Original source · versioned page text
2016-02-02 P&O Committee - Item 3 - Attachment 3 - Noosa River Environmental Values and Water Quality Objectives
Noosa River environmental values and water quality objectives
Table 13 Drinking water EV: Priority water quality objectives for drinking water supply in the vicinity
of off-takes, including groundwater, before treatment
Indicator Water quality objectives
Hardness 60-200 mg/L (as CaCO3) Refer ADWG (treated water guideline)
Taste and odour 5 µg/L Geosmin or 10 µg/L MIB or 10 µg/L combined Geosmin & MIB
Cyanotoxins (specific Saxitoxin 3 µg/L (ADWG health alert value for acute exposure; and
assessment of SEQWater Toxic Cyanobacteria Risk Assessment 2006)
treatment step
efficiencies for each Mycrocystin 1.3 µg/L (ADWG treated water guideline)
toxin is required)
Cylindrospermopsin 1 µg/L
Cryptosporidium 0 oocyst
Giardia 0 cyst
E. coli 100 cfu/100mL
(ensure sufficient turbidity reduction and chlorine contact:dose)
Manganese (soluble) 50 µg/L
Iron (soluble) 50 µg/L
Turbidity 25 NTU for WTP designed for offtakes from open water storages
50 NTU for WTP designed for offtakes in riverine (weir) systems
Colour 50 Hazen Units
Conductivity/TDS See ADWG (no treatment options to remove salt) 500 mg/L TDS. Site
specific conversion to conductivity required. ADWG recommends
average multiplication factor of 2 to derive conductivity (µs/cm):
1000 µs/cm
Dissolved oxygen 4 mg/L at water surface
Pesticides Presence at detectable levels (detection limits specified by Qld Health
Scientific Services)
Dissolved Organic 10 mg/L
Carbon
Source: Queensland Bulk Water Supply Authority Trading as: Seqwater