WP1323 - Working Near Overhead and Underground Electric Lines
Attached to the e-mail MCU16/0081 - Energex advice agency response - 28 Eenie Creek Road Noosaville.
Electricity Entity Requirements:
Working Near Overhead and Underground Electric Lines
Minimum statutory clearances from nearby overhead electric lines for scaffolding erected with
barriers affixed
Voltage Level Horizontal Distance “A” Vertical Distance “B”
(in m) (in m)
Low voltage conductors 1.5 2.7
(uninsulated)
Low voltage conductors 0.3 0.6
(insulated) – these distances can
only be applied after the integrity
of the insulation has been
verified by Electricity Entity
Above LV and up to 33 kV 1.5 3.0
(uninsulated)
Above LV and up to 33 kV Contact Electricity Entity for consultation.
(insulated)
Above 33 kV (uninsulated) Additional requirements may apply for voltage levels above 33 kV,
contact the Electricity Entity for consultation.
NOTE: Dimensions “A” and “B” is between the scaffolding and the closest conductor
of the overhead electric line. Dimension B is also taken from the lowest part of
the mid span sag adjacent to the scaffolding.
Check this is the latest version before use. Page 13of30 EGX WP1323 Ver 2
9 June 2015 EE BS001405R107 Ver 2
Joint Reference Document between Energex and Ergon Energy
Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062