10. Demonstrate that the site can be developed with no net increase in runoff from
the site for storm events up to a 1 in 100 year Average Recurrence Interval. In
this regard the stormwater drainage system designed for the site will need to
incorporate an adequate detention system (holding tanks and rainwater tanks) to
retain these flows, which can be utilised for irrigation, toilet flushing, hose down of
paved surfaces, and ground water recharging.
The present proposal and Stormwater Management Plan does not address this
issue.
In this regard additional flows into the existing drainage system in the David Low
Way will not be supported.
11. Demonstrate that the site can be drained without the use of pumps in accordance
with Specific Outcome O17 of Table 14-46 of the Driveways & Carparking Code.
In this regard the basement proposal cannot be supported unless it can be
drained by gravity means.
The applicant is also advised that given stormwater from the carparking and
driveway areas of will contain contaminants such as oil, grease, and fuel, all
stormwater runoff will need to be collected and discharged through a suitable
grease/oil arrestor and/or Gross Pollutant Traps to separate these contaminants
and prevent them from entering Council’s drainage system.
Traffic Issues
12. The previously submitted traffic report shall be amended to reflect the new
proposal plan (and any changes that may be generated as a result of this
information request) and resubmitted for Council to review.
Engineering Reports
13. Please arrange for all engineering design plans and engineering reports
submitted with the application to be certified by an appropriately qualified
Registered Professional Engineer Queensland (RPEQ), as it is noted that none of
the plans nor any of the engineering reports have been prepared, checked, and
approved by an authorised person. In this regard none of the plans or the
engineering reports will be assessed in detail until a RPEQ has authorised them.
Council therefore reserves the right to make a subsequent request for further
information upon review and assessment of the authorised documentation with
no consequence to IDAS time lines set by the Integrated Planning Act.
The applicant and any consultants assisting in the preparation of this
development proposal are advised that an independent check of some or all of
the technical reports and plans submitted may be forwarded to Council’s own
expert specialists, and the cost of this independent review will be borne by the
applicant.
Please provide four (4) copies of all information that you are providing. In addition, it
would assist Council if you could also provide an electronic copy of your response.
Please be aware that under Section 3.2.12 of the Integrated Planning Act, the applicant
is to respond to any information request within 12 months of the request or otherwise,
the application lapses.
Award Winner - Australian Clean Beach
Challenge 2004 Litter Prevention
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
06/2689 - Request for further Info [As Published]Related documentApplication case desk ↗
About this file
- File size
- 25 KB (small file)
- File type
No other editions are linked here.