Building inspection report - 267 Taylor St, Wilsonton - tack room

of 7

Page text shows just the words. Original shows the document exactly as it was published.

Page text read automatically using OCR, there may be inaccuracies

Anstey Design Pty Ltd

ABN: 86 612 095 271

Email: [email protected]

34 Wilden St

Paddington QLD 4064

Phone: 0417 029464

25 September 2020



Mr Terry King

111 Wrights Rd

Gowrie Little Plains QLD. 4352

Dear Terry

Re: Proposed relocation of existing tack room building from 267 Taylor St Wilsonton to 83 Tunba
Court Cooroy Mountain QLD

As per your instructions, I carried out a structural inspection of this building on 17 September 2020
with regard to its suitability to be transported and re-established at the proposed new location at
Cooroy Mountain with an estimated maximum wind classification of N3.

The existing tack room (refer photo below), is single storey timber framed building with
chamferboard wall cladding & fibro roof cladding. It is currently supported on timber stumps. The
building is in a sound structural condition with no visible signs of potential failure or degradation of
the main timber structural framing and it is considered suitable for transport and re siting at the new
location. The structural timber framing appears to be in the order of F17 hardwood throughout.




Overall view
Log in to download the original file

Building inspection report - 267 Taylor St, Wilsonton - tack room.pdf · 3.1 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 6 pages

Page 2

The building to be moved has maximum overall dimensions of approximately:

-length 4.15m plus 0.45m eaves overhangs

-width 3.6m plus 0.45m eaves overhangs

-wall height 2.85m

and consists of the following members/ materials:

-round hardwood timber stumps

-100 x 75 hardwood bearers with 2000 continuous spans

-100 x 50 hardwood floor joists at 450 centres with 1750 continuous spans

-75 x 50 hardwood stud wall framing

-the roof framing consists of 100 x 50 hardwood rafters at 600 nominal centres & 75 x 38 hardwood
battens

-external wall cladding is timber chamfer boards

-roof cladding is asbestos cement ‘Super Six’ profile

Structural timber replacement:

It is the builder/removalists responsibility to ensure that any defective timber found during the
course of removal and re-establishment is replaced with new equivalent timber members.

Where a splice join is required, it should be adequate to ensure there is no loss of strength due to
replacement of the defective timber member.

All cuts should be spliced with timber fish plates of the same dimensional width and 500 either side
of the cut location, fixed with 2/M10 bolts each side of the cut. This should be increased to 750mm
for floor joists or to the satisfaction of the inspecting authority.

External treatment:

All timber should be treated in accordance with Australian Standard AS1684.2 2006 Non Cyclonic
Areas Residential timber framed construction Part 2 recommendations.

The exterior of the building is fully clad with timber chamfer boards which are in fair condition.

Roof sheeting is asbestos cement and should be replaced.

The timber fascia boards are in fair condition.

Tiedown requirements:

    -   Rafter to wall top plate – 1 framing anchor with 4/2.8mm nails each leg to receiving
        members or 30 x 0.8 GI strap with 4/2.8mm nails each end to top plate face.
    -   Wall top plate to bearer - fix the top plate to alternate studs with 2/100mm No 14 Type 17
        screws and provide a 30 x 0.8 GI strap fixing from the bottom of alternate studs to the
        bearer with either 2/75mm No14 Type 17 screws or a minimum of 4/2.8mm nails each leg.
    -    Bearer to stump – provide 2/M12 bolts through bearer to top of new steel stump head
        cast-in to concrete bored pier.

Page 3

   -   Roof batten to rafter – fix with minimum 1/75mm No 14 Type 17 screw, 50mm penetration
       to rafter.

   Note: All connections are to be in conformance with AS1684.2 requirements. It is the
   builder/removalists responsibility to ensure that the existing building infrastructure is in sound
   condition and any timber deemed unsatisfactory be replaced in accordance with the minimum
   requirement outlined above, or as specified in AS1684.2 and sound building practice.

   Summary:

   Based on the inspection carried out, it is my professional opinion that the building is in a sound
   condition, suitable for removal and re-establishment at the proposed new site with an estimated
   maximum wind classification of N3 and in accordance with AS 1170.2.

   Generally however, the following comments are noted:

   -the main structural members such as floor, wall and roof framing appear to be in a sound
   condition and are adequately sized for the spans, with the following comments:

       -minimum tie down requirements as noted above.

   -when moved to the new location, the building is to be low set and supported on engineer
   designed stumps as detailed on Anstey Design drawing number 20203 dated 25 September
   2020.

   -roof sheeting & guttering to be replaced.

Transport considerations:

   -the building should be transported in one piece (approximately 5.0m long x 4.5m wide) due to
   the compact size and layout of the building and design of the framing, with appropriate
   transport bracing.



   For any further enquiries, please contact the undersigned.

   Yours faithfully




   Russell Anstey

   BE Civil MIE Aust

    CPEng NPER No 70471

    RPEQ No 4212

Page 4

Front view




Side view


[OCR of page images]
Front view

 

 

 

 

 

 

 

 

 

Side view

 

Page 5

Rear view




Internal view


[OCR of page images]
 

 

 

 

 

 

 

Pr —~ L j
ri ira ‘

\ ;
rt AY 4

§

rr

i
Rear view

 

Internal view

Page 6

Internal view showing T & G timber floor




Internal view showing VJ wall lining & ceiling


[OCR of page images]
 

Internal view showing T & G timber floor

 

Internal view showing VJ wall lining & ceiling

Page 7

Sub floor framing


[OCR of page images]
 

Sub floor framing

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.