARE TO AUSTRALIAN HEIGHT DATUM.                                                                                                     - OFFICIAL PRE-START MEETING HELD AND PRE-START MEETING MINUTES ISSUED
                                                                                                                                                          IS OVER-STRESSED BY EXCESSIVE LOADING.                                                                                                                                                                                               - CONTRACTOR'S MANAGEMENT PLANS SUBMITTED (SITE, TRAFFIC, ENVIRONMENT,
                                                                                                                                                                                                                                            L5. DIMENSIONS SHALL NOT BE SCALED FROM DRAWINGS.                                                                                                  SAFETY) FOR SUPERINTENDENT'S REVIEW.
                                                                                                                                                    G5    ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE CURRENT VERSION
                                                                                                                                                          OF THE APPLICABLE STANDARD EXCEPT WHERE VARIED BY THE SPECIFICATION AND/OR        L6. DESIGN USES DIGITAL TERRAIN MODEL GENERATED FROM THE SITE SURVEY. SOME                                                                    DRIVEN PILES:
                                                                                                                                                          DRAWINGS. APPLICABLE CODES OF PRACTICE INCLUDE BUT ARE NOT LIMITED TO THE             ELEMENTS ARE INTERPOLATED AND MAY VARY FROM THE ACTUAL SITE CONDITIONS
                                                                                                                                                          FOLLOWING:                                                                                                                                                                                                                      P1.       PILES SHALL BE CONSTRUCTED IN ACCORDANCE WITH AS2159.
                                                                                                                                                          AS 1163         STRUCTURAL STEEL HOLLOW SECTIONS
                                                                                                                                                          AS 1170         SAA LOADING CODE                                                  DESIGN CRITERIA
                                                                                                                                                                                                                                                                                                                                                                                          P2.       CONSTRUCTION CONSTRAINTS: AVOID LOADING EXISTING REVETMENT WALLS.
                                                                                                                                                          AS 1289         METHODS OF TESTING SOILS FOR ENGINEERING PURPOSES
                                                                                                                                                          AS 1554         WELDING OF STEEL STRUCTURES                                       DC1 THE STRUCTURAL ELEMENTS HAVE BEEN DESIGNED FOR THE FOLLOWING LIVE LOADS
                                                                                                                                                                                                                                                                                                                                                                                          P3.       DESIGN LOADS: PILES TO ACHIEVE GEOTECHNICAL CAPACITIES (VERTICAL &
                                                                                                                                                          AS 1664         ALUMINIUM STRUCTURES                                                  IN ACCORDANCE WITH AS 1170.1: LIVE LOAD REDUCTIONS ARE NOT APPLICABLE.
                                                                                                                                                                                                                                                                                                                                                                                                    HORIZONTAL) SHOWN ON THE DRAWINGS
                                                                                                                                                          AS 1684         RESIDENTIAL TIMBER-FRAMED CONSTRUCTION                                ELEMENT              UDL        CONCENTRATED
                                                                                                                                                          AS 1720         TIMBER STRUCTURES                                                     ROOF                 0.25 kPa   1.1KN
                                                                                                                                                                                                                                                                                                                                                                                          P4.       REQUIRED PILE POSITION TOLERANCES:
                                                                                                                                                          AS 2159         PILING CODE                                                           INTERNAL FLOORS      1.5kPa
                                                                                                                                                          AS 4100         STEEL STRUCTURES                                                      DECK                 2.0kPa
                                                                                                                                                                                                                                                                                                                                                                                                    PLAN POSITION: +/- 50mm AT UNDERSIDE OF EACH GROUND BEAM.
                                                                                                                                                          AS 5100         BRIDGE DESIGN                                                         THOROUGHFARES        4.0 kPa
                                                                                                                                                                                                                                                                                                                                                                                                    PILE VERTICALITY:
                                                                                                                                                          BCA             BUILDING CODE OF AUSTRALIA (NATIONAL CONSTRUCTION CODE)                                                                                                                                                                   - WITHIN 4% FOR ALL PILES
                                                                                                                                                                                                                                            DC2 WIND LOADS HAVE BEEN DETERMINED IN ACCORDANCE WITH AS 1170.2 BASED ON:
                                                                                                                                                    G6    ANY DISCREPANCY SHALL BE REFERRED TO THE SUPERINTENDENT FOR A DECISION BEFORE         IMPORTANCE LEVEL                2
                                                                                                                                                                                                                                                                                                                                                                                          P5.       PILE TOE LEVELS ON THE DRAWINGS ARE ESTIMATED LEVELS. ACTUAL TOE LEVELS
                                                                                                                                                          PROCEEDING WITH THE WORK.                                                             REGION                          N4
                                                                                                                                                                                                                                                                                                                                                                                                    SHALL BE DETERMINED DURING CONSTRUCTION BY AN RPEQ-CERTIFIED
                                                                                                                                                                                                                                                ULTIMATE WIND SPEED             61 m/s
                                                                                                                                                                                                                                                                                                                                                                                                    GEOTECHNICAL ENGINEER.
                                                                                                                                                    G7    ALL PROPRIETARY PRODUCTS NOT DEEMED TO COMPLY WITH THE BCA SHALL HAVE                 SERVICEABILITY WIND SPEED       39.0 m/s
                                                                                                                                                          THIRD-PARTY CERTIFICATION WITH RELEVANT TESTING AND SIGN-OFF BY AN RPEQ ENGINEER.     TERRAIN CATEGORY                2
                                                                                                                                                                                                                                                                                                                                                                                          P6.       DO NOT FOUND PILES HIGHER THAN TOE LEVELS ON DRAWINGS, UNLESS APPROVED BY
                                                                                                                                                          PROPRIETARY PRODUCTS INCLUDES PREFABRICATED TRUSSES, LIGHT-GAUGE STEEL                                                                                                                                                                    BOTH THE SUPERINTENDENT AND THE GEOTECHNICAL ENGINEER. THE
                                                                                                                                                          FRAMING, FLOORING PRODUCTS, RECYCLED TIMBER AND PLASTICS, BALUSTRADES, SCREENS, DC3 EARTHQUAKE LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 1170.4 BASED                                                                             SUPERINTENDENT SHALL SEEK ADVICE FROM THE DESIGN ENGINEER AS REQUIRED.
                                                                                                                                                          SHADE FABRICS, JOINERY, PARTITIONS AND OPERABLE WALLS.                                ON:
                                                                                                                                                                                                                                                ACCELERATION COEFFICIENT        0.06
File: C:\- Projects\00 - Black & More\7550 - Noosa Jetty Builders\7550B - 39 The Anchorage, Noosaville. QLD\ 7550B - Notes Sheet.dwg




                                                                                                                                                    G8    REFER TO ARCHITECTS DRAWINGS FOR DETAILS OF ALL GROOVES, FILLETS, HOBS, DRIP          SITE FACTOR                     1
                                                                                                                                                          GROOVES AND THE LIKE.                                                                 IMPORTANCE LEVEL                1
                                                                                                                                                                                                                                                STRUCTURE TYPE
                                                                                                                                                    G9    GIVE AT LEAST 24 HOURS NOTICE OF AN INSPECTION BEING REQUIRED FOR :                   DESIGN CATEGORY                 EDC1
                                                                                                                                                          - PILING
                                                                                                                                                          - JETTY FRAMING (TIMBER)                                                                                     DC4 FIRE RESISTANCE LEVELS OF STRUCTURAL ELEMENTS HAVE BEEN TAKEN AS FOLLOWS:
                                                                                                                                                          - BRACING AND TIE DOWN                                                                                           ELEMENT       FRL (mins)
                                                                                                                                                                                                                                                                           COLUMNS        -/-/-
                                                                                                                                                    G10   ALL FABRICATION SHOP DRAWINGS SHALL BE PROVIDED TO THE ENGINEER FOR REVIEW AND                                   BEAMS          -/-/-
                                                                                                                                                          COMMENT IN A3 HARDCOPY OR PDF FORMAT.                                                                            WALLS          -/-/-
                                                                                                                                                    G11 ABBREVIATIONS (GENERAL):                                                                                       DC5 DETERMINATION OF DESIGN LOADING FOR NON-STRUCTURAL ELEMENTS SUCH AS
                                                                                                                                                        NTS      NOT TO SCALE                                                                                              CEILING AND CLADDING SYSTEMS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
                                                                                                                                                        UNO      UNLESS NOTED OTHERWISE
                                                                                                                                                        NSOE     NOT SHOWN ON ELEVATION                                                                                DC6 FLOOD LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 5100 WITH NOMINAL
                                                                                                                                                        NSOP     NOT SHOWN ON PLAN                                                                                         FLOOD VELOCITY TO BE CONFIRMED BY HYDRAULIC REQUIREMENTS AS FOLLOWS:
                                                                                                                                                        TYP      TYPICAL                                                                                                   -V100 = 1m/s.
                                                                                                                                                        (O)      OVER
                                                                                                                                                        (U)      UNDER                                                                                                 TEMPORARY WORKS:
                                                                                                                                                        CRS      CENTRES
                                                                                                                                                        NOM      NOMINAL
                                                                                                                                                                                                                                                                       T1.       MAINTAIN THE WORKS IN A SAFE CONDITION. ENSURE STRUCTURES ARE NOT
                                                                                                                                                        CFW      CONTINUOUS FILLET WELD
                                                                                                                                                                                                                                                                                 OVER-STRESSED AT ANY TIME. TEMPORARY ROAD SURFACES SHALL BE TRAFFICABLE
                                                                                                                                                                                                                                                                                 AT ALL TIMES. POTHOLES ETC SHALL BE MONITORED AND REPAIRED.
                                                                                                                                                                                                                                                                       T2.       CONTRACTOR'S RPEQ TO CERTIFY DESIGN AND CONSTRUCTION FOR TEMPORARY
                                                                                                                                                                                                                                                                                 WORKS: STRUTS, PROPPING, FORMWORK STRIPPING AND PROPPING PROCEDURES, TIE
                                                                                                                                                                                                                                                                                 BACKS, EXCAVATION SHORING, PROTECTION WORKS, DE-WATERING SYSTEMS,
                                                                                                                                                                                                                                                                                 FORMWORK, EARLY LOADING OF STRUCTURES AND THE LIKE.
                                                                                                                                                                                                                                                                                                                                                                                                                                                                           CONSTRUCTION ISSUE
Printed: 18 April 2019, 3:32 PM




                                                                                                                                                                                                                              NOOSA JETTY BUILDERS           © Black & More                                                                          Client                                     Project                                           Drawing Title
                                                                                                                                                                                                                              JoB No: 1166                   This document is and shall remain
                                                                                                                                                                                                                                                                                                                Black & More
                                                                                                                                                                                                                                                                                                                ABN 19 609 960 232
                                                                                                                                                                                                                                                                                                                                                             NOOSA JETTY BUILDERS   PROPOSED NEW JETTY
                                                                                                                                                                                                                              Address:                       the property of Black & More.                                                           Address
                                                                                                                                                                                                                                                                                                                                                             39 THE ANCHORAGE, NOOSAVILLE. QLD 4566                                                GENERAL NOTES - SHEET 1 OF 2
                                                                                                                                       Revisions




                                                                                                                                                                                                                                                             This document may only be used                     93 Digger St Cairns North QLD 4870
                                                                                                                                                                                                                              39 THE ANCHORAGE, NOOSAVILLE                                                      PO Box 999N Cairns North QLD 4870
                                                                                                                                                                                                                                                             for the purposes for which it was
                                                                                                                                                                                                                              LOT 795 ON 9910421             commissioned and in accordance                                                          Drawn           Drawing        Approved                               Date    18/04/19
                                                                                                                                                                                                                                                                                                                Telephone (07) 4031 9944                        ST             FM
                                                                                                                                                                                                                              Client:                        with the Terms of Engagement for                                                                        Check
                                                                                                                                                                                                                                                             the commission. Unauthorised use                   Email     [email protected]                                                                                                   Drawing Size Scale (A3 size)     Drg No                 Revision
                                                                                                                                                   C1 CONSTRUCTION ISSUE                           FM      FM        18/04/19 S & J HARRIS                                                                                                                                                                                   RPEQ 19951
                                                                                                                                                   No.                         Description       Reviewed Approved     Date
                                                                                                                                                                                                                                                             of this document in any form
                                                                                                                                                                                                                                                             whatsoever is prohibited.
                                                                                                                                                                                                                                                                                                                Internet  www.blackm.com             Designed
                                                                                                                                                                                                                                                                                                                                                                FM
                                                                                                                                                                                                                                                                                                                                                                     Design
                                                                                                                                                                                                                                                                                                                                                                     Check     JB    Drawing is not to be used for construction unless approved      A3             NOT TO SCALE            7550B- S002    C1
                                                                                                                                       External References:    B&M-JETTY-TITLE-A3_e.dwg

Used in these records

About this file

File size
1.1 MB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

7550B_39 The Anchorage Jetty_Construction Issue.pdf · 1.1 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.