Original source · versioned page text
EGX_PROD_n6923390_191_Hollett_Road,_Noosaville_L53_SP163571
Attached to the e-mail Amended Energex Response (23.4.20) - 152006.1999.4.
J&P Richardson Industries Pty Ltd -11-
4.3.2 Scenario2 Feeder 10PoE load forecasted
The results of electric and magnetic field calculations relevant to scenario2 are summarised
in Table 8 and Figure 8 below and figure 9 overleaf.
Table 8 EMF levels scenario2 : maximum 132kV feeder load
Calculated value at edge of
4mG offset
PARAMETER easement Maximum
Northern Southern Northern Southern
Magnetic Field strength 0.83 mG 0.71 mG N/A N/A 2.26mG
Electric Field strength 0.136kV/m 0.113kV/m ------ ------ 0.329kV/m
Figure 8 Magnetic Field profile : scenario2
Hollett Road EMF Study V1.0
See the original