                                                                                                                                                                                                                                         EARTHWORKS NOTES
                                                                                                                                                                                                                                         1.   FOR GENERAL NOTES REFER DWG 002, WHICH IS TO BE REQUESTED AND VIEWED PRIOR TO COMMENCEMENT OF
                                                                                                                                                                                                                                              CONSTRUCTION IF NOT SUPPLIED.
                                                                                B      0.00
                                                                                 -
                                                                                                                                                                                                                                         2.   GRASS AND TOPSOIL SHALL BE STRIPPED TO A MINIMUM DEPTH OF 100MM OVER THE EXTENT OF THE WORKS
                                                                                                                                                                                                                                              UNLESS DIRECTED OTHERWISE AND STOCKPILED FOR FUTURE USE AS NON-STRUCTURAL FILL IF REQUIRED, OR



                                                                                     STREET
                                                                                                                                                                                                                                              REMOVE FROM SITE.




                                            PEARL
                                                                                                                                                                                                                                         3.   COMPACT THE EXPOSED SUBGRADE OR LOOSE TOP LEVEL MATERIAL TO A MINIMUM 98% STANDARD MAXIMUM
                                                                                                                                                                                                                                              DRY DENSITY TO AS1289 5.1.1. ANY 'SOFT SPOTS' IDENTIFIED BY THE PROOF ROLLING SHALL BE REMOVED AND
                                                                                                                                                                                                                                              REPLACED WITH A COMPACTED IMPORTED GENERAL FILL MATERIAL TO THE ABOVE COMPACTION
                                                                                                                                                                                                                                              REQUIREMENTS.

                                                                                                                                                                                                                                         4.   IMPORTED GENERAL FILL MATERIAL SHALL BE SUPPLIED AND COMPACTED WHERE NECESSARY TO OBTAIN
                                                                                                                                                                                                                                              SUBGRADE/PLATFORM LEVEL. IMPORTED GENERAL FILL MATERIAL SHALL BE CLEAN GRADED MATERIAL FREE OF
                                                                                                                                                                                                                                              ORGANIC MATTER AND STONES GREATER THAN 150mm AND CAPABLE OF BEING COMPACTED INTO COHERENT
                                                                                                                                                                                                                                              FILLING TO THE SPECIFIED STANDARD. THE MATERIAL SHALL HAVE A LINEAR SHRINKAGE NOT GREATER THAN 8%
                                                                                                                                                                                                                                              AND A MINIMUM C.B.R. OF 10%.

                                                                                                                                                                                                                                         5.   ANY PROPOSED RETAINING WALL WORKS MUST BE WHOLLY WITHIN THE PROPERTY BOUNDARY OF THE SUBJECT
                                                                                                                                                                                                                                              SITE, INCLUDING REAR OF RETAINING WALL DRAINAGE INFRASTRUCTURE FOR RETAINING WALLS IN CUT/
                                                                                                                                                   10.00                                              CUT/FILL DEPTH RANGE
                                                                                                                                                                                                      Lower_value Upper_value   Colour   6.   ALL RETAINING WALL GREATER THAN 1M TO BE STRUCTURALLY DESIGNED WITH CONSTRUCTION CERTIFICATION
                                                                                                                                                                                                                                              BY MANUFACTURER / INSTALLER.
                                                                                                                                                                                                      -0.9   to     -1.0   M
                                                                                10.00                                                                                                                                                    7.   ALL EARTHWORKS OPERATIONS SHALL BE CARRIED OUT WITH 'LEVEL 1' SOIL ENGINEERING SUPERVISION IN
                                                                                                                                                                                                      -0.8   to     -0.9   M                  ACCORDANCE WITH APPENDIX B OF AS 3798. THE NOMINATED GEOTECHNICAL TESTING AUTHORITY SHALL
                                                                                                                                                                                                                                              PROVIDE CERTIFICATION THAT ALL GENERAL EARTHWORKS OPERATIONS HAVE BEEN CARRIED OUT IN
                                                                                                                                                                                                                                              ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS AND THE CONTROLLED FILL IS SUITABLE FOR PURPOSE
                                                                                                                                                                                                      -0.7   to     -0.8   M
                                                                                                                                                                                                                                              WITH A MINIMUM 150KPA BEARING CAPACITY UNDER THE PLATFORM/STRUCTURES.

                                                                                                                                                                                                      -0.6   to     -0.7   M
                                                                                                                                                                                                                                         8.   ALL EARTHWORKS FILL AND EXCAVATED AREAS SHALL BE COMPACTED TO 98% STANDARD MAXIMUM DRY
                                                                                                                                                                                                                                              DENSITY (AS 1289 5.1.1) IN LAYERS NOT EXCEEDING 150MM COMPACTED THICKNESS.
                                                                                                                                                                                                      -0.5   to     -0.6   M
                                                                                                                                                                                                                                         9.   THE NOMINATED GEOTECHNICAL TESTING AUTHORITY SHALL PROVIDE CERTIFICATION THAT ALL GENERAL
                                                                                                                                                                                                      -0.4   to     -0.5   M                  EARTHWORKS OPERATIONS HAVE BEEN CARRIED OUT IN ACCORDANCE WITH THE DRAWINGS.

                                                                                                                                                                                                      -0.3   to     -0.4   M             10. CONTRACTOR TO UNDERTAKE ALL EARTHWORKS TESTING TO COMPLY WITH THE PROJECT SPECIFICATION AND
                                                                                                                                                                                                                                             LOCAL AUTHORITY REQUIREMENTS.
                                                                                                                                                                                                      -0.2   to     -0.3   M
                                                                                                                                                                                                                                         11. FINISHED SURFACES TO ALL DISTURBED AREAS ARE TO BE TREATED IN ACCORDANCE WITH LANDSCAPE
                                                                                                                                                                                                                                             DRAWINGS WHERE AVAILABLE.




                                                                                                                                                                                         45.63
                                                                                                                                                                                                      -0.1   to     -0.2   M
                                                                                                                                                          20.00                                       0.     to     -0.1   M
                                                                                                                                                                                                                                         12. FINISHED EARTHWORKS SURFACES TO BE STABILISED

                                                                                                                                                                                                                                         13. ALL EARTHWORKS TO BE CARRIED OUT AT +/- 2% OPTIMUM MOISTURE CONTENT.
                                                                                                                                                                                                      0.     to      0.1   M
                                                                                      20.00                                                                                                                                              14. ALL NEW WORKS TO MATCH NEATLY INTO EXISTING.
ELM




                                                                                                                                                                                                      0.1    to      0.2   M
                                                                                                                                                                                                                                         15. ALL WORKS TO BE CONSTRUCTED IN ACCORDANCE WITH ALL APPROVED MANAGEMENT PLANS.




                                                                                                                                                                           40.00
                                                                                                                                                                                                 A    0.2    to      0.3   M
                                                                                                                                                                                                  -                                      16. ADEQUATE SAFETY FENCING/BARRIERS TO BE APPLIED TO ALL BATTERS OR RETAINING WALLS (TEMPORARY OR
                                                                                                                                                                                                      0.3    to      0.4   M                 PERMANENT) AS PER RELEVANT AUSTRALIAN STANDARDS AND LEGISLATION.




                                                                                                                                    30.00
                                                                                                                                                                                                      0.4    to      0.5   M             17. DUST CONTROL MEASURES ARE TO INCLUDE SPRAYING WATER ON UNPAVED ROADS, ACCESS TRACKS AND
                                                                                                                                                                                                                                             STOCKPILES AT A SUFFICIENT LEVEL TO SUPPRESS DUST GENERATION. ADDITIONALLY CONTRACTORS ARE TO
                                                                                        20.00
                                                                                                                                                                                                                                             COVER OR ENCLOSE STOCKPILES WHERE REASONABLY PRACTICAL TO RESTRICT DUST MOVEMENT.
                                                                                                                                                                                                      0.5    to      0.6   M
          0.00




                                                                                                                                                                                                                                         18. PRIOR TO THE CONTRACTOR COMMENCING ANY WORKS DETAILED ON THIS DRAWING, THE CONTRACTOR IS TO
                                                                                                                                                                                                      0.6    to      0.7   M
                                            10.00




                                                                                                                                                                                                                                             NOTIFY RECOR AND RECEIVE WRITTEN CONFIRMATION THAT WORKS CAN COMMENCE.
 STREET




                                                                                                                                                                                                      0.7    to      0.8   M             19. ALL BATTERS TO BE KEYED/STEPPED INTO EXISTING MATERIAL AS DIRECTED BY GEOTECHNICAL ENGINEER.
                                                                                                                                                                                                                                             CONTRACTOR TO ALLOW FOR ALL KEYING/STEPPING AS REQUIRED.
                                                                                                                                                                                                      0.8    to      0.9   M

          A
                                                                                                                                                           30.00                                      0.9    to      1.0   M
                                                                                                                                                                                                                                         20. ALL TEMPORARY AND FINAL BATTER SLOPES ARE TO BE INSPECTED AND APPROVED BY GEOTECHNICAL
                                                                                                                                                                                                                                             ENGINEER. CERTIFICATION OF LONG TERM STABILITY TO BE PROVIDED BY GEOTECHNICAL ENGINEER PRIOR TO
           -                                                                                                                                                                                                                                 PRACTICAL COMPLETION.
                                                                                                                                                                                                      1.0    to      1.1   M
                                                                                            30.00                                                                                                                                        21. CONTRACTOR'S RPEQ GEOTECHNICAL ENGINEER IS TO CONFIRM THAT ALL CONSTRUCTED CUT/FILL BATTERS
                                                                                                                                                                                                                                             AND RETAINING STRUCTURES ON THE SITE HAVE ACHIEVED ADEQUATE STABILITY WITH A LONG-TERM FACTOR OF
                                                                                                                                                                                                      1.1     to     1.2   M                 SAFETY GREATER THAN OR EQUAL TO 1.5 AGAINST GEOTECHNICAL FAILURES.
                                                                                                                                                                       33.40                          1.2     to     1.3   M             22. IT IS RECOMMENDED THAT THE GEOTECHNICAL CONSULTANT BE CONTACTED TO CONFIRM THE SOIL CONDITIONS
                                                                                                                                                                                                                                             PRIOR TO EARTHWORKS COMMENCING.

                                                                                                                                                                  C
                                                                                                                                                                   -
                                                                                                        33.42                                                                                                                                                             EARTHWORKS VOLUMES
                                                                                                                                                                                                                                                                          EARTHWORKS VOLUMES FROM
                                                                                                  B                                                                                                                                                                       EXISTING SURFACE TO DESIGN
                                                                                                   -
                                                                                                                                                                                                                                                                          SURFACE
                                                                                                                                                                                                                                                                          CUT = -51.872m³
                                                                                                                                                                                                                                                                          FILL = 266.445m³
                                                                                                                                                                                                                                                                          BALANCE = 214.573m³


                                                                                                                                                                                                                                                                    NOTE:
                                                                                                                                                                                                                                                                    EXCEPT WHERE NOTED ON PLAN AND ASSOCIATED DESIGN
                                                                                                                                                                                                                                                                    DRAWINGS, ALL IN-GROUND SERVICES WITHIN THE PROPERTY
                                                                                                                                                                                                                                                                    BOUNDARY INCLUDING BUT NOT LIMITED TO: STORMWATER
                                                                                                                                                                                                                                                                    DRAINAGE,   SEWERAGE,   WATER,     GAS,  ELECTRICAL  AND
                                                                                                                                                                                                                                                                    COMMUNICATIONS TO BE SAFELY BE DISCONNECTED, REMOVED
                                                                                                                                                                                                                                                                    FROM SITE AND CAPPED OFF AT SITE BOUNDARY. CONTRACTOR TO
                                                                                                                                                                                                                                                                    ARRANGE ALL NECESSARY APPLICATIONS AND PERMITS WITH THE
                                                                                                                                                                                                                                                                    RELEVANT AUTHORITIES. SERVICES TO BE CAPPED IN
                                                                                                                                                                                                                                                                    ACCORDANCE      WITH    RELEVANT      SERVICE   PROVIDER
                                                                                                                                                                                                                                                                    SPECIFICATIONS AND STANDARD DETAILS




                                                                                                        CLIENT DETAILS:                                           PROJECT ADDRESS:                            APPROVED BY:                         PROJECT NAME:

                                                                                                                                                                                                                                                   PROPOSED COMMERCIAL DEVELOPMENT
                                                                                                                   IRONBARK SMSF PTY LTD                                                                                                           TITLE:                                            STATUS:

                                                                                                                                                                                48 ELM STREET                                                      BULK EARTHWORKS                                   FOR APPROVAL - NOT FOR
               © ABN 89 647 469 707
                                       02   25/05/23   RFI UPDATE                     BP    BP    BP                                                                           COOROY, 4570, QLD                        BEN PARRY                  LAYOUT PLAN                                       CONSTRUCTION
             75 NOOSA DRIVE                                                                                                                                                                                             RPEQ: 28084
                                       01   09/02/23   OPW ISSUE                      BP    JB    JB    SCALE:
          NOOSA HEADS, QLD 4567                                                                                                                                                                                      CPEng NER MIEAUST
              +61 7 5211 1003         REV    DATE               DESCRIPTION           DWN   CHK   APP
                                                                                                                                    1:100                                                                              DATE: 25/05/23
                                                                                                                                                                                                                                                   DRAWING NUMBER:                                   PROJECT NUMBER:                        SHEET REV:
                                                                                                                                                                                                                                                                                                                                             SIZE:
          RECORCONSULTING.COM                                       REVISIONS
                                                                                                                          DO NOT SCALE, IF IN DOUBT ASK
                                                                                                                                                                                                                                                   020                                               20220206                                A1 02
Log in to download the original file

civil.pdf · 5.5 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.