SLAB BOTTOM REINFORCEMENT NOTES SLAB TOP REINFORCEMENT NOTES
• LAPS TO SLAB REINFORCEMENT TO BE AS PER TABLE ON • LAPS TO SLAB REINFORCEMENT TO BE AS PER TABLE ON
DRAWING S001 UNLESS NOTED OTHERWISE ON PLAN DRAWING S001 UNLESS NOTED OTHERWISE ON PLAN
• REINFORCEMENT IS TO BE DISPLACED AROUND • REINFORCEMENT IS TO BE DISPLACED AROUND
PENETRATIONS, NOT CUT. PROVIDE N16-200 INFILL BARS. PENETRATIONS, NOT CUT. PROVIDE N16-200 INFILL BARS.
• PROVIDE 1 N16x1500 LONG TRIMMER BAR AT ALL RE-ENTRANT • PROVIDE 1 N16x1500 LONG TRIMMER BAR AT ALL RE-
CORNERS. ENTRANT CORNERS.
• ALL DISTRIBUTION REINFORCEMENT TO BE N12-300 U.N.O. • ALL DISTRIBUTION REINFORCEMENT TO BE N12-300 U.N.O.
LAP LENGTH
300 TYP. REFER DRG. S001
N16-200
N16-200
LAP LENGTH 300 TYP.
REFER DRG. S001
SLAB BOTTOM REINF. SCHEMATIC SLAB TOP REINF. SCHEMATIC
BEAM BOTTOM REINFORCEMENT NOTES BEAM TOP REINFORCEMENT NOTES
N12-200
N12-200
• LAPS TO BEAM REINFORCEMENT TO BE AS PER TABLE ON • LAPS TO BEAM REINFORCEMENT TO BE AS PER TABLE ON
N12-200 DRAWING S001 UNLESS NOTED OTHERWISE ON PLAN DRAWING S001 UNLESS NOTED OTHERWISE ON PLAN N12-200
• FOR PENETRATIONS LESS THAN Ø100 LOCALLY DISPLACE • FOR PENETRATIONS LESS THAN Ø100 LOCALLY DISPLACE SIDE
SIDE FACE REINFORCEMENT AND PROVIDE 1 N16 x 600 FACE REINFORCEMENT AND PROVIDE 1 N16 x 600 LONG TO EACH
LONG TO EACH PENETRATION FACE AT EACH SIDE OF PENETRATION FACE AT EACH SIDE OF BEAM. PENETRATIONS
BEAM. PENETRATIONS LESS THAN Ø100 MAY NOT BE LESS THAN Ø100 MAY NOT BE SHOWN ON PLAN.
SHOWN ON PLAN. • ALL BEAMS TO HAVE N12 LIGS AT 300 CRS. UNLESS NOTED
• ALL BEAMS TO HAVE N12 LIGS AT 300 CRS. UNLESS NOTED OTHERWISE ON PLAN.
OTHERWISE ON PLAN.
LAP LENGTH
300 TYP. REFER DRG. S001
N16-200
N16-200
LAP LENGTH 300 TYP.
REFER DRG. S001
BEAM BOTTOM REINF. SCHEMATIC BEAM TOP REINF. SCHEMATIC
N16-200 N16-200
2 N20 TRIMMERS TOP
AND BOTTOM
300 TYPICAL U.N.O.
MIN.
LAY 1st & 4th
K1, K2 & K3 VILLA ROOF BOTTOM REINFORCEMENT PLAN SLAB REINFORCEMENT K1, K2 & K3 VILLA ROOF TOP REINFORCEMENT PLAN
MIN.
300
SCALE 1 : 50 COGGED AT PENETRATION. SCALE 1 : 50
LAY 2nd & 3rd
LAP LENGTH
LAYING SEQUENCE U.N.O. TYP.
BARS REQUIRED IN OTHER SEQUENCE
ARE TAGGED ON PLAN THUS:-
(1) LAID 1ST, (2) LAID 2ND
(3) LAID 3RD, (4) LAID 4TH
NOTE:
FOR PENETRATIONS LESS THAN 300 SQ. REINFORCEMENT
IS TO BE DISPLACED NOT CUT. PROVIDE N16-200 INFILL BARS.
TYPICAL SLAB PENETRATION DETAIL
SCALE 1:20
500mm 0 500 1000 1500 2000
INFORMATION
1 :50
NOT FOR CONSTRUCTION
Client Status Title
MARK BAIN INFORMATION
K1, K2 & K3 VILLA ROOF BOTTOM & TOP
Drawn By Designed By Approved By
JAL JM JO
REINFORCEMENT PLANS
Project No. Discipline Scale
[email protected] 20220173 STRUCTURAL As indicated (at A1)
Project Name
37 MARY ST NOOSAVILLE, QLD Drawing No. Revision
1 04.11.22 ISSUE FOR INFORMATION JAL JO NOOSA VILLAS
07 5211 1003 S131 1
Rev Date Description By Chk 10 NATASHA AVE & 24 KATHARINA ST, NOOSA HEADS QLD
FULL SIZE ON ORIGINAL 0 10 20 30 40 50 60 70 80 90 100 mm
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Structural Plans 20220173 - 10 Natasha Structural Issue 190123.pdfRelated documentApplication case desk ↗
About this file
- File size
- 10.3 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.