3 PROPOSED DEVELOPMENT
The proposed site layout for the shopping centre is shown in Figure 3. The development will
replace the Bowls Club. It will consist of an IGA Supermarket in the main building and speciality
shops to the south and east. At this stage, Renzo Tonin Ron Rumble has been informed by Multi
Span Australia Pty Ltd that the exact uses and tenancies for speciality shops are unknown.
The loading area and service for the supermarket will be located to the west of the building.
Delivery trucks will enter the loading area along a one-way driveway off Rufous Street to the
northwest (Entry A -
see Figure 3) and exit on Rufous Street to the southwest (Entry B). There is
a small service bay area located to the east. Vehicles accessing the small service bay area will
enter and exit the site via Entry B.
Access to the proposed carparking areas will be via Entry B. There are approximately 100
carparking spaces provided on the site.
As the exact uses and tenancies for the commercial buildings are unknown at this stage, the
locations, capacities and sizes of mechanical/building services plant could not be determined at
the time of this assessment.
Typical delivery times for deliveries at the centre have been obtained from the proposed IGA
operator who operates other IGA stores within the Sunshine Coast area (information obtained via
David Hood, Architect). The operator has stated that Heavy Rigid Vehicle (HRV)deliveries from
IGA warehouses would occur once a day, typically between Sam and noon on week days only.
HRV deliveries will not occur during evening and night periods (6pm to 7am).
To minimise potential noise nuisance, it is proposed to construct 2.5m and 3.5m high acoustic
barriers as shown in Figure 4. For the noise barriers to provide adequate noise reduction, they
are required to have a minimum superficial density of 14kg/m2 and a maximum leakage of 1%.
This may be achieved using materials such as concrete tilt panel, masonry block wall, 35mm thick
CCA treated lapped and capped timber palings or 75mm Hebel Power Panel. The northern end of
the barrier will consist of a solid and gap-free gate for ingress of service and delivery vehicles.
@ Renzo Tonin Ron Rumble Proposed Shopping Centre, Rufous Street, Peregian
Noise Impact Assessment
Q9554-01F02 (Rev 3) Peregian Shopping Centre.doc Multi Span Australia Group pty Ltd
5August 2013 Page 8
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Response to Information Request 5-7 Rufous Street Peregian Beach - Attachment D MCU13/0092Related documentApplication case desk ↗
About this file
- File size
- 23.1 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.