slope stability
Integra Partnerships 22340-001-Rev0
14 September 2022
Steel reinforced concrete bored piles founded as noted above may be designed using an allowable end
bearing pressure of 300 kPa. Parameters for screw pile design are given in Table 1 below. Settlements
under such pressures should be no more than about 25 mm.
Table 1: Screw Pile Design Parameters
Ultimate Allowable
Bearing
Unit weight Friction angle, Bearing Bearing
Founding Material Capacity
(kN/m3) Ø (°) Capacity fbult Capacity fball
Factor, Nq
(kPa) (kPa)
Medium dense natural
18 32 25 1200 400 (Note 1)
sand
Dense to very dense (or
19 36 35 1800 600
denser) natural sand
Notes:
1) Allowable pressure based on a working stress factor of safety value of 3 on the ultimate pressure. If a limit state
design methodology is adopted the ultimate bearing capacity may be used and must be multiplied by a
geotechnical reduction factor Øg determined in accordance with AS2159-2009 to obtain the Design
Geotechnical Strength (Rd,g).
The advice of a specialist piling contractor must be sought regarding feasibility, design and installation of the
piling system for this site, including an assessment of potential vibration effects on nearby structures, and
monitoring requirements.
If steel screw piles are adopted, it will be important to ensure close supervision of installation, as piling may
not encounter sufficient drilling resistance (from torque measurement) in sands at the suggested founding
depth, and piles could extend to much greater depth than necessary.
It is therefore recommended that site specific static load testing be conducted from screw piles, if adopted, at
a minimum. Where tension or compression capacity developed in the footings is critical for the future
structure (e.g. resistance to uplift forces from high winds), then cyclic load tests (including measurement of
deflections under tension and compression cycles) should also be undertaken prior to construction.
Kentledge for static testing, or simulated cyclic loads, should prove the piles to a minimum of two times the
expected working load within tolerable deflections.
All footings should be founded such that they are not adversely affected by or affect any adjacent
excavations, trenches, retaining walls, or in ground structures that are not designed to support building
loads. Footings should be founded at least below a plane extending 1 m horizontally from the base of
trenches/excavations/retaining walls/swimming pool, then rising up at 1V:1H, as illustrated in Text Figure 9
overleaf.