20.001 - 012 3-19 Larburnum Cr_Construction Issue_C1

of 4

Page text shows just the words. Original shows the document exactly as it was published.

GENERAL                                                                                           DIMENSIONS/LEVELS                                                                                              TIMBER FRAMING & BRACING:                                                                                ABBREVIATIONS:
G1    STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE                                   L1.    CONSTRUCTION SHALL BE SET OUT USING SURVEY BENCHMARKS PROVIDED BY COUNCIL.                              T1      ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS 1720, AS 1684                       A.C.F. -     ALL CORES FILLED
      SPECIFICATION, ARCHITECTURAL, AND OTHER CONSULTANTS' DOCUMENTS.                                                                                                                                                    AND THE REFERENCED STANDARDS THEREIN.                                                            BTM.     -   BOTTOM
                                                                                                  L2.    ALL LEVELS AND SETOUT POINTS ARE SHALL BE CONFIRMED ON SITE BY REGISTERED                                                                                                                                        B.W.     -   BOTH WAYS
G2    REFER TO THE ARCHITECTURAL DRAWINGS FOR SETOUT. NO DIMENSIONS SHALL BE                             SURVEYOR PRIOR TO CONSTRUCTION. ADVISE ANY DISCREPANCY BEFORE PROCEEDING.                               T2      ALL FRAMING, BRACING AND TIE-DOWN INFORMATION FORMS THE BASIS OF THE                             CB       -   CONSTRUCTION BREAK
      OBTAINED BY SCALING FROM DRAWINGS.                                                                                                                                                                                 STRUCTURES STABILITY DOWN TO FOUNDATIONS. ALTERNATIVE METHODS SHALL                              C.O.S. -     CONFIRM ON SITE
                                                                                                  L3.     DIMENSION STANDARDS:                                                                                           ONLY BE ACCEPTED ON APPROVAL OF THE ENGINEER.                                                    D&C      -   DESIGN & CONSTRUCT
G3    UNLESS OTHERWISE NOTED (UNO), ALL LEVELS ARE IN METRES AND ALL DIMENSIONS ARE IN                   - REDUCED LEVELS, CHAINAGES AND COORDINATES ARE ALL IN METRES.                                                                                                                                                   DWG      -   DRAWING
      MILLIMETRES.                                                                                       - CIVIL DRAWINGS (SKC SERIES): ALL OTHER DIMENSIONS ARE IN METRES (m).                                  T3      PREFABRICATED TIMBER ROOF TRUSSES, PROPRIETARY FLOOR JOIST SYSTEMS
                                                                                                                                                                                                                                                                                                                          E.F.     -   EACH FACE
                                                                                                         - STRUCTURAL DRAWINGS (SKS SERIES): ALL OTHER DIMENSIONS ARE IN MILLIMETRES (mm).                               AND ALTERNATIVE TIMBER ELEMENTS TO THOSE SHOWN ON THE ENGINEERING
                                                                                                                                                                                                                                                                                                                          H.D.G. -     HOT DIP GALVANISED
G4     THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE STABILITY OF THE                                                                                                                                          DRAWINGS ARE TO BE DESIGNED AND CERTIFIED BY THE SUPPLIER'S STRUCTURAL
      STRUCTURE UNTIL ITS COMPLETION AND SHALL ENSURE THAT NO PART OF THE STRUCTURE               L4.    ALL LEVELS ARE TO AUSTRALIAN HEIGHT DATUM.                                                                      ENGINEER. DESIGN AND INSPECTION CERTIFICATES FOR THESE ELEMENTS ARE TO BE                        Lg.      -   LONG
      IS OVER-STRESSED BY EXCESSIVE LOADING.                                                                                                                                                                             ISSUED TO THE CONTRACTOR FOR LODGEMENT WITH THE LOCAL AUTHORITY.                                 L.V.     -   LENGTH VARIES
                                                                                                  L5.    DIMENSIONS SHALL NOT BE SCALED FROM DRAWINGS.                                                                                                                                                                    N.S.O.P. -   NOT SHOWN ON PLAN
G5    ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE CURRENT VERSION                                                                                                                              T4      ALL TIMBER MEMBERS USED ARE TO HAVE A MINIMUM LEVEL OF DURABILITY AS                             SS       -   STAINLESS STEEL
      OF THE APPLICABLE STANDARD EXCEPT WHERE VARIED BY THE SPECIFICATION AND/OR                  L6.    DESIGN USES DIGITAL TERRAIN MODEL GENERATED FROM THE SITE SURVEY. SOME                                          SPECIFIED IN AS1684.2 - APPENDIX B.                                                              TYP.     -   TYPICAL
      DRAWINGS. APPLICABLE CODES OF PRACTICE INCLUDE BUT ARE NOT LIMITED TO THE                          ELEMENTS ARE INTERPOLATED AND MAY VARY FROM THE ACTUAL SITE CONDITIONS                                                                                                                                           U.N.O. -     UNLESS NOTED OTHERWISE
      FOLLOWING:                                                                                                                                                                                                 T5      ALL HWD TIMBER SHALL BE SEASONED UNO.                                                            V        -   VARIES
      AS 1163        STRUCTURAL STEEL HOLLOW SECTIONS
      AS 1170        SAA LOADING CODE                                                                                                                                                                            T6      ALL TIMBER SHALL BE FREE OF GUM VEINS, KNOTS, SHAKES, CHECKS, WANES AND ANY
      AS 1554        WELDING OF STEEL STRUCTURES                                                  CONSTRUCTABILITY CONSTRAINTS:                                                                                          OTHER IMPERFECTIONS WITHIN CONNECTION ZONES.
      AS 1664        ALUMINIUM STRUCTURES
      AS 1684        RESIDENTIAL TIMBER-FRAMED CONSTRUCTION                                       CC1. CONSTRUCTABILITY CONSTRAINTS:                                                                             T7      ALL TIMBER FRAMING TO BE MINIMUM H6 TREATED UNO.
      AS 1720        TIMBER STRUCTURES
      AS 2159        PILING CODE                                                                    A)   PROTECT ALL EXISTING INFRASTRUCTURE (EG CULVERT CROSSING, PAVEMENTS,                                    T8      EXPOSED FRAMING (TIMBER FRAMING THAT MAY BE SUBJECT TO PERIODIC WETTING):
      AS 4100        STEEL STRUCTURES                                                                    FENCING & ELECTRICAL POLES/WIRES) FROM ANY DAMAGE.                                                                  - SHALL BE EITHER H6 PRESSURE TREATED OR DURABILITY CLASS 1
      AS 4997        GUIDELINES FOR THE DESIGN OF MARITIME STRUCTURES                                                                                                                                                          SPECIES (MINIMUM) SAWN TIMBER (UNO)
      AS 5100        BRIDGE DESIGN                                                                 B)    ALLOW OF LIKELIHOOD OF FLOW WITHIN THE WATERWAY: EXISTING WATERWAY ARE
      BCA           BUILDING CODE OF AUSTRALIA (NATIONAL CONSTRUCTION CODE)                              FLOODED MULTIPLE TIMES PER YEAR. PROTECT CONSTRUCTION EQUIPMENT AND                                     T9      WASHERS SHALL BE PROVIDED UNDER ALL NUTS AND BOLT HEADS (EXCEPT CUP-HEAD
                                                                                                         WORKS.                                                                                                          BOLTS) BEARING AGAINST TIMBER AS FOLLOWS:
G6    ANY DISCREPANCY SHALL BE REFERRED TO THE SUPERINTENDENT FOR A DECISION BEFORE                                                                                                                                          BOLT SIZE      WASHER
      PROCEEDING WITH THE WORK.                                                                   CC2. NO WORK TO COMMENCE ON SITE UNTIL:                                                                                    <=M12           50X50X3.0mm
                                                                                                                                                                                                                                M16         57X57X4.0mm
                                                                                                       - OFFICIAL PRE-START MEETING HELD AND PRE-START MEETING MINUTES ISSUED
G7    ALL PROPRIETARY PRODUCTS NOT DEEMED TO COMPLY WITH THE BCA SHALL HAVE                                                                                                                                                     M20         65X65X5.0.mm
                                                                                                       - CONTRACTOR'S MANAGEMENT PLANS SUBMITTED (SITE, TRAFFIC, ENVIRONMENT,
      THIRD-PARTY CERTIFICATION WITH RELEVANT TESTING AND SIGN-OFF BY AN RPEQ ENGINEER.                                                                                                                                       >M20           75X75X6.0mm
                                                                                                       SAFETY) FOR SUPERINTENDENT'S REVIEW.
      PROPRIETARY PRODUCTS INCLUDES PREFABRICATED TRUSSES, LIGHT-GAUGE STEEL
      FRAMING, FLOORING PRODUCTS, RECYCLED TIMBER AND PLASTICS, BALUSTRADES, SCREENS,                                                                                                                            T10     X….. INDICATES M12DIA ANCHOR ROD/BOLT
      SHADE FABRICS, JOINERY, PARTITIONS AND OPERABLE WALLS.
                                                                                                                                                                                                                 T11     [X]….. INDICATES M16DIA ANCHOR ROD/BOLT
G8    REFER TO ARCHITECTS DRAWINGS FOR DETAILS OF ALL GROOVES, FILLETS, HOBS, DRIP
                                                                                                  DRIVEN PILES:
      GROOVES AND THE LIKE.                                                                                                                                                                                      T12     SB…. INDICATES STRAP BRACE ROOF BRACING FIXED TO TOP OF EACH JOIST WITH 2
                                                                                                  P1.    PILES SHALL BE CONSTRUCTED IN ACCORDANCE WITH AS2159.                                                           SCREWS. BEND STRAP BRACING OVER AT ENDS, FIX WITH 2 SCREWS TO TOP OF JOIST
G9     GIVE AT LEAST 24 HOURS NOTICE OF AN INSPECTION BEING REQUIRED FOR :                                                                                                                                               AND 4 SCREWS TO SIDE FACE OF SUPPORTING MEMBER. ALL ROOFS TO BE BRACED.
                                                                                                  P2.    CONSTRUCTION CONSTRAINTS: AVOID LOADING EXISTING REVETMENT WALLS.
      - PILING
      - JETTY FRAMING (TIMBER)                                                                                                                                                                                   T13     ALL FASTENERS ARE TO BE GRADE A4-70 STAINLESS STEEL IN ACCORDANCE WITH
                                                                                                  P3.    DESIGN LOADS: PILES TO ACHIEVE GEOTECHNICAL CAPACITIES (VERTICAL &                                              ISO-3506-1. EXTERNAL ANCHORS WHERE SUBJECT TO SALT AIR SHALL BE STAINLESS
      - BRACING AND TIE DOWN
                                                                                                         HORIZONTAL) SHOWN ON THE DRAWINGS                                                                               STEEL A4-70:
G10   ALL FABRICATION SHOP DRAWINGS SHALL BE PROVIDED TO THE ENGINEER FOR REVIEW AND                                                                                                                                          -SCREWS TO BE NO.14 TYPE 17 WITH 50MM EMBEDMENT (UNO)
                                                                                                  P4.    REQUIRED PILE POSITION TOLERANCES:                                                                                   -ALL JOIST HANGERS, FRAMING ANCHORS, TRIPLE GRIPS AND THE LIKE, SHALL BE
      COMMENT IN A3 HARDCOPY OR PDF FORMAT.
                                                                                                                                                                                                                              STAINLESS STEEL. TO BE MANUFACTURED BY PRYDA OR APPROVED
                                                                                                         PLAN POSITION: +/- 50mm AT UNDERSIDE OF EACH GROUND BEAM.                                                            EQUIVALENT, WITH 5 NO. 2.8mm DIA X 30MM
G11   ABBREVIATIONS (GENERAL):
                                                                                                         PILE VERTICALITY:                                                                                                    NAILS EACH LEG MINIMUM. INSTALL AS PER MANUFACTURERS SPECIFICATION.
      NTS      NOT TO SCALE
                                                                                                         - WITHIN 4% FOR ALL PILES
      UNO      UNLESS NOTED OTHERWISE
      NSOE     NOT SHOWN ON ELEVATION                                                                                                                                                                            T14     PROVIDE BLOCKING OVER SUPPORTS AT 1800 MAX CRS IN ACCORDANCE WITH AS 1684
                                                                                                  P5.    PILE TOE LEVELS ON THE DRAWINGS ARE ESTIMATED LEVELS. ACTUAL TOE LEVELS                                         FOR TIMBER BEARERS AND JOISTS WITH D/B >= 4.
      NSOP     NOT SHOWN ON PLAN
                                                                                                         SHALL BE DETERMINED DURING CONSTRUCTION BY AN RPEQ-CERTIFIED
      TYP      TYPICAL
                                                                                                         GEOTECHNICAL ENGINEER.                                                                                  T15     FOR JOISTS WITH SPAN >3000 AND BOTTOM OF JOIST UNRESTRAINED BY CEILING
      (O)      OVER
      (U)      UNDER                                                                                                                                                                                                     DIAPHRAGM:
                                                                                                  P6.    DO NOT FOUND PILES HIGHER THAN TOE LEVELS ON DRAWINGS, UNLESS APPROVED BY                                            -PROVIDE 1 ROW OF BLOCKING BETWEEN EACH JOIST AT
      CRS      CENTRES
                                                                                                         BOTH THE SUPERINTENDENT AND THE GEOTECHNICAL ENGINEER. THE                                                               MIDSPAN FOR SPANS < 4200mm
      NOM      NOMINAL
                                                                                                         SUPERINTENDENT SHALL SEEK ADVICE FROM THE DESIGN ENGINEER AS REQUIRED.                                               -PROVIDE 2 ROWS OF BLOCKING BETWEEN EACH JOIST AT
      CFW      CONTINUOUS FILLET WELD
                                                                                                                                                                                                                                  THIRD POINTS FOR SPANS >4200mm

                                                                                                                                                                                                                 T16     FIXING LOCATIONS TO BE FIXED ACCORDING TO THE FOLLOWING MINIMUM PACINGS
DESIGN CRITERIA                                                                                   ALUMINIUM:                                                                                                             (D = FIXING SHANK DIA. IN mm):
                                                                                                                                                                                                                         BOLTS       4D  EDGE DISTANCE TO BOTH EDGES IN DIRECTION OF SHEAR LOAD
DC1 THE STRUCTURAL ELEMENTS HAVE BEEN DESIGNED FOR THE FOLLOWING LIVE LOADS                       A1.    ALL WORKMANSHIP AND MATERIALS SHALL COMPLY WITH BEST PRACTISE ALUMINIUM                                                    5D   PITCH BETWEEN BOLTS
    IN ACCORDANCE WITH AS 1170.1: LIVE LOAD REDUCTIONS ARE NOT APPLICABLE.                               FABRICATION AND THE CURRENT AUSTRALIAN STANDARD AS 1664.                                                                   5D   EDGE DISTANCE FROM END OF ELEMENT
    ELEMENT            UDL         CONCENTRATED                                                   A2.    ALUMINIUM SECTIONS SHALL COMPLY WITH AS 1734, AS 1886 OR AS 1867.                                                          13D MINIMUM OVERALL ELEMENT DEPTH
    DECK               2.0kPa      2.7KN                                                          A3.    ALL WELDING SHALL COMPLY WITH AS 1665.
                                                                                                  A4.    ALL WELDING SHALL BE CARRIED OUT USING ARGONGAS SHIELDING. WELD
DC2 WIND LOADS HAVE BEEN DETERMINED IN ACCORDANCE WITH AS 1170.2 BASED ON:                                                                                                                                        MINIMUM SPACING, EDGE & END DISTANCES FOR NAILS AND SCREWS
                                                                                                         CONSUMABLES SHALL BE COMPATIBLE WITH BOTH PARENT ALLOYS IN ACCORDANCE
    IMPORTANCE LEVEL            2                                                                        WITH AS AS 1665. FOR 6063-T6 USE 4043 FILLER WIRE. PLATE-TO-EXTRUSION ALLOYS
    REGION                      B                                                                                                                                                                                                                   MINIMUM DISTANCE
                                                                                                         SHALL BE WELDED USING APPROPRIATE FILLERS IN ACCORDANCE WITH WTIA
    ULTIMATE WIND SPEED         51 m/s                                                                   TECHNICAL NOTES WHERE NOT COVERED BY AS 1665.
    SERVICEABILITY WIND SPEED   39.0 m/s                                                                                                                                                                           SPACING TYPE        HOLES FOR                      HOLES FOR
                                                                                                  A5.    ALL WELDS SHALL BE A MINIMUM 5mm CONTINUOUS FILLET WELD ALL ROUND,
    TERRAIN CATEGORY           1.5                                                                                                                                                                                                     NAILS NOT                      NAILS PREBORED SCREWS
                                                                                                         UNLESS NOTED OTHERWISE.
                                                                                                                                                                                                                                       PREBORED                       TO 80% DIA.
                                                                                                  A6.    ALUMINIUM EXTRUSIONS SHALL BE STRUCTURAL GRADE ALLOY:- EXTRUSIONS 6063-T6
DC3 EARTHQUAKE LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 1170.4 BASED                                                                                                                                      END DISTANCE          20D                               10D        10D
                                                                                                         UNLESS NOTED OTHERWISE.
    ON:                                                                                                                                                                                                            EDGE DISTANCE          5D                                 5D        5D
                                                                                                  A7.    ALUMINIUM PLATE IS TO BE WROUGHT GRADE ALLOY 5083 H116.
    ACCELERATION COEFFICIENT    0.06                                                                                                                                                                               ALONG-GRAIN SPACING   20D                                10D       10D
                                                                                                  A8.    ALL STEEL AND STAINLESS STEEL BOLTS AND ALL OTHER FIXINGS MUST BE ISOLATED
    SITE FACTOR                1                                                                                                                                                                                   CROSS-GRAIN SPACING    10D                               3D         3D
                                                                                                         FROM ALUMINIUM USING NYLON OR SIMILAR APPROVED PACKERS/GASKETS, AND
    IMPORTANCE LEVEL           1                                                                         WASHERS WITH SHANK COLLARS.
    STRUCTURE TYPE                                                                                A9.    SHOP DETAIL DRAWINGS ARE TO BE SUBMITTED TO THE ARCHITECT AND ENGINEER
    DESIGN CATEGORY            EDC1                                                                      FOR REVIEW. APPROVAL IS TO BE OBTAINED FROM THE COUNCIL, THE ARCHITECT AND
                                                                                                         THE ENGINEER, PROIR TO COMMENCING FABRICATION.
DC4 FIRE RESISTANCE LEVELS OF STRUCTURAL ELEMENTS HAVE BEEN TAKEN AS FOLLOWS:
    ELEMENT        FRL (mins)
    COLUMNS        -/-/-
    BEAMS         -/-/-                                                                           TEMPORARY WORKS:
    WALLS         -/-/-

DC5 DETERMINATION OF DESIGN LOADING FOR NON-STRUCTURAL ELEMENTS SUCH AS                           T1.    MAINTAIN THE WORKS IN A SAFE CONDITION. ENSURE STRUCTURES ARE NOT
    CEILING AND CLADDING SYSTEMS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR                           OVER-STRESSED AT ANY TIME. TEMPORARY ROAD SURFACES SHALL BE TRAFFICABLE
                                                                                                         AT ALL TIMES. POTHOLES ETC SHALL BE MONITORED AND REPAIRED.
DC6 FLOOD LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 5100 WITH NOMINAL
    FLOOD VELOCITY TO BE CONFIRMED BY HYDRAULIC REQUIREMENTS AS FOLLOWS:
    -V100 = 1m/s.                                                                                 T2.    CONTRACTOR'S RPEQ TO CERTIFY DESIGN AND CONSTRUCTION FOR TEMPORARY
                                                                                                         WORKS: STRUTS, PROPPING, FORMWORK STRIPPING AND PROPPING PROCEDURES, TIE
                                                                                                         BACKS, EXCAVATION SHORING, PROTECTION WORKS, DE-WATERING SYSTEMS,
                                                                                                         FORMWORK, EARLY LOADING OF STRUCTURES AND THE LIKE.




© THIS DRAWING IS PROTECTED                                                               ASSOCIATED CONSULTANTS                                                                                                                                    PROJECT                                                               DRAWING TITLE
UNDER COPYRIGHT IN
ACCORDANCE WITH
AGREEMENT BETWEEN
LODESTAR MERIDIAN PTY LTD
                                                                                                                          NOOSA JETTY BUILDERS
                                                                                                                          JoB No: 1317
                                                                                                                          Address:
                                                                                                                                                                                    Long View                                                        PROPOSED NEW JETTY
                                                                                                                                                                                                                                                     UNIT 3, 19 LARBURNUM CRESCENT, NOOSAVILLE.
                                                                                                                                                                                                                                                                                                                           STRUCTURAL NOTES SHEET
T/AS LONG VIEW CONSULTING
                                                                                                                                                                     L              Consulting Engineers
                              REVISIONS




ENGINEERS AND THE CLIENT AS                                                                                               UNIT 3, 19 LARBURNUM CRESCENT,
NAMED HEREIN. EXCLUSIVE                                                                                                   NOOSAVILLE                                                Lodestar Meridian Pty Ltd T/as Long View Consulting Engineers
USE IS GRANTED UNDER THE
AGREEMENT ONLY FOR THE
                                                                                                                          LOT: 5      RP: GTP 104767                 V              Post:     PO Box 963 Cooroy QLD 4563
                                                                                                                                                                                                                                                    DRAWN
                                                                                                                                                                                                                                                               S.T.
                                                                                                                                                                                                                                                                      CHECKED
                                                                                                                                                                                                                                                                                F.M.
                                                                                                                                                                                                                                                                                       APPROVED          DATE
                                                                                                                                                                                                                                                                                                            26/02/2021
                                                                                                                                                                                                                                                                                                                          SCALE BAR                             DRAWING SCALES
                                                                                                                                                                                                                                                                                                                                                                                  1:1
                                                                                                                                                                                                                                                                                                                                                                                        DRAWING SIZE
                                                                                                                                                                                                                                                                                                                                                                                         A1 ORIGINAL
                                                                                                                          Client: BRUCE ARGENT-SMITH                                ABN:      87 711 552 832
PROJECT. THIS DRAWING SHALL
NOT BE CONSTRUCTED UNLESS                 1   CONSTRUCTION ISSUE        C1     F.M.                                                                                                 Mobile: 0414 681 676
                                                                                                                                                                                                                                                    DESIGNED          CHECKED                            RPEQ / Cert.     PROJECT NUMBER                        DRAWING NUMBER          REVISION
DESCRIBED AS "CONSTRUCTION                                                                                                                                                          Email:    [email protected]
ISSUE".                                   No. DESCRIPTION               REV.   APP.                                                                                                 Internet: www.longviewconsulting.com.au                                    F.M.             F.M.                              19951                     20.001-012                           S02               C1
Log in to download the original file

20.001 - 012 3-19 Larburnum Cr_Construction Issue_C1.pdf · 1.1 MB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.