Bushfire Report


    (a) be fully sarked with sarking, except that foil backed insulation blankets may be
        installed over battens; OR
    (b) have any gaps sealed at the fascia, or wall line, hips and ridges by:
        (i) a mesh or perforated sheet with a maximum aperture of 2 mm, made of corrosion-
            resistant steel, bronze or aluminium (this may include gutter guard), or
          (ii) mineral wool, or
          (iii) other non-combustible material, or
          (iv) -a combination of any of the above.

Roof penetrations

The following apply to roof penetrations:
    (a)   roof penetrations, including roof lights, roof ventilators, roof-mounted evaporative
          cooling units, aerials, vent pipes and supports for solar collectors, shall be adequately
          sealed at the roof to prevent gaps greater than 3 mm.
    (b)   openings in vented roof lights, roof ventilators or vent pipes shall be fitted with ember
          guards made from a mesh or perforated sheet with a maximum aperture of 2 mm,
          made of corrosion-resistant steel, bronze or aluminium.
    (c)   glazed elements in roof lights and skylights may be of polymer provided a grade safety
          glass diffuser, complying with AS 1288, is installed under the glazing.

Eaves linings, fascias and gables

The following apply to eaves linings, fascias and gables:
    (a) gables shall comply with requirements for walls.
    (b) eaves ventilation openings are to be fitted with ember guards and be made of
          corrosion resistant steel, bronze or aluminium.
The Standard does not provide construction requirements for fascias, bargeboards and eaves
linings.

Gutters and downpipes

The Standard does not provide material requirements for gutters and downpipes, with the
exception of box gutters.

Box gutters are to be non-combustible and flashed at the roof junction with non-combustible
material.

If installed, gutter and valley leaf guards are to be non-combustible.

Verandas, decks, steps, ramps and landings

Decking may be spaced. There is no requirement to enclose the subfloor spaces of verandas,
decks, steps, ramps or landings.

Decking, stair treads and trafficable surfaces of ramps and landings less than 300 mm
(measured horizontally at deck level) from glazed elements that are less than 400 mm
(measured vertically) from the surface of the deck are to be made from:
    (a) of non-combustible material; or
    (b) of bushfire-resisting timber; or
    (c) a combination of items (a) and (b) above.


Max Bushfire Protection Consulting                                                          53
Log in to download the original file

Appendix F - Bushfire Hazard Assessment and Managment Report.pdf · 5.4 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.