Attached to the e-mail Amended Energex Response (23.4.20) - 152006.1999.4.
(i)
SUMMARY
A subdivision is proposed of Lot 53 SP163571 at Hollett Road, Noosaville.
Lot 53 is encumbered by a 26.5 metre wide easement that accommodates an
ENERGEX double circuit concrete and steel tower line supporting two 132kV high
voltage circuits.
ENERGEX has requested that an assessment be undertaken of the magnetic field
levels impacting on the proposed lots that will be located adjacent to the transmission
corridor to confirm that the levels are within industry standards and guidelines.
Average and maximum magnetic field calculations have been completed with respect
to the installed infrastructure and determined to be significantly less than the adopted
reference value of 4mG at the edge of the easement nearest the subject lots.
The subdivision layout has incorporated the principles of prudent avoidance in
building location and design on lots adjacent to the subdivision. This provision will
further reduce the magnetic field levels experienced by persons occupying the
residential subdivision.
Any miscellaneous development of the easement area for park or other recreational
purposes should aim to keep persons as clear of the powerline structures and
conductor alignment as practicable.