13. APP H. Engineering Services Report
Attached to the e-mail MCU14/0102 Development Application 4 of 4 App H Engineering, App I Water quality, App J Economic Needs, App K Local Code response..
Original PDF page 11, section 1. The text section number identifies this passage in the reader.
5 WATER AND SEWER SUPPLY (UNITY
WATER INFRASTRUCTURE)
5.1 Services Advice Notice
Hyder Consulting received a Services Advice Notice (SAN) regarding the servicing of the
proposed development for water and sewer services from Unity Water which states that the
existing infrastructure has sufficient capacity to service the proposed development. Refer to
Appendix E for the Notice.
5.2 Water Supply
5.2.1 Existing Water Supply Infrastructure
Unity Water DBYD maps indicate that there is a potable water reticulation main located within
the Lionel Donovan Drive and Eumundi Noose Road. Both pipes are 100mm diameter mains.
There are multiple hydrants and valves on the main. Lot 4SP159610 takes service from the
main in Eumundi Noosa Road and Lot 31SP170751 is intended to be serviced by the main in
Lionel Donovan Drive.
In the current Priority Infrastructure Plan (PIP), Noosa Council have not indicated any priority
water supply infrastructure works within the area surrounding the subject site.
For details of the surrounding water infrastructure refer to Unity Water DBYD results in
Appendix E.
5.2.2 Proposed Water Supply Infrastructure
It is proposed to maintain the existing water connections to the site on Eumundi Noosa Road
and Lionel Donovan Drive. Lot 4 SP159610 will maintain connection to the 100mm diameter
main on Eumundi Noosa Road, and Lot 31 SP170751 will maintain connection to the 100mm
diameter main on Lionel Donovan Drive.
Unity Water’s SAN also advises that it may be necessary to upgrade the existing water
reticulation main to 150mm diameter (including hydrants) along Eumundi Noosa Road to allow
for sufficient fire flow. Hyder Consulting considers this to be an unnecessary burden on the
proposed development as the intended purpose for the site is largely consistent with the
planning scheme.
Additionally, Lot 4SP170751 is already used for industrial purposes, and there will be an
decrease in demand on the water infrastructure in Eumundi Noosa Road due to the proposed
development. Table 5.1 compares the existing and developed case demand over Lot
4SP159610.
139 EUMUNDI-NOOSA ROAD & 30 LIONEL DONOVAN DRIVE, NOOSAVILLE
Hyder Consulting Pty Ltd-ABN 76 104 485 289 Page 6
f:\aa007595\f-reports\f0001-aar-aa007595 esr report\f0001-aa007595-aar-03 - esr.docx