Figure 5.3 – Post-Development Mitigated Model
5.3.7 Comparison of Peak Flows at Lawful Point of Discharge
The pre-development and post-development mitigated peak flow rates were compared for the
catchment and are shown in Table 5-6 and Table 5-7 below.
Table 5-6 - Comparison of Peak Flows
Pre-Development Peak Flows Post-Development Peak Flows Post-Development Peak Flows
Property State (Un-Mitigated) (Un-Mitigated) (Mitigated)
(m3/s) (m3/s) (m3/s)
50% AEP
(m3/s)
0.035 0.055 0.034
20% AEP
(m3/s)
0.058 0.084 0.048
10% AEP
(m3/s)
0.065 0.094 0.056
5% AEP (m3/s) 0.084 0.110 0.064
2% AEP (m3/s) 0.102 0.135 0.089
1% AEP (m3/s) 0.115 0.155 0.087
Site Based Stormwater Management Plan
Proposed Townhouse Development at 5 Pearl Street, Cooroy