Electrical Reticuation Plans A251400a
Plans and drawings: the text below has words only, no drawings.
LEGEND GENERAL NOTES
1. NO OTHER SERVICES TO ENCROACH INTO THE STANDARD UNDERGROUND
EXISTING
ELECTRICITY CORRIDOR.
OVERHEAD CABLE
2. ALL CABLES TO BE INSTALLED IN CONDUIT WITHIN THE STANDARD
ELECTRICITY ALIGNMENT ALLOCATED BY THE LOCAL COUNCIL. WHERE
PROPOSED CONDUITS VARY FROM THIS AND AT FOOTPATH CROSSING PROTECTIVE
OVERHEAD CABLE STRIP IS TO BE INSTALLED. WHERE PRACTICAL ELECTRICITY CABLES
SHALL NOT BE CLOSER THAN 250mm TO THE REAL PROPERTY BOUNDARY.
EXISTING
UNDERGROUND 3. A, B OR C WHEN SHOWN BESIDE LV PILLARS DENOTES SERVICE PHASING.
CABLE
4. THE CONTRACTOR SHALL MEASURE ACTUAL CABLE LENGTHS REQUIRED
ON SITE AFTER INSTALLATION OF CONDUITS THEN NOTIFY
PROPOSED ENERGEX/SUPPLIER WHEN CONFIRMING CABLE ORDER.
UNDERGROUND
CABLE
5. ALL BENDS INSTALLED ON 80mm,100mm AND 125mm RETICULATION
E CONDUITS MUST BE 1830mm RADIUS UNLESS OTHERWISE SPECIFIED.
PROPOSED
ELECTRICAL 6. CONTRACTOR TO SUPPLY ALL LABELS AND SITE ID NUMBERS TO ENERGEX
SERVICE CONDUIT
SPECIFICATION.
ET
PROPOSED 7. WHEN CROSS ROAD CONDUIT FINISHES OPPOSITE A TRUNCATION PEG,
ELECTRICAL & PROPERTY SIDE OF TRENCH TO BE 300mm ALIGNMENT FROM PEG.
COMMUNICATION
SERVICE CONDUITS 8. WHERE CROSS-ROAD ELECTRICITY CONDUITS RUN PARALLEL TO OTHER
SERVICES OR CONDUITS, A MINIMUM SEPARATION OF 1.0m MUST BE
DEVELOPERS NOTES MAINTAINED.
POLE 1. DO NOT CONSTRUCT DRIVEWAYS /
TRANSFORMER CROSSOVERS UNTIL ELECTRICAL 9. CIVIL CONTRACTOR TO INSTALL ALL CROSS ROAD CONDUITS FOR NEW
WORKS HAVE BEEN COMPLETED. ROADS, ELECTRICAL CONTRACTOR TO INSTALL ALL CROSS ROAD
CONDUITS REQUIRING EITHER ROAD BORING OR CUT & REINSTATEMENT
PADMOUNT
Lot 45 OF ROADWAY, UNLESS OTHERWISE NOTED ON THE WORKS PLANS.
TRANSFORMER RP136461
#19 10. CO-ORDINATE CONDUIT INSTALLATION WITH COMMUNICATIONS CARRIER
CONTRACTORS.
HV POLE 11. ELECTRICITY PILLARS TO HAVE 600mm EXCLUSION ZONE. NO
NON-ENERGEX ASSETS TO BE INSTALLED WITHIN THIS EXCLUSION ZONE.
HV / LV POLE SEQ WATER REQUIRE 1.1m CLEARANCE BETWEEN 12. ENERGEX REQUIRE 1.0m CLEARANCE BETWEEN SERVICE PILLARS AND
DRIVEWAYS. IF LESS THAN 1.0m SEPARATION THEN PROTECTIVE
ELECTRICAL PILLARS AND WATER METERS. INSTALL
BOLLARDS MUST BE INSTALLED. DEVELOPMENTS WITH ONE OR MORE
WATER METERS MINIMUM 1.5m FROM BOUNDARY PEG SEPARATE BUILDINGS SHARING A COMMON SLAB OR STRUCTURE &
LV POLE Lot 44 WHERE WATER METERS SHARE A COMMON BOUNDARY CONSTRUCTED ACROSS MULTIPLE FREEHOLD LOTS (E.G. UNITS,
RP136461
Lot 21 WITH ELECTRICAL PILLARS. TOWNHOUSES) IS TO COMPLY WITH ENERGEX OPERATIONAL UPDATE
#17 C0078 (REVISED) - FREEHOLD LOTS WITH ABUTTING STRUCTURES
SP236315
HV UNDERGROUND Lot 101 (TERRACE HOUSING).
#20
POLE TERMINATION SP191688
#15 14. AS/NZS3000 CONSUMERS CONDUIT LOCATED WITHIN THE PUBLIC
FOOTPATH MUST BE INSTALLED BY AN ELECTRICAL CONTRACTOR. THE
LV UNDERGROUND CONSUMERS CONDUIT MUST BE 50mm DIA OR LARGER, HEAVY DUTY, HAVE
POLE TERMINATION RIPARIAN ZONE 2 A MINIMUM OF 600mm OF COVER, AND MUST BE PROTECTED BY PVC
COVENANT AREA C RIPARIAN ZONE 1 MATERIALS SUMMARY - S2603254 COVER STRIP.
COVENANT AREA B
AERIAL STAY UNDERGROUND CONSTRUCTION CONTRACTOR
MODEL No QTY MODEL No QTY
THE CONTRACTOR SHALL BE RATED BY ENERGEX FOR THE FOLLOWING
Lot 82
GROUND STAY
WORK AREA RP136461
LVSP12-6
TRENCHING
1
117m
LVC416XPV
DRIVEWAY BORE
51m
7m
PROCESS.
WCS 2-CW - UNDERGROUND CONSTRUCTION - CONTESTABLE WORKS
#18
Cancelling Lot 43 on RP136461 OVERHEAD WCS 25-CW - OVERHEAD MAINS ELECTRICAL CONSTRUCTION -
RES
CONTESTABLE WORKS
MODEL No QTY MODEL No QTY
PT FUSE WCS 31 - COMMISSIONING AND OPERATION OF THE NETWORK
LVBR16/AOH 1 LVT4C16 1
MA C
WCS 34 - EARTHING SYSTEMS
URD CONTRACTOR SHALL NOTE THAT THIS SUMMARY SHEET MUST NOT BE USED FOR
DISC LINK TENDER PURPOSES. THE CONTRACTOR SHALL CHECK QUANTITIES AGAINST ACTUAL STANDARDS AND SPECIFICATIONS
JIRRI
OPEN SCHEDULES ON THESE DRAWINGS.
THIS WORKS PLAN IS TO BE READ IN CONJUNCTION AND COMPLY WITH THE
FOLLOWING ENERGEX MANUALS AND SPECIFICATIONS
DISC LINK
Lot 100 Lot 83
CLOSED Lot 11 · OVERHEAD CONSTRUCTION MANUAL
SP156380 RP136461
SP156380 · OVERHEAD DESIGN MANUAL
#13 #16
#13 · UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
CUTOUTS Lot 10 · WCS 61.1 - UNDERGROUND TRENCHLESS TECHNOLOGY
ENERGEX APPROVED ENSAR
OPEN
SP156380 · NETWORK LABELLING AND SIGNAGE MANUAL
#11
CONSUMER'S INSTALLATION SHALL COMPLY WITH AS/NZS 3000:2018 - SAA
CUTOUTS WIRING RULES, THE QECM & THE QEMM.
CLOSED
FILE: C:\USERS\LENNIN.SANTOS\ONEDRIVE - AMPFLO PTY LTD\DESKTOP\AMPFLO FOLDER\PROJECTS\1. ONGOING PROJECTS\251400 - 15 JIRRIMA CRS COOROIBAH\A251400A
FOR DETAILS OF TRENCH CROSS-SECTIONS, REFER TO ENERGEX
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL.
EARTH
Lot 2
SP179878
Lot 5 EXCEED VOLTAGE DROP (SP6009-C/DLL1) ON SITE SERVICES CHECKS
SP156930
EXISTING PILLAR
#11 #14 UNDERGROUND SERVICES SHOWN ON THIS WORKS PLAN IN THE VICINITY OF
Lot 1 PROPOSED EXCAVATION WORKS HAVE BEEN TAKEN FROM ASSET OWNER'S
SP179878 PAPER RECORDS AND ARE INDICATIVE ONLY.
PROPOSED PILLAR
#11
A. BALLANTYNE 25.03.2026 THE CONTRACTOR IS RESPONSIBLE FOR THE REPAIR OF DAMAGE TO ANY
EXISTING UNDERGROUND ASSETS CAUSED BY HIS WORKS AND THE
Lot 12 RE-ESTABLISHMENT OF ANY SURVEY MARKS DISLODGED.
Emt ASP179878 SP266741
LINK PILLAR THE CONTRACTOR SHALL REQUEST ON-SITE IDENTIFICATION AND LOCATION
#12
240LV OF EXISTING BURIED SERVICES FROM THE "BEFORE YOU DIG AUSTRALIA"
SERVICE - www.byda.com.au (A MINIMUM OF TWO DAYS NOTICE IS REQUIRED)
D
CONDUIT / CABLE LOCALITY PLAN SEWERAGE, STORMWATER, GAS AND WATER PLANS FOR THE SITE MAY BE
CROSS-SECTION OBTAINED ON REQUEST FROM THE PROJECT SERVICE SUPERVISOR.
SCALE N.T.S
X
WATER METER REINSTATEMENT NOTES
BACKFILL & REINSTATEMENT OF FOOTPATH AND ROADWAY TO NOOSA SHIRE
PROPOSED
DRIVEWAY ENTRY COUNCIL REQUIREMENTS. REFER STANDARD DRAWINGS:
- RS-056 - RURAL DRIVEWAY
PROPOSED ZERO - RS065 - CONCRETE PATHWAY CONSTRUCTION DETAILS
LOT IDENTIFIER - RS170 - PAVEMENT TRENCHING AND WIDENING
LIGHTING
LEGEND
LED STREET
LIGHT
FOR APPROVAL
EXISTING UNKNOWN (NOT FOR CONSTRUCTION)
STREET LIGHT
NOTE: NOT ALL 15/04/2026 10:51 am
SYMBOLS MAY BE
USED
S2603254
This document is CLIENT SITE CONTACT DETAILS ALIGNMENTS PROJECT / CERTIFICATION: PROJECT
the property of NAME ENERGEX OH 3.0 SUB PROJECT NO. APPROVED: Ivan Lubacheski 2 LOT RESIDENTIAL SUBDIVISION
RPEQ No: 20070
Ampflo Pty Ltd RHIANA MAGEE ENERGEX UG 0 - 0.9 PARENT PROJECT NO. - DATE: 16/04/2026 15 JIRRIMA CRES, COOROIBAH
and may only be COMPANY TELSTRA BYDA WORK REQUEST NO. - LOCALITY PLAN
PLOT: 15/04/2026 10:51:33 am
used for the ABN 28 111 423 842
purpose for RHIANA MAGEE - GAS BYDA PLANNER & PHONE -
Electrical and Telecommunications
LEGEND, NOTES, MATERIALS SUMMARY
which it was PHONE - HP GAS BYDA LOTS 1&2 Consultants CHECKED: R. YUMUL & ENSAR
commissioned. MOBILE 0419 132 841 WATER BYDA CANCELLING LOTS 43 ON RP136461 ISO 9 0 0 1
Phone : (07) 3372 9280 ISSUE
CERTIFIED DESIGNER: L. SANTOS DRAWING: A251400
A
Unauthorised A 15/04/2026 ISSUED FOR APPROVAL LS RY IL EMAIL [email protected] STORMWATER BYDA LOCAL AUTHORITY NOOSA SHIRE COUNCIL Email : [email protected]
use is prohibited. REV DATE DETAILS DRAWN CHECKED APPRVD SEWERAGE BYDA PEGGED? ON REQUEST
Q U A L I T Y
MANAGEMENT
Website : ampflo.com.au ISSUE DATE: 15/04/2026 PROJECT: 251400 SHEET 01 OF 03 A1
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 2 pages
Page 2
LEGEND
EXISTING
OVERHEAD CABLE
PROPOSED
OVERHEAD CABLE
EXISTING
UNDERGROUND
CABLE
PROPOSED
UNDERGROUND
CABLE
E
PROPOSED
ELECTRICAL
SERVICE CONDUIT
Cancelling Lot 43 on RP136461 Lot 44
ET
RP136461
PROPOSED #17
ELECTRICAL &
COMMUNICATION
SERVICE CONDUITS
k V)
00 (11
143
3-7/3.
POLE
TRANSFORMER
PADMOUNT
T
TRANSFORMER
EXISTING DWELLING
TO REMAIN
T
HV POLE
T
4
HV / LV POLE
T
T
LV POLE
T
HV UNDERGROUND
POLE TERMINATION
LOT 2
Lot 82
T
RIPARIAN ZONE 1 RP136461
LV UNDERGROUND
BΦ LOT 1 COVENANT AREA B #18
T
AΦ
POLE TERMINATION
(SUPPLY FROM STN 3)
T
(SUPPLY FROM STN 3)
AERIAL STAY
T
GROUND STAY X95494
CHANGE OF
T
PT FUSE
SERVICE REQUIRED
BY
T
RES
CC
DEVELOPER
MA C
DISC LINK N
T
OPEN
GROUND LEVEL
JIRRI
E
T
DISC LINK E
CLOSED E
E
T
450mm
E
kV)
E ELECTRICAL CONTRACTOR TO STRICTLY TAPE
00 (11
CUTOUTS
E
600mm
P
OPEN IMPLEMENT THE FOLLOWING RULES FOR
T
78
E
3-7/3.
E PILLAR INSTALLATION:
EASEMENT A E A. 1.1m EDGE TO EDGE SEPARATION
T
E OF PILLAR TO WATER METER
CUTOUTS
E 3 T
CLOSED B. 1.0m EDGE TO EDGE SEPERATION
E
FILE: C:\USERS\LENNIN.SANTOS\ONEDRIVE - AMPFLO PTY LTD\DESKTOP\AMPFLO FOLDER\PROJECTS\1. ONGOING PROJECTS\251400 - 15 JIRRIMA CRS COOROIBAH\A251400A
OF PILLAR TO DRIVEWAY W
T
W P P
EARTH
T
EX. PP
100mm
PROPOSED DRIVEWAY EXISTING OH SERVICE minimum clearance
T
EXISTING PILLAR & PROPERTY POLE TO
BORE EXISTING to electrical conduit
DRIVEWAY BE RECOVERED
Lot 83
T
PROPOSED PILLAR Lot 10 16LV RP136461
#16
SHARED TRENCH ELECTRICAL / COMMS / WATER
ALL SERVICE CONDUITS BY CIVIL CONTRACTOR
SP156380 CC
T
#11
N
LINK PILLAR Electrical and communication service conduits to be installed within service easement
and in compliance with AS/NZS 3000 (SAA Wiring Rules).
T
4B25
240LV
D 1
2 · Electrical service conduit to be orange heavy duty PVC UNO.
D
T
CONDUIT / CABLE P95495
CROSS-SECTION · Communications conduit to be white medium duty PVC. Refer to comms plan for
size.
X
16LVT
· Protective cover strip to be laid above all service conduits.
WATER METER DANGER · All conduits to be installed with draw wire and capped minimum 1 metre within lot
LIVE 11kV & LV OH MAINS
being serviced.
PROPOSED AT P95495
DRIVEWAY ENTRY
TYPICAL INTERNAL
4-7/3. 0 (11kV)
)
75 (LV
PROPOSED ZERO
SHARED TRENCH DETAILS
0
73
3-7/3.
LOT IDENTIFIER
LIGHTING
LEGEND
10 0 10 20 30 40 50 METRES
LED STREET
LIGHT
SCALE 1:500 (BEFORE REDUCTION)
FOR APPROVAL
(NOT FOR CONSTRUCTION)
EXISTING UNKNOWN
STREET LIGHT TO BE BUILT IN CONJUNCTION WITH
15/04/2026 10:51 am
NOTE: NOT ALL
SYMBOLS MAY BE
TELECOMMUNICATIONS PROVISIONING
USED
S2603254
This document is CLIENT SITE CONTACT DETAILS ALIGNMENTS PROJECT / CERTIFICATION: PROJECT
the property of NAME ENERGEX OH 3.0 SUB PROJECT NO. APPROVED: Ivan Lubacheski 2 LOT RESIDENTIAL SUBDIVISION
RPEQ No: 20070
Ampflo Pty Ltd RHIANA MAGEE ENERGEX UG 0 - 0.9 PARENT PROJECT NO. - DATE: 16/04/2026 15 JIRRIMA CRES, COOROIBAH
and may only be COMPANY TELSTRA BYDA WORK REQUEST NO. - ELECTRICAL RETICULATION PLAN
PLOT: 15/04/2026 10:51:33 am
used for the ABN 28 111 423 842
purpose for RHIANA MAGEE - GAS BYDA PLANNER & PHONE -
Electrical and Telecommunications
& DETAIL
which it was PHONE - HP GAS BYDA LOTS 1&2 Consultants CHECKED: R. YUMUL
commissioned. MOBILE 0419 132 841 WATER BYDA CANCELLING LOTS 43 ON RP136461 ISO 9 0 0 1
Phone : (07) 3372 9280 ISSUE
CERTIFIED DESIGNER: L. SANTOS DRAWING: A251400
A
Unauthorised A 15/04/2026 ISSUED FOR APPROVAL LS RY IL EMAIL [email protected] STORMWATER BYDA LOCAL AUTHORITY NOOSA SHIRE COUNCIL Email : [email protected]
use is prohibited. REV DATE DETAILS DRAWN CHECKED APPRVD SEWERAGE BYDA PEGGED? ON REQUEST
Q U A L I T Y
MANAGEMENT
Website : ampflo.com.au ISSUE DATE: 15/04/2026 PROJECT: 251400 SHEET 02 OF 03 A1
Page 3
LEGEND
EXISTING
OVERHEAD CABLE
PROPOSED
OVERHEAD CABLE
EXISTING
UNDERGROUND
CABLE
PROPOSED
UNDERGROUND
CABLE
E
PROPOSED
ELECTRICAL
SERVICE CONDUIT
ET
SWITCHING & COMMISSIONING PLAN - LV
PROPOSED
ELECTRICAL & WORK AREA (subject to site conditions, amendments by switching co-ordinator and approval by LV
COMMUNICATION outage co-ordinator)
SERVICE CONDUITS
SWITCHING - LV ONLY
3
U12723520
POLE
TRANSFORMER
1. INSTALL NEW LV UG NETWORK AS PER PLAN
1
16mm² 4C Cu 2. ERECT & LIVE BRIDGE NEW 16mm² UNDERGROUND TERM AT P95495 (STN 1) -
P95495
JIRRIMA CRES
PADMOUNT
TRANSFORMER P95495 - JIRRIMA CRES (STN 1) 3. TEST AND COMMISSION
OVERHEAD WORKS SCHEDULE
LABEL SITE LOCATION FOR POLES CONSTRUCTION
SIZE ATTACHING OF LABEL LABEL INFORMATION 4. PERFORM POST COMMISSIONING CHECKS LOCATION
STN SITE ID
REMARKS
No (POLE No) EDT EDT SST LST
EXISTING RECOVER ERECT SINK FOOT
COMP
ALIGN LCC EXISTING RECOVER ERECT No KBS ANG LCC
300x100 POLE No. TO JIRRIMA CRES U12723520 & SERVICES ANG kN kN kN ID
HV POLE
JIRRIMA CRES 1 P95495 EX EX EX EX P14/M EX EX PO1 EX 11P EX
P95495
LVT EX
LOCATION GSW
HV / LV POLE JIRRIMA CRES LVBR16/AOH 1
LVT4C16 1 250 DO NOT EARTH CABLE GUARD
LV POLE
OVERHEAD SERVICE SCHEDULE
HV UNDERGROUND
POLE TERMINATION SAG (m) TOTAL FITTINGS
STN HOUSE No OF CONDUCT
LOCATION EXISTING TRANSFER RECOVER ERECT DIST (m) SAG SPAN REMARKS
No No SPANS OR MAINS CHANGE FUSE SERVICE FITTING
15° 25° Ø
LENGTH BOX POA SIZE CODE OR IIN
LL1
S
LV UNDERGROUND JIRRIMA CRES 1 #15 4B25 4B25 1 29 EX EX EX EX EX EX TO BE RECOVERED BY ENERGEX
A CRE
9-C/D
POLE TERMINATION
SP600
M
JIRRI
AERIAL STAY
URD CONDUIT SCHEDULE - FOOTPATHS - BY ELECTRICAL CONTRACTOR
GROUND STAY CONDUIT LENGTH (m) X-SECTION (m)
STATIONS PVC CABLE KERB
LOCATION 100mm 125mm EQL 100mm EXCAV/ TRENCH DRAW WIRE MARKERS REMARKS
FROM - TO No. No. PROTECTION
LD LD COMMS MD TAPE DETAIL
PT FUSE (m)
JIRRIMA CRES 1 2 4 1 4 4 D 6
2 3 37 2 37 2 37 37 N 195 BORE DRIVEWAY (7.0m)
DISC LINK SP6009-C
OPEN 3 4 83 2 83 2 83 83 N 425
(200kVA)
TOTAL 244m 240m 120m 4m 124m 626m
DISC LINK
CLOSED
CONSUMER CONDUIT SCHEDULE - BY CIVIL CONTRACTOR
CUTOUTS
OPEN FROM TO ELECTRICAL (m) COMMS (m)
LOCATION REMARKS
STN LOT 40HD 50HD 63HD 80HD 20MD 50MD
JIRRIMA CRES 3 2 158
CUTOUTS TOTAL 158m
CLOSED
FILE: C:\USERS\LENNIN.SANTOS\ONEDRIVE - AMPFLO PTY LTD\DESKTOP\AMPFLO FOLDER\PROJECTS\1. ONGOING PROJECTS\251400 - 15 JIRRIMA CRS COOROIBAH\A251400A
EARTH
UNDERGROUND CABLE SCHEDULE
CABLE
STATIONS LENGTH (m)
LOCATION VOLTS EX REC IN CABLE SIZE/TYPE CU CODE REMARKS
EXISTING PILLAR FROM - TO
NEW REC
JIRRIMA CRES 1 3 LV * 16mm² Cu 4C XLPE/PVC LVC416XPV 51 INCLUDES LENGTH UP POLE
TOTAL LVC416XPV 51
PROPOSED PILLAR
LINK PILLAR
EQUIPMENT SCHEDULE
240LV
D LOCATION STN No SITE ID EX REC IN SIZE AND DESCRIPTION COMP ID CU CODE QTY REMARKS
CONDUIT / CABLE JIRRIMA CRES 3 U12723520 * ELECT PILLAR CROSS ROAD 16SQMM 6X100AMP PI1 LVSP12-6 1
CROSS-SECTION P95501
X
WATER METER
PROPOSED
EXISTING & PROPOSED LV SCHEMATIC DIAGRAM
DRIVEWAY ENTRY NTS
ALL NEW LV CABLES TO BE 4c 240mm² Al XLPE UNO
PROPOSED ZERO
LOT IDENTIFIER
LIGHTING
LEGEND
LED STREET
LIGHT
FOR APPROVAL
EXISTING UNKNOWN (NOT FOR CONSTRUCTION)
STREET LIGHT
NOTE: NOT ALL 15/04/2026 10:51 am
SYMBOLS MAY BE
USED
S2603254
This document is CLIENT SITE CONTACT DETAILS ALIGNMENTS PROJECT / CERTIFICATION: PROJECT
the property of NAME ENERGEX OH 3.0 SUB PROJECT NO. APPROVED: Ivan Lubacheski 2 LOT RESIDENTIAL SUBDIVISION
RPEQ No: 20070
Ampflo Pty Ltd RHIANA MAGEE ENERGEX UG 0 - 0.9 PARENT PROJECT NO. - DATE: 16/04/2026 15 JIRRIMA CRES, COOROIBAH
and may only be COMPANY TELSTRA BYDA WORK REQUEST NO. - LV SCHEMATIC, SCHEDULES, LABEL &
PLOT: 15/04/2026 10:51:33 am
used for the ABN 28 111 423 842
purpose for RHIANA MAGEE - GAS BYDA PLANNER & PHONE -
Electrical and Telecommunications
COMMISSIONING PLAN
which it was PHONE - HP GAS BYDA LOTS 1&2 Consultants CHECKED: R. YUMUL
commissioned. MOBILE 0419 132 841 WATER BYDA CANCELLING LOTS 43 ON RP136461 ISO 9 0 0 1
Phone : (07) 3372 9280 ISSUE
CERTIFIED DESIGNER: L. SANTOS DRAWING: A251400
A
Unauthorised A 15/04/2026 ISSUED FOR APPROVAL LS RY IL EMAIL [email protected] STORMWATER BYDA LOCAL AUTHORITY NOOSA SHIRE COUNCIL Email : [email protected]
use is prohibited. REV DATE DETAILS DRAWN CHECKED APPRVD SEWERAGE BYDA PEGGED? ON REQUEST
Q U A L I T Y
MANAGEMENT
Website : ampflo.com.au ISSUE DATE: 15/04/2026 PROJECT: 251400 SHEET 03 OF 03 A1