RFI - Klaus Vario Product Data
Electrical installation
Electrical installation diagram On-site facilities for operating element
Surface-mounted operating element
110
= =
6
Electrical specifications (services to be provided by the customer)
Nr. Quantity Designation Position Frequency
1 1 Power meter in the supply cable
Pre-fuse:
2 1 3x safety fuse 16 A (slow-blow) or
in the supply cable 1x per unit
Circuit breaker 3x 16 A (trip characteristic K or C)
Supply cable 5 x 2.5 mm² (3 PH+N+PE) with marked wires and
3 1 to master switch 1x per unit
protective earth
4 every 10 m Foundation earth connection Corner of the floor plate
Equipotential bonding in accordance with DIN EN 60204
5 1 1x per system
from foundation earth connection to system
6 2 Empty pipe EN 25 (M25)
Electrical specifications (KLAUS Multiparking scope of supply)
Nr. Designation
7 Lockable master switch
8 Supply cable 5 x 2.5 mm² (3 PH+N+PE) with marked wires and protective earth
9 Unit junction box
10 Control cable 3 x 0.75 mm² (PH+N+PE)
11 Control cable 7 x 1.5 mm² with marked wires and protective earth
12 Operating element
13 Control cable 5 x 1.5 mm² with marked wires and protective earth
14 Hydraulic unit 3.0 kW, three-phase current 230/400 V / 50 Hz
15 Control cable 5 x 1.5 mm² with marked wires and protective earth to next system
16 Chain monitoring
Product data SingleVario 2061 584.69.890-012 04/2023 English 10