Figure 6: Stormwater Drainage Catchments
3.9.3 Scenario Method
The proposed development was modelled using split catchment source nodes. Three (3) urban residential source
nodes were identified, comprising of road, ground cover and roof nodes. Sub-catchments were derived from the
proposed stormwater drainage plans.
Although the exact quantity of dwellings cannot be confirmed, it is expected that the average density of dwellings/ha
within Lots 1 and 2 will be approximately 65 dwellings/ha and should be roughly between the 40 dwellings/ha and 80
+ dwellings/ha impervious fraction recommendations in Table 3.5 of the MUSIC Modelling Guidelines – South East
Queensland Version 1.0 (WBD, 2010). The nominated fraction impervious for each source node modelled in MUSIC
was therefore:
• Road source node: 40% impervious
• Ground cover source node: 70% impervious
• Roof source node: 100% impervious
The roof area has conservatively been estimated to be approximately 90% of the lot area, with the remaining 10%
categorised as ground cover.
The ~20m wide access reserves that extend from Road 1 to the balance lot 100 have been included in the Road node.
40% fraction impervious has been adopted within the access reserves to allow for future driveway and path accesses.
This matches the impervious percentage within the Road 1 reserve.
Table 3: MUSIC Source Node Characteristic
Source Node Road Ground Cover Roof Total
Catchment Sub-Catchment Area (ha) Area (ha) Area (ha) Area (ha)
A N/A 0.73 0.09 0.85 1.67
62 Lake Macdonald Drive, Cooroy – Engineering Services Report Page 9
233467 | M24-1037Rpt – Issue A – April 2025
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Final Engineering services report _62 Lake Macdonald Drive.pdfRelated documentApplication case desk ↗
About this file
- File size
- 27.0 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.