Attachment K - HSTP Design
Very large file (11.6 MB): the original may take a few minutes to open or download. The page text below is quick to read.
3.0 DESIGN DETERMINATION We have determined the soil to have the following characteristics Soil Characteristics (AS/NZS 1547/2012) Borehole Nos 1 and 2 Depth (mm) 0- 300 Soil Category 3 Indicative Drainage Moderate Structure High Texture Loam Indicative Permeability P (m/day) as Ksat 1.5-3.0 For our calculations we have assessed the design flow as follows Design calculations DIR (mm/day) (Advanced/Secondary quality effluent) 4.0 Hydraulic load (It/day/person) 120 Design flow Q (It/day) (equivalent population 7 people) 840 Design sizing calculation Ai=Q/DIR = 840/4.0 Disposal Area Ai (m’) =210 Fixed Low pressure heavy droplet ‘wobbler’ type (or such) spray irrigation system Note — AS/NZS 1547-2012 (Appendix H, Table H1) lists the typical wastewater design flow allowance for households with an on-site roof water tank supply as 120litres/person/day (all wastes). With the installation of standard water reduction fixtures the design flow can be reduced substantially. Where the design flow ‘Q’, nominated above, is exceeded the area (Ai) will need to be increased accordingly. On-site sewerage systems are not suitable for accepting waste from garbage grinders. Unearthed Geotechnical P/L. 3 Design Report 023-038