 Attention: Peter Cook                                                                                                         04 Jul 2023
 By Email                                                                                                  ARCOS PROJECT:230489
                                                                                                                   Report 01 Revision A
Report on Geotechnical Investigation
Proposed Secondary Dwelling
70 Blanckensee Road, Black Mountain
Arcos Unit Group Pty Ltd (Arcos Group) has undertaken a geotechnical investigation for the above project and client.
SUMMARY OF INVESTIGATION

                     Results of Australian Geomechanic Society Landslide Risk Assessment
                                                                    Low
Note:     The above is a summary of the detailed investigation results discussed within this report. The entire report must be read,
          understood and kept in entirety.




Graduate Geotechnical Engineer                                                                    Principal Geotechnical Engineer




Mitchell Horne B.Eng (Civ)(Hons)                                                 Billy Blake B.Eng (Civ)(Hons), MIEAust, RPEQ,
                                                                                                                   CPEng, NER
[email protected]                                                                        [email protected]
For and On Behalf of Arcos Group                                                                For and on Behalf of Arcos Group




Sunshine Coast | Brisbane | Gold Coast
Full text of the other 21 pages

Page 2

                                                                                                       ABN 51 640 311 842
                                                                                                       arcosgroup.com.au
                                                                                      Sunshine Coast | Brisbane | Gold Coast




1         INTRODUCTION
Arcos Unit Group Pty Ltd (Arcos Group) was commissioned to undertake a geotechnical investigation for the project
at the location described on the title page of this report.
This report outlines the results of the investigation, laboratory testing, analysis, and interpretive reporting on the
following items:
 Review of the existing slope stability hazards, their attributed risks and impacts of the proposed development in
  alignment with the practices set out within the Australian Geomechanics Society guidelines; and,
 Provide recommendations from a geotechnical context that will avoid or reduce any potential instability.
This report must be kept in entirety. The use of this document is exclusively undertaken in accordance with our terms
and conditions.

2         REGIONAL GEOLOGY
The site is in an area underlain by the Middle Triassic aged Kin Kin Beds Formation, which typically comprises
“Strongly cleaved and commonly kinked mudstone with thin siltstone laminae; minor volcanilithic sandstone”.

3         EXISTING STABILITY RISK
Local authorities prepare mapping tools to aid in assessing potential slope stability requirements. The mapping tools
are a “high level” approach where the site specific investigations are specific to a particular site/allotment. It is
important to note that where a site specific investigation and slope stability assessment are undertaken, they take
precedence.
Reference to the available overlays for the area show the site has been initially mapped as “Moderate” in terms of
landslide hazard.

4         GEOTECHNICAL INVESTIGATION
A site classification investigation was undertaken by Global Testing on 23 May 2023. The purpose of the investigation
was to inform the site classification and effluent design for the proposed secondary dwelling. The investigation
comprised the drilling and logging of 5 boreholes at the location of the proposed secondary dwelling and the proposed
effluent irrigation area (refer test location plan). The subsurface conditions encountered in the boreholes generally
comprised potentially uncontrolled clayey sand fill to approximately 0.5 m depth, overlying stiff or stronger sany and
silty clays to termination of the bores at 4 m depth

5         ASSESSMENT
Geotechnical comments are based on the factual findings of the investigation, best practice, local experience,
published correlations; however, are fundamentally founded in opinion and this should be considered.
A site assessment was undertaken by a graduate geotechnical engineer on 3 July 2023. The allotment is described
as Lot 1 on RP193199 and encompasses approximately 20 000 m2. The site has been proposed to be placed in a
relatively level and clear area near the existing dwelling. Surface levels across the allotment are intially level where
the secondary dwelling is proposed at approximately RL203 (based on Noosa Council Intramaps) before falling away
to the north at angles of approximately 10 – 15 degrees to approximately RL 153. No obvious signs of disturbed
ground, tension cracks or hummocks were noted in the vicinity of the proposed residence during the assessment. A
variety of vegetation ranging from small shrubs to mature trees were observed. The mature trees were all observed
to be typically vertical with no misshapen or curved trunks. Misshapen or curved trunks are usually good indicators
for previous slope instability.


Sunshine Coast | Brisbane | Gold Coast

Page 3

                                                                                                          ABN 51 640 311 842
                                                                                                          arcosgroup.com.au
                                                                                         Sunshine Coast | Brisbane | Gold Coast




6         AGS ASSESSMENT
Landslides are caused where a soil or rock mass has a decrease in strength, usually attributed to groundwater,
resulting in the material not being able to maintain its own self-weight resulting in a slope failure.
The Australian Geomechanics Society (AGS) developed a set of tools and procedures for assessing the stability of
a slope. The tools and procedures presented with the AGS documentation form the basis of the assessment
undertaken herein and their documentation is attached for reference.
The guidelines also identify that the regulator typically sets the standard for levels of tolerable risk. AGS defines
tolerable risk as “risks within a range that society can live with so as to secure certain benefits. It is a range of risk
regarded as non-negligible and needing to be kept under review and reduced further if practicable”.
The guides suggest that areas of moderate or greater risk should not be developed unless a rigorous remediation
plan be implemented to reduce the area to a level of Acceptable Risk. AGS defines acceptable risk as “risk which
everyone affected is prepared to accept. Action to further reduce such risk is usually not required unless reasonably
practicable measures are available at low cost in terms of money, time and effort.”.
AGS suggest that regulators generally accept risk levels of “low” or lower as a level of acceptable risk.
AGS prepared a semi-quantitative assessment tool for determining the level of risk for a site. The tool separates the
potential hazards for a site, from a stability context, and rates them with a level of risk frequency. The multiplication
of these individual risk frequency summates as the risk frequency rating which is then measured against the levels
of risk nominated by AGS.
The results of this analysis are shown in Table 1.
TABLE 1: AGS ASSESSMENT

                Hazard                         Likelihood                Consequence                    Risk Level
             Global Failure                   Barely Credible             Catastrophic                       Low
         Creep in Shallow Soils                  Unlikely                    Medium                          Low
  Rotational or translational slide down           Rare                       Major                          Low
                 the slope
          Existing batter failure             Almost Certain              Catastrophic                       Low


Based on the results of the AGS assessment, the perceived risk based on the conditions encountered and information
available at the time of the assessment is “Low”.

7         HILLSIDE CONSTRUCTION
The following works should be implemented in addition to other items highlighted within this document. These points
are considered to be typical good hillside construction practice as explained in attached documentation:
 A minimum footing depth of 1.2 m is recommended. Footings should be founded into stiff (or stronger) natural
  clays.
 Fill should be limited to no more than 1 m and should be step keyed into the existing slope. The fill should be
  formed at no steeper than 3H:1V, unless retained by an engineered retention system. All fill should be placed in
  accordance with AS3798.
 Where slopes are not supported by an engineer designed support system, natural slopes within or near movement
  sensitive areas should be no steeper than 2.5H:1V.



Sunshine Coast | Brisbane | Gold Coast

Page 4

                                                                                                        ABN 51 640 311 842
                                                                                                        arcosgroup.com.au
                                                                                       Sunshine Coast | Brisbane | Gold Coast




 All stormwater and surface water is to be discharged by an approved stormwater drainage system. The use of
  subsurface drainage systems are not suitable unless greater than 50 m downslope from the envelope at this site.
 Ongoing maintenance of effluent wastewater areas are also considered mandatory.
 Avoid leakage from underground services and drains. Any leaking services or blocked drains should be remedied
  promptly.
 Erosion protection of cut and fill batters will be required. Batters should incorporate crest and toe drainage. Batters
  should be vegetated appropriately to minimise erosion.
 Overland flow paths will need to be carefully directed to approved outlets to minimise erosion possibility.

8         GEOTECHNICAL RECOMMENDATIONS
The following sections details specific geotechnical constraints or recommendations in addition to general hillside
construction notes.


8.1       FOOTINGS
In accordance with industry standards, a geotechnical engineer from Arcos should undertake the testing within the
footings to confirm that the encountered material is in alignment with the adopted parameters and assumptions
provided within this report. Where this does not occur, Arcos cannot be held liable for any of the information presented
within this report.
All footings will need to be designed to accommodate potential ground surface movement, settlement values and
any additional settlement values associated with the placement of new fill.
Settlement for suitably sized and designed high level footings should be in the order of 1-2% of the width of the
footing.
If footings are located adjacent to an underground service or other obstruction that is not homogenous with the
founding strata, the footing should be extended a minimum 0.3 m below an imaginary line projected at a 45 degree
angle from the lowest point of the service/obstruction. This is depicted graphically for reference:




Where footings found into stiff or stronger clays residual clays, they may be dimensioned for a maximum allowable
bearing pressure of 100 kPa. Based on the borelogs, the above material is encountered at approximately 0.7 m to
0.8 m depth below existing surface levels at the time of the investigation.



Sunshine Coast | Brisbane | Gold Coast

Page 5

                                                                                                       ABN 51 640 311 842
                                                                                                       arcosgroup.com.au
                                                                                      Sunshine Coast | Brisbane | Gold Coast




The ultimate geotechnical end bearing and shaft adhesion parameters are presented in Table 2 for deep level
footings where high level footings are not suitable. The values given will need to reduced by applying a suitable
geotechnical strength reduction factor (Φg) for limit state or divided by a suitable factor of safety for working stress
methods. The Φg should be selected by the designer.
TABLE 2: DEEP LEVEL FOOTING – ULTIMATE GEOTECHNICAL PARAMETERS (LONG PILE)

                  Material                          Bored               Bored            Screw               Screw

                                                   Fb (kPa)            Fs (kPa)         Fb (kPa)            Fs (kPa)
           Stiff or stronger clays                    675                30                450                  NR
 Notes: Fb = Base Bearing (Ultimate); Fs = Shaft Adhesion (Ultimate)


The upper 1 m of soil profile should be ignored in shaft calculations for bored piles to allow for shrinkage cracks. Due
to installation disturbance, shaft adhesion should be ignored for steel screw piles. The values presented in Table 2
assume that the material equal to four pile diameters below the base of any footings is as strong or stronger.
Settlement values are subjected to a variety of factors; however, a properly designed and constructed pile should
have a serviceability settlement between 1% and 2% of its’ diameter.




ATTACHMENTS
About Your Geotechnical Report
Interpretation of the Subsurface Sheets
Practice Note Guidelines
Client Supplied Information




Sunshine Coast | Brisbane | Gold Coast

Page 6

                                                                                                    ABN 51 640 311 842
                                                                                                    arcosgroup.com.au
                                                                                   Sunshine Coast | Brisbane | Gold Coast




                                         ABOUT YOUR GEOTECH REPORT



                                                            Reporting
These notes have been provided to clarify and               The report has been prepared and reviewed by
enhance the reader’s understanding of the                   suitably qualified and experienced persons. The
terminology used throughout the report, and also to         persons draw on previous experience, local
identify where limitations exist. All investigations are    knowledge, published literature, and otherwise
undertaken based on budgetary constraints which             standard engineering approaches and principals. The
impart a level of uncertainty as a result of limiting the   context of which the report has been prepared for must
amount of investigation undertaken.                         be considered and if the context changes, due
                                                            consideration should be given to the possibility that the
                                                            report is no longer considered relevant and review by
Copyright                                                   Arcos Unit Group Pty Ltd must be undertaken.
This report remains the property of Arcos Unit Group        Arcos Unit Group Pty Ltd undertakes quality
Pty Ltd at all times unless ownership is transferred in     assurance checks in accordance with its’ quality
writing. It cannot be included in any documentation         system requirements; however, restrictions on the
without the express written permission of Arcos Unit        project outside of Arcos Unit Group Pty Ltd’s control
Group Pty Ltd                                               can result in unanticipated variations, changes in
                                                            policy or interpretation of said policies by the relevant
                                                            authority, or the actions of contractors subject to
Subsurface Report Sheets (Bores etc)                        commercial pressure.
The provided subsurface sheets are inherently an
interpretation undertaken by a suitably qualified and
experienced person; however, the reliability of the
                                                            Site Variations
provided information will rely on the method of             If site variations become evident at the time of
investigation. It is prudent to state that these sheets     construction or after the release of a report, Arcos Unit
only represent a very small percentage of the               Group Pty Ltd requests immediately notification. This
subsurface conditions across a particular project.          notification is proposed in order to assist in
                                                            remediation prior to any permanent structures or
It reasons that given the relatively small representation
                                                            design procedures are undertaken.
of the subsurface conditions for a project, spacial
variability between testing locations must be taken into
consideration including the orientation of strata           Collaboration
intersections.
                                                            Arcos Unit Group Pty Ltd strongly recommends open
The presence or lack of groundwater is usually stated       and collaborative communication about the use and
on the subsurface sheets; however, it must be noted         inherent interpretation of Arcos Unit Group Pty Ltd’s
that the measurements undertaken onsite are typically       report. Please contact the author of the report to
very inaccurate and if the presence or lack of              arrange for an obligation free discussion regarding the
groundwater will have any degree of affect on the           potential benefits of having geotechnical consultants.
project, additional groundwater monitoring techniques
should be employed such as groundwater monitoring
wells.




Sunshine Coast | Brisbane | Gold Coast

Page 7

                                                                                                           ABN 51 640 311 842
                                                                                                           arcosgroup.com.au
                                                                                        Sunshine Coast | Brisbane | Gold Coast




                                      Interpretation of the Subsurface Sheets


The terminology included on Arcos Unit Group Pty            the most important component. Typically, the strength
Ltd’s has been evolved from AS1726:2016. Typically          of rock is based on laboratory testing, tactile
a soil’s strength, colour, plasticity, grain size, other    assessment and other observations as relevant. The
inclusions, and moisture will be described. A rock’s        industry standard method for assessing the strength of
strength, weathering, colour, grain, and other              rock in the field is to use the point load strength index
inclusions are typically described.                         (AS4133.4.1). It is important to note that the point load
                                                            strength index does not take into consideration the
                                                            degree of fracturing of a rock mass which can both
Soil                                                        lower and increase the overall rock strength. The
Soil is typically described by the components that          strength of rock is broken down as follows:
make it up by percentage or whichever has a                 Very Low Strength (VLS)              < 2 MPa (UCS)
governing behaviour. The types and sizes reproduced         Low Strength (LS)                    2 to 6 MPa (UCS)
from AS1726 are:                                            Medium Strength (MS)                 6 to 20 MPa (UCS)
Boulder >200 mm                                             High Strength (HS)                   20 to 60 MPa (UCS)
Cobble 63 to 200 mm                                         Very High Strength (VHS)             60 to 200 MPa (UCS)
Gravel 2.36 to 63 mm                                        Extremely High Strength (EHS)        > 200 MPa (UCS)
Sand    0.075 to 2.36 mm                                    Very Low Strength (VLS)              < 0.1 Is(50)
Silty   0.002 to 0.075 mm                                   Low Strength (LS)                    0.1 to 0.3 Is(50)
Clay    < 0.002 mm                                          Medium Strength (MS)                 0.30 to 1.0 Is(50)
The strength of soil is usually assessed by suitably        High Strength (HS)                   1.0 to 3.0 Is(50)
experienced persons through the use of laboratory           Very High Strength (VHS)             3.0 to 10.0 Is(50)
test results, published literature, field assessments or    Extremely High Strength (EHS)        > 10.0 Is(50)
a combination of the above. The strength of soil is         The Is(50) values are based on a correlation between
characterised into either cohesive (clays and silts) or     the unconfined compressive strength (UCS) of 20.
cohesionless (sands and gravels) as shown below:            This value varies significantly and site specific testing
Cohessive Soil Strength Term                                must take precedence.

Very Soft            < 12.5 kPa                             Rock weathering is broken down as follows:
Soft                 12.5 to 25 kPa                         Extremely weathered (EW) Behaves as soil but rock structure
Firm                 25 to 50 kPa                                  evident
Stiff                50 to 100 kPa                          Highly weathered (HW) Colour and strength of original fresh rock
                                                                    is not recognisable. Decomposition of rock evident
Very Stiff           100 to 200 kPa
                                                            Moderately weathered (MW)    Defects are heavily stained with
Hard                 > 200 kPa
                                                                   rock mass showing signs of discolouration
Cohesionless Soils Strength Term (uncorrected Qc)           Slightly weathered (SW)     Some staining but minimal to no
Very Loose           <2 MPa                                          change in strength

Loose                2 to 5 MPa                             Fresh stained       (FS) Minor staining evident

Medium Dense         5 to 15 MPa                            Fresh rock          (FR) No change

Dense                15 to 25 MPa                           Rock fracturing is broken down as follows and can only
Very Dense           > 25 MPa                               be accurately described where undamaged
                                                            continuous sampling has been undertaken:
                                                            Fragmented (Fg)      Defect spacings < 20 mm
Rock
                                                            Highly Fractured (HF)    Defect spacings 20 to 50 mm
Rock is typically described by the components that          Fractured (Fr) Defect spacings 50 to 200 mm
make it up by percentage or whichever has a                 Slightly Fractured (SF) Defect spacings 200 to 1000 mm
governing behaviour. The strength of rock is typically      Unbroken (Ub) Defect spacings > 1000 mm




Sunshine Coast | Brisbane | Gold Coast

Page 8

                                                          ABN 51 640 311 842
                                                          arcosgroup.com.au
                                         Sunshine Coast | Brisbane | Gold Coast




Sunshine Coast | Brisbane | Gold Coast

Page 9

                                                          ABN 51 640 311 842
                                                          arcosgroup.com.au
                                         Sunshine Coast | Brisbane | Gold Coast




Sunshine Coast | Brisbane | Gold Coast

Page 10

                                                          ABN 51 640 311 842
                                                          arcosgroup.com.au
                                         Sunshine Coast | Brisbane | Gold Coast




Sunshine Coast | Brisbane | Gold Coast

Page 11

                                                          ABN 51 640 311 842
                                                          arcosgroup.com.au
                                         Sunshine Coast | Brisbane | Gold Coast




Sunshine Coast | Brisbane | Gold Coast

Page 12

                                                                                         QBCC #:15288478
                                                                                         PH: 07 54 740 900
                                                                        3/53 Gateway Drive, Noosaville 4566
                                                                               [email protected]




 JOB NUMBER              23-0572 SITE CLASSIFICATION REPORT
 CLIENT                  Darran Taylor Building
 SITE LOCATION           PROPOSED SECONDARY RESIDENCE.
                         70 Blanckensee Road, Black Mountain QLD, Australia
 REPORT DATE             25/05/2023


1. INTRODUCTION
The purpose of this report is to classify the subject allotment in accordance with Australian Standard
2870 - 2011 'Residential Slabs and Footings'. From this classification, a footing system can be recom-
mended for the structure so as to allow adequate performance of the footings under the soil conditions
determined at the site.
Trees: There are small (<5m), medium (5-10m), and large (>10m) trees at this site. Global Testing
recommends an experienced arborist be commissioned to quantify the existing size, location, pre-
dicted maximum height and type of these trees to aid in the design process. It is the responsibility of
the designing engineer to apply the principals of AS2870-2011 Appendix H 'Guide to Design of Foot-
ings for Trees'. The classification herein excludes the effect of trees on the site.


2. SITE DESCRIPTION
 Type of Allotment                                                   Acreage
 Vegetation                                   Grassed/Scattered Undergrowth/Trees/Existing Dwellings
 Slope                                                            5-20% to North
 Surface Water will Drain Towards                                     North
 Will Surface Water from adjoining                                     No
 allotments traverse this site?
 Surrounding Allotments
                                 Left                                   Rural
                                Right                                   Rural
                                Rear                                    Rural
 Depth to Weathered Rock                                         BH1 (N/a), BH2 (N/a)
 Depth to Water Table                                            BH1 (N/a), BH2 (N/a)


3. SITE CLASSIFICATION AND TARGET STRATA
Based on the findings of the site investigation, the classification of the site is considered to conform to:

   CLASS “P” – (Due to Uncontrolled Fill and the Presence of Trees - See
                           Target Stratum)
    PLEASE NOTE: If not for the above reasons, this site would have the characteristics of a Class M Site.

in accordance with Australian Standard 2870 - 2011, 'Residential Slabs and Footings, Construction'.

The target stratum for the foundation of the structure located at BH1 is SANDY CLAY
encountered at 500 mm below existing ground level.
The target stratum for the foundation of the structure located at BH2 is SANDY CLAY
encountered at 500 mm below existing ground level.

       Page | 1 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                             23-0572

Page 13

                                                                                       QBCC #:15288478
                                                                                       PH: 07 54 740 900
                                                                      3/53 Gateway Drive, Noosaville 4566
                                                                             [email protected]


PLEASE NOTE: This report does not address slope stability. If a slope stability analysis is re-
quired, the services of a suitably qualified geotechnical engineer should be sought. We can rec-
ommend one or organise this service on your behalf.
It is the designing engineer’s responsibility to address the potential influence of any trees present
on or around the proposed building site.

If any further fill is placed over the existing ground, the structure shall be piered through the fill
into the existing material. Further note that the placement of reactive material as fill, or cutting
of the site may change the site’s classification.


4. SOIL PROFILE
Refer to Soil Profile Report for borelog information.
Whilst every effort has been made to ensure that the borelogs carried out at the subject allotment are
indicative of the soil profile over the site any discrepancy between the profile detailed in the borelogs
and that observed during construction shall be referred to Global Testing for immediate attention.


5. MATERIALS LABORATORY TEST RESULTS
Soil Laboratory testing carried out on samples of the soil taken from the site gave the following results:
                    BOREHOLE                                                 BH1
                    DEPTH RANGE OF SAMPLE                                900-1100 mm
                    LIQUID LIMIT (%)                                          N/a
                    PLASTIC LIMIT (%)                                         N/a
                    PLASTIC INDEX (%)                                         N/a
                    LINEAR SHRINKAGE (%)                                      N/a
                    INSTABILITY INDEX (%)                                     N/a
                    SHRINK SWELL INDEX, Iss (%)                               3.6
                    PREDICTED SURFACE MOVEMENT                            30-40 mm


Please note that the Plasticity Index (PI) determined by the Atterberg Test may be correlated to an
Instability Index (Ips)with reference to the results of extensive testing carried out by others, notably, Dr
P Mitchell, ‘Footings for Small Scale Domestic Structures,’ March 1990.
 Yours Sincerely,




 (Luke Wade - Office Manager)




       Page | 2 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                             23-0572

Page 14

                                                                                        QBCC #:15288478
                                                                                        PH: 07 54 740 900
                                                                       3/53 Gateway Drive, Noosaville 4566
                                                                              [email protected]


                                               LIMITATIONS

Recommendations given in this report are based on the information supplied by the client regarding the
proposed building construction in conjunction with the findings of the investigation. Any change in
construction type, building location or omission in the client supplied information, may require addi-
tional testing and/or make the recommendations invalid.


The recommendations herein identify a target soil stratum into which the footings are to be founded.
The target stratum has been located by the depth in mm of the target stratum's upper horizon boundary
below the existing ground surface level at the time of the site investigation. Any cutting or filling works
and any surface erosion or deposits subsequent to the site investigation, will alter the measured location
of the stratum relative to the surface. Where required, the author should be notified in such cases to
confirm the location of the target stratum.


The description of the soil given in the Soil Profile section of this report is intended as a brief overview
of the soil's primary constituents. For a detailed classification of the soil, the reader should refer to the
Soil Profile Reports and/or Borehole Reports attached to this report.

Every reasonable effort has been made to locate the test sites so that the borehole profiles are repre-
sentative of the soil conditions within the area investigated. The client should be made aware however,
that exploration is limited by time available and economic restraints. In some cases, soil conditions can
change dramatically over short distances, therefore, even careful exploration programs may not locate
all the variations.

If soil conditions different from those shown in this report are encountered or are inferred from other
sources, then the author must be notified immediately.

This report may not be reproduced except in full. The information and drawings provided with this
report shall only be used and will only be applicable for the development shown on the client supplied
information provided for this site.

Any dimensions, contours, slope directions and magnitudes shown on the Test Locality Plan shall not
be used for any building construction or costing calculations. The purpose of the plan is to show ap-
proximate location of field tests only.

Any changes made to these recommendations by persons unauthorised by the author will legally be
interpreted as that person assuming the responsibility for the long-term performance of the footing sys-
tem.

The recommendations contained in this report have not taken into consideration the long-term effects
of any previous, current or potential subsurface work by mining companies or potential slope instability
problems. At the time of writing this report neither our client (nor his agent) nor the local authority had
made the author aware that these problems may be affecting this allotment. If a mining subsidence or
slope stability assessment is required for this allotment, the recommendations of a suitably qualified
geotechnical engineer should be sought.



       Page | 3 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                             23-0572

Page 15

                                                                                QBCC #:15288478
                                                                                PH: 07 54 740 900
                                                               3/53 Gateway Drive, Noosaville 4566
                                                                      [email protected]


SOIL PROFILE REPORT
CLIENT:      Darran Taylor Building            AUTHORISED            Darran Taylor Building
                                               BY:
PROJECT:     70 Blanckensee Road, Black        DATE TESTED:          23/05/2023
             Mountain QLD, Australia           JOB NO:               23-0572


                 Drilling Method: Jacro 105 100mm.                                      Borehole
                                                                                          No.1
  Depth       Description                                           PENET.             Est. Bearing
                                                               (blows per 100mm)
  (mm)                                                                                  Capacity
                                                                1      2    3      4       (kPa)
    0         (FILL) CLAYEY SAND (SC)-Fine to
              coarse, brown-grey, low plasticity clay, trace
              of gravel, moist, medium dense
   100                                                          3                          110
   200                                                          5
   300                                                          3
   400                                                          5
   500        SANDY CLAY (CH)-High plasticity, grey,            2                          100
              fine to medium sand, moist, firm to stiff
   600                                                          2
   700                                                          2
   800                                                          4
   900        SILTY CLAY (CH)-High plasticity, pale             4                          125
              grey, low plasticity fines, moist, stiff
   1000                                                         4
   1100                                                         4
   1200                                                         4
   1300                                                         4
   1400                                                         8                          150
   1500                                                        10
   1600                                                        10
   1700                                                        10
   1800                                                        12
   1900                                                        11
   2000       SILTY CLAY (CH)-High plasticity, brown,          12                          150
              low plasticity fines, moist, hard
   2100                                                        12
   2200                                                        12
   2300                                                        15
   2400                                                        15
   2500                                                        15                          150
   2600
   2700
   2800
   2900
   3000
   3100
   3200

    Page | 4 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                          23-0572

Page 16

                                                                           QBCC #:15288478
                                                                           PH: 07 54 740 900
                                                          3/53 Gateway Drive, Noosaville 4566
                                                                 [email protected]


3300
3400
3500
3600
3700
3800
3900
4000




 Page | 5 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                       23-0572

Page 17

                                                                                QBCC #:15288478
                                                                                PH: 07 54 740 900
                                                               3/53 Gateway Drive, Noosaville 4566
                                                                      [email protected]




SOIL PROFILE REPORT
CLIENT:      Darran Taylor Building           AUTHORISED           Darran Taylor Building
                                              BY:
PROJECT:     70 Blanckensee Road,             DATE TESTED:         23/05/2023
             Black Mountain QLD, Aus-         JOB NO:              23-0572
             tralia


                 Drilling Method: Jacro 105 100mm.                                      Borehole
                                                                                          No.2
  Depth       Description                                          PENET.              Est. Bearing
                                                               (blows per 100mm)
  (mm)                                                                                  Capacity
                                                               1     2      3      4       (kPa)
    0         (FILL) CLAYEY SAND (SC)-Fine to
              coarse, brown-grey, low plasticity clay, trace
              of gravel, moist, medium dense
   100                                                               2                     100
   200                                                               3
   300                                                               3
   400                                                               3
   500        SANDY CLAY (CH)-High plasticity, grey,                 3                     110
              fine to medium sand, moist, firm to stiff
   600                                                               3
   700                                                               4
   800        SILTY CLAY (CH)-High plasticity, pale                  5                     150
              grey, low plasticity fines, moist, stiff
   900                                                               5
   1000                                                              6
   1100                                                              5
   1200                                                              5
   1300                                                              8
   1400                                                              8
   1500       SILTY CLAY (CH)-High plasticity, brown,                8                     150
              low plasticity fines, moist, hard
   1600                                                              8
   1700                                                             10
   1800                                                             10
   1900                                                             10
   2000                                                             10                     150
   2100                                                             12
   2200                                                             12
   2300                                                             12
   2400                                                             15
   2500                                                             15                     150
   2600
   2700
   2800
   2900

    Page | 6 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                          23-0572

Page 18

                                                                           QBCC #:15288478
                                                                           PH: 07 54 740 900
                                                          3/53 Gateway Drive, Noosaville 4566
                                                                 [email protected]


3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000       Borehole Terminated




 Page | 7 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                       23-0572

Page 19

                                                                          QBCC #:15288478
                                                                          PH: 07 54 740 900
                                                         3/53 Gateway Drive, Noosaville 4566
                                                                [email protected]




   Site- 70 Blanckensee Road, Black Mountain QLD, Australia




Page | 8 Borelogging in accordance with AS1726-2017 Geotechnical Site Investigations
                                      23-0572

Page 20

                                                                                                                                                                     N
                                                                                                       10% SLOPE

                                                                 20% SLOPE                                                5% SLOPE




                                                                                                   S
                                                                                                 UR
                                                                                                            PROPOSED




                                                                                               CO
                                                                                                            SECONDARY




                                                                                             ER
                                                                                                            RESIDENCE




                                                                                      AT


                                                                                       12000
                                                                                   W
                                                                                                              15000




                                                                                 NT
                                                                              TE
                                                                            IT
                                                                                                                                                                                    SATELLITE IMAGERY
                                                                                                            BH1




                                                                          RM
                                                                         TE




                                                                                                                   8000
                                                                                                            PN1




                                                                       IN
                                                                                                                                                                                     LEGEND




                                                                                                                                            OURS
                                                                                           BH2
                                                                                           PN2                                                                                             BHx = BOREHOLE




                                                                                                                                                       IN
                                                                                                                                        TERC
                                                                                                                                                                                           LOCATION




                                                                                                                                                   UNTA
                                                                                                                                                                                           PNx = DYNAMIC CONE




                                                                                                                                    T WA
                                                                                                   4000                                                                                    PENETROMETER LOCATION




                                                                                                                               ITTEN
                                                                                                                                                                                           TREES




                                                                                                                                                 K MO
                                                                                                                                 M
                                                                                                                            INTER
                                                               EXISTING
                                           EXISTING           RESIDENCE




                                                                                                                                             BLAC
                                          WATERTANK




                                                                          EXIST
                                                                               ING D
                                                                                           RIVEW
                                                                                                       AY
                                                                   EXISTING
                                                                   GARAGE




SITE PLAN
SCALE:   1 : 500

                                                      CLIENT DETAILS                            PROJECT DETAILS                                     DRAWING TITLE                                       JOB No.     23/0572
                   SITE CLASSIFICATION
                   EFFLUENT DESIGN
                   SOUTH EAST QLD                     DARRAN TAYLOR BUILDING                    LOT 1, 70 BLANCKENSEE ROAD,                         TEST LOCATION PLAN                                  DRG No.      301
                   [email protected]
                                                                                                BLACK MOUNTAIN, QLD                                                                                                   1
                                                                                                                                                    DRAWN: CA   DATE: 24/05/2023   SCALE:As indicated@A3 REVISION

Page 21

                                                                                                                                                                                                                                                                                                        LEGEND

                                                                                                                                                                                                                                                                                                                   BHx = BOREHOLE LOCATION


                                                                                                                                                                                                                                                                                                                   PNx = DYNAMIC CONE
                                                                                                                                                                                                                                                                                                                   PENETROMETER LOCATION
                                                                                                                                                                                                                    10% SLOPE
                                                                                                                                                20% SLOPE                                                                                                                                                          PTx = PERCOLATION TEST
                                                                                                                                                                                                                                       5% SLOPE




                                                                                                                                                                                                                                                                OURS
                     INDICATIVE BOUNDARY LINE                                                                                                                                                                                                                                                                      =TREES




                                                                                                                                                                                          S
                                                                                                                                                                                        UR




                                                                                                                                                                                                                                                           TERC
                                                                                                                                                                                                                                                                                                        IMPORTANT DIRECTION




                                                                                                                                                                              CO
                                                                                                                                                                                                                                                                                                        DO NOT INSTALL FROM THIS DESIGN UNTIL IT IS




                                                                                                                                                                            ER
                                                                                                                                                                                                                                  BH 1                                                                  STAMPED AND APPROVED BY THE LOCAL




                                                                                                                                                                                                                                                                A
                                                                                                                                                                      AT
                                                                                                                                                                                                                                  PN 1                                                                  AUTHORITY.




                                                                                                                                                                                                                                                          ENT W




                                                                                                                                                                                                                                                                                   NORTH
                                                                                                                                                                                                                                                                                                        COUNCIL MAY MAKE CHANGES TO THIS DESIGN




                                                                                                                                                                      W
                                                                                                                                                                                                                                                                                                        AS PART OF THE APPROVAL PROCESS. ONLY




                                                                                                                                                              T
                                                                                                                                                            EN
                                                                                                                                                                                                                                                                                                        INSTALL FROM THE STAMPED POSSIBLE
                                                                                                                                                                                                  BH 1                                                                                                  CHANGES.




                                                                                                                                                                                                                                                     MITT
                                                                                                                                                            T
                                                                                                                                                                                                  PN 1




                                                                                                                                                         IT
                                                                                                                                                       RM
                                                                                                                                                                                          PROPOSED




                                                                                                                                                                                                                                                INTER
                                                                                                                                                     TE
                                                                                                                                                                                          SEDONDARY




                                                                                                                                                   IN
                                                                                                                                                                                           DWELLING
                                                                                                                                                                                         BH 2
                                                                                                                                                                                         PN 2




                                                                                                                                                                      AWAY FROM HOUSE
                                                                                                                                                                                                                                                       ADVANCED SECONDARY ASTP

                                                                                                                                                                                                                                                       TO BE INSTALLED IN A SUITABLE LOCATION




                                                                                                                                                                            15000
                                                                                                                                                                                                                                                       BY THE INSTALLING PLUMBER NOT ADJACENT
                                                                                                                                                                                                                                                       TO LIVING ROOMS OR BEDROOMS (TO BE
                                                                                                                                                                                                                               10000                   INSTALLED)
                                                                                                                                                                                                              BH 3         5000
                                                                                                                                                                                                              PT 1
                                                                                                                                                                                                                                                COVERED SURFACE DRIP IRRIGATION
                                                                                                                                                                                                                                                AREA = 80M2 TO BE INSTALLED




                                                                                                                                                                      10000
                                                                                                                                                                                          BH 4
                                                                                                                                              EXISTING                                    PT 2                                                  PEGGED TO THE GROUND NETAFIM OR
                                                                                                                                             RESIDENCE                                                                                          WASTEFLOW PRESSURE
                                                                                                              EXISTING                                                                                                                          COMPENSATING DRIPPER LINES (TO BE
                                                                                                             WATERTANK                                                                                      BH 5                                INSTALLED)
                                                                                                                                                                                                            PT 3
                                                                                                                                                                                                                                                8 PRESSURE COMPENSATING
                                                                                                                                                                                                RESERVE AREA                                    DRIPPER LINES (TO BE INSTALLED)
                                                                                                                                                         FLUSH OUT VALVE

                                                                                                                                                  EXISTING
                                                                                                                                                  GARAGE




                                                                                                                                                                                                                                          BIRD PROOF MESH TO BE
                                                                                                                                                                                                                                          PLACED ON SURFACE OF MULCH
                                                                                                                                                                                                                                          AND PEGGED TO THE GROUND
                                                                                                                                                                                                                                                                                                   SURFACE TO BE PLANTED OUT
                                                                                                                                                                                                                                                                                                   WITH A MINIMUM OF 8 PLANTS

                                                                                                                                                                                                                                                                       1000 MAX CENTRES                    300 HIGH MOUND SURROUND




                                                                                                                                                                                                                     150
                                                                                                                                                                                            150MM COVER
                                                                                                                                                                                            MULCH

                                                                                                                                                                                                                                                                           PEGGED TO THE GROUND NETAFIM OR WASTEFLOW
                                                                                                                                                                                                                                                                           PRESSURE COMPENSATING DRIPPER LINES. PLACE
                                                                                                                                                                                                                                                                           ON SURFACE AND COVER WITH 150MM MULCH




                                                                                                                                                                                                    TYP CROSS SECTION COVERED SURFACE DRIP IRRIGATION SYSTEM



                                                           SITE CLASSIFICATION | EFFLUENT DESIGN  CLIENT DETAILS           PROJECT DETAILS               SITE INFORMATION                           DRAWING TITLE                                                                                           JOB No.         DRG No. REVISION
                                                           SUNSHINE COAST | BRISBANE | GOLD COAST
                                                                                                                                                         RPD:                   LOT 1 ON RP193199
                                                           [email protected]
                                                                                                           DARRAN TAYLOR   PROPOSED DWELLING
                                                                                                                                                                                                    SITE PLAN
                                                                                                                                                                                                                                                                                                        23/0572 154                         1
                                                           COPYRIGHT © All rights reserved, this work is                                                 POSTCODE:                           4563
                                                           copyright and cannot be reproduced or copied    BUILDING        LOT 1, 70 BLANCKENSEE ROAD,   SUBURB:                  BLACK MOUNTAIN
24/05/2023 FOR CONSTRUCTION                     CA   1
  DATE                        DESCRIPTION       BY   REV
                                                           in any form without prior consent
                                                                                                                           BLACK MOUNTAIN, QLD           AUTHORITY:         NOOSA SHIRE COUNCIL     DRAWN: CA        DESIGN: LW     CHECK: GB            DATE:      24/05/2023 SCALE: As indicated@A1

Page 22

                                                          ABN 51 640 311 842
                                                          arcosgroup.com.au
                                         Sunshine Coast | Brisbane | Gold Coast




   Contact Us

          07 5293 7648

          @arcosgroup

          [email protected]

          arcosgroup.com.au



Sunshine Coast | Brisbane | Gold Coast

Used in these records

About this file

File size
2.9 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

220241.01 - 70 Blanckensee Road, BLACK MOUNTAIN - SECONDARY DWELLING - Slope Stability Report.pdf · 2.9 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.