WP1323 - Working Near Overhead and Underground Electric Lines
Attached to the e-mail MCU16/0081 - Energex advice agency response - 28 Eenie Creek Road Noosaville.
Electricity Entity Requirements:
Working Near Overhead and Underground Electric Lines
Minimum Separation Requirements
Underground Services Running Parallel with Electricity Entity Electrical Assets
(Minimum Separation required in mm)
Voltage Gas Communication Water Sanitary drainage Storm
Level or TV Water
≤DN 200 >DN200 ≤DN 200 >DN 200
LV 300
(Ergon) 100
250 500 *1000 500 1000 500
HV
(Energex) 300
*Contact your local utility/council to obtain specific separation distances
Underground Services Crossing Electricity Entity Electrical Assets
(Minimum Separation required in mm)
Voltage Gas Communication Water Sanitary drainage Storm Water
Level or TV
LV
100 100 300 300 100
HV
Notes:
1. These clearances are each Electricity Entity’s minimum requirements, additional separation may be required by
the Service Owner. The greater of the separation requirements shall apply.
2. Where the above tables does not list a separation requirement for a particular underground service type, the
following minimum separation from electricity entity electrical assets shall apply:
LV = 100 mm
HV = 300 mm
3. Compliance with these minimum separation requirements does not guarantee that issues such as Earth
Potential Rise (EPR) and Low Frequency Induction (LFI) are managed, where these issues need to be
managed, advice will need to be sought from an RPEQ Engineer
4. All separation distances are measured from the exterior surface of the conduit / cable not centrelines or inner
wall surfaces.
6.4. Additional Details and Fact Sheets on Electricity Entity Requirements
Additional details and Fact Sheets on Electricity Entity requirements for working near
underground electrical assets are located on the following internet site.
Energex: https://www.energex.com.au/safety/safety-around-the-network
Ergon Energy: https://www.ergon.com.au/network/safety/business-safety/the-outdoor-
workplace/working-near-powerlines
Check this is the latest version before use. Page 20of30 EGX WP1323 Ver 2
9 June 2015 EE BS001405R107 Ver 2
Joint Reference Document between Energex and Ergon Energy
Energex Limited ABN 40 078 849 055 Ergon Energy Corporation Limited ABN 50 087 646 062