WP1323 - Working Near Overhead and Underground Electric Lines

Attached to the e-mail MCU16/0081 - Energex advice agency response - 28 Eenie Creek Road Noosaville.

of 31

Page text shows just the words. Original shows the document exactly as it was published.

Electricity Entity Requirements:
Working Near Overhead and Underground Electric Lines

                                               Minimum Separation Requirements

Underground Services Running Parallel with Electricity Entity Electrical Assets
(Minimum Separation required in mm)
Voltage         Gas           Communication                    Water                    Sanitary drainage           Storm
 Level                           or TV                                                                              Water
                                                      ≤DN 200          >DN200         ≤DN 200        >DN 200
     LV         300
              (Ergon)                100
                250                                      500           *1000            500             1000         500
     HV
             (Energex)               300

                                *Contact your local utility/council to obtain specific separation distances


Underground Services Crossing Electricity Entity Electrical Assets
(Minimum Separation required in mm)
Voltage         Gas           Communication                    Water                 Sanitary drainage         Storm Water
 Level                           or TV

     LV
                100                  100                         300                          300                 100
     HV


Notes:
1. These clearances are each Electricity Entity’s minimum requirements, additional separation may be required by
    the Service Owner. The greater of the separation requirements shall apply.
2.    Where the above tables does not list a separation requirement for a particular underground service type, the
      following minimum separation from electricity entity electrical assets shall apply:
         LV = 100 mm
         HV = 300 mm
3.    Compliance with these minimum separation requirements does not guarantee that issues such as Earth
      Potential Rise (EPR) and Low Frequency Induction (LFI) are managed, where these issues need to be
      managed, advice will need to be sought from an RPEQ Engineer
4.    All separation distances are measured from the exterior surface of the conduit / cable not centrelines or inner
      wall surfaces.

6.4. Additional Details and Fact Sheets on Electricity Entity Requirements
Additional details and Fact Sheets on Electricity Entity requirements for working near
underground electrical assets are located on the following internet site.
Energex: https://www.energex.com.au/safety/safety-around-the-network
Ergon Energy: https://www.ergon.com.au/network/safety/business-safety/the-outdoor-
workplace/working-near-powerlines




Check this is the latest version before use.                Page 20of30                                       EGX WP1323 Ver 2
9 June 2015                                                                                               EE BS001405R107 Ver 2
                            Joint Reference Document between Energex and Ergon Energy
                    Energex Limited ABN 40 078 849 055  Ergon Energy Corporation Limited ABN 50 087 646 062
Log in to download the original file

WP1323 - Working Near Overhead and Underground Electric Lines.pdf · 710 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.