20181085-ASC14 - Engineering Drawings

Attached to the e-mail Operational Works Application OPW20/0114 - Email 4 of 4 -Engineering Certificate - Engineering Drawings - QCAT Appeal - 4 Portside Crt, Noosaville.

of 3

Page text shows just the words. Original shows the document exactly as it was published.

                                                           PROPOSED NEW JETTY
                                                  at No.1/4 PORTSIDE COURT, NOOSAVILLE
                                                         BUILDER: PONTOON WORKS
                                                              Job No.: 20-0274
                                                                                                                DRAWING REGISTER
                                                                                  Sheet No.          TITLE                            REVISION   Date of Issue
                                                                                    S01              GENERAL NOTES                A              18/06/2020
                                                                                    S02              JETTY LAYOUT & CONNECTIONS   A              18/06/2020




                                                       Office:   Suite 35/13 Norval Court, Maroochydore
                                                       Ph:       (07) 5444 5578
                                                       Web:      hrdesigngroup.com.au
                                                       Email:    [email protected]
Cromar Winning Consulting Engineers Pty Ltd T/A
ABN 30 169 626 957
Log in to download the original file

20181085-ASC14 - Engineering Drawings.PDF · 110 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 2 pages

Page 2

                   1 - GENERAL NOTES:                                                                                                    5 - REINFORCED CONCRETE:
                   1.0    These drawings shall be read in conjunction with HR Design Group specification and                             5.0    All work shall be in accordance with all current Australian Standards as a MINIMUM
                          certification, all architectural and other consultants drawings and specifications.                                   work standard.
                          Any discrepancies shall be referred to the architect or project manager for a
                          decision before proceeding with the work.                                                                      5.1    Concrete shall have a characteristic compressive strength after 28 days of not less
                                                                                                                                                than that listed below for the various concrete elements UNO.:
                   1.1    Dimensions SHALL NOT be obtained by scaling off the drawings.                                                               i)      FOOTINGS                            - 25 MPa
                   1.2    All dimensions shall be checked by Builder prior to commencement of works.                                                  ii) INTERIOR GROUND SLABS                   - 25 MPa
                                                                                                                                                      iii) EXTERIOR GROUND SLABS                  - 32 MPa
                   1.3    Prior to the commencement of construction the Builder shall check and                                                       iv) BLOCKWORK CORE FILL                     - 20 MPa
                          co-ordinate with the Architect and other consultants all steps, falls, rebates,                                             v) SUSPENDED SLABS                          - 40 MPa
                          setdowns, chases and penetrations. Any discrepancies with our drawings shall
                          be referred to us for clarification and/or revision. Under no circumstances                                    5.2    Minimum clear cover to reinforcing bar shall be in accordance with the following table. However
                          shall the Builder proceed with the works until all discrepancies have been                                            cover to reinforcing noted on the plans shall take precedence over those stated in the table.
                          satisfactorily resolved.                                                                                                    i)     FOOTINGS                            - 50mm TO ALL SIDES
                                                                                                                                                      ii) INTERIOR GROUND SLABS                  - 30mm TOP & BOTTOM
                   1.4    All workmanship and materials shall be in accordance with the relevant Australian                                           iii) EXTERIOR GROUND SLABS                 - 45mm TOP & BOTTOM
                          Standards, the BCA and local council regulations.
                                                                                                                                         5.3    All concrete shall be mechanically vibrated. Vibrator shall not be used to spread
                   1.5    The contractor shall be responsible for the maintaining the structure and adjacent                                    concrete.
                          structures in a stable condition, ensuring no part is overstressed during the works.
                                                                                                                                         5.4    All concrete surfaces shall be cured using an approved method for seven (7) days
                                                                                                                                                immediately after concrete is hard. Confirm method of curing with Engineer prior to
                   2 - SAFETY RISK & HAZARDS                                                                                                    use. Following concrete placement and as required during the finishing process,
                                                                                                                                                aliphatic alcohol or approved curing compound shall be applied to exposed surfaces
                   2.0    It is essential that an adequate safety plan is prepared by the contractor for the                                    to limit moisture loss from the fresh concrete.
                          works. HR Design Group may not be aware of all safety risks and hazards involved
                          in this project and the absence of comment does not imply that there are no                                    5.5    Sizes of concrete elements do not include thickness of applied finishes.
                          risks or hazards.
                                                                                                                                         5.6    Construction joints where not shown shall be located to the Engineer's approval.

                                                                                                                                         5.7    No holes, chases, blockouts, ducts or embedment of pipes other than those shown
                   3 - LOADINGS:                                                                                                                on the structural drawings shall be made in concrete members without prior approval
                                                                                                                                                of the Engineer.
                   3.0    The structural work as shown on these drawings has been designed for the following
                          cases :                                                                                                        5.8    No additives shall be added or applied to the concrete mix without the approval of
                                i)    General floor live load of 1.5 kPa uniform distributed load                                               the Engineer.
                                ii) General floor live load of 1.8 kN point load
                                                                                                                                         5.9    All steel reinforcement in concrete elements shall be inspected by the Engineer and
                                iii) Balcony and stair floor live load of 2.0 kPa uniform distributed load                                      passed prior to pouring of any concrete.
                   3.1    Load combinations have been calculated in accordance with AS1170.1 requirements.                               5.10   All reinforcement shall be supported on plastic chairs, generally at not greater than
                                                                                                                                                800mm centres in both directions. Bars shall be tied at alternate intersections.
                                                                                                                                                Conduits, pipes etc ... shall not be placed in the cover of the concrete.
                   4 - STRUCTURAL STEEL:
                                                                                                                                         5.11   All reinforcement shall comply with the requirements of the relevant Australian
                   4.0    All steelwork shall be constructed in accordance with code of practice AS4100 Steel Structures                        Standards.
                          Code, AS1554, AS1163, AS3679, AS4600 and all other codes of practice referred to therein.
                                                                                                                                         5.12   Concrete to have a maximum aggregate size of 20mm with 80mm maximum slump
                   4.1    Steel quality shall conform with the following Australian Standards UNO:
                                                                                                                                                and a water/cement ratio of not greater than 0.65.
                          - Steel Plates & Sections AS3679 Grade 300
                          - Rectangular Hollow Sections AS1163 Grade C350 LO                                                             5.13   The maximum permissible transport time for concrete between batching and placement
                          - Circular Hollow Sections AS1163 Grade C350                                                                          on site shall be in accordance with the following table.
                          - Square Hollow Sections AS1163 Grade C350
                          - Purlins/Girts AS1397 Grade G450 Z350                                                                                             AMBIENT AIR                                MAX. BATCHING TO
                                                                                                                                                            TEMPERATURE                                  PLACEMENT TIME
                   4.2    Unless noted otherwise all welds shall be 6mm continuous fillet E41XX electrode,                                                    10° - 24°C                                    120 minutes
                          all bolts M16 4.6/S, all plates 10mm thick.                                                                                         25° - 27°C                                     90 minutes
                                                                                                                                                              28° - 30°C                                     60 minutes
                   4.3    Unless noted otherwise, bolt holes shall be 2mm greater than specified bolt size.
                                                                                                                                                              31° - 33°C                                     45 minutes
                   4.4    The steelwork sub-contractor's shop drawings shall be submitted to the Engineer for                                                 34° - 36°C                                     30 minutes
                          review before fabrication commences.                                                                                                 37°C+                                 No placement of concrete
                                                                                                                                                                                                  unless chilled water or ice in mix
                   4.5    Fabricator to check all dimensions on site with contractor.
                                                                                                                                         5.14   A leveling sand layer (50mm minimum in thickness) shall be placed under slab on
                   4.6    Internal steelwork shall be blast cleaned to class 1 and coated with minimum 100µm high
                                                                                                                                                ground. The sand shall be salt free and compacted to 65% Density Index.
                          build Alkyd primer before erection. External steelwork shall be blast cleaned to class 2.5
                          and hot dipped galvanised to AS4680 with a coating mass of 600g/m2 (average).                                  5.15   A vapour barrier (200µm thick polythene sheet) shall be placed beneath the slab on
                                                                                                                                                ground so that the ground surface under the slab and thickenings is entirely covered in
                   4.7    The structural steel framework and bracing members shown on the plans are those
                                                                                                                                                accordance with AS3610 and AS2870.
                          required in the design for the completed structure only and the contractor shall be
                          responsible for providing any necessary temporary connections, supports and bracing                            5.16   Slab fabric shall be lapped one full panel of fabric plus 25mm so that the two
                          during the erection process to maintain the stability and safety of the steelwork                                     outermost transverse wires of one sheet overlap the two outermost transverse wires of
                          throughout construction.                                                                                              the sheet being lapped by 25mm.
                   4.8    Encased steelwork shall not be painted and shall be wrapped with F41 fabric, 50 cover.                         5.17   Where brittle floor coverings such as ceramic tile shall be used, an additional layer of
                                                                                                                                                SL62 Mesh shall be added to the existing slab reinforcement. If no extra reinforcement
                   4.9    The steel fabricator shall provide all bolts necessary for the erection of the steelwork
                                                                                                                                                is added covering should be delayed until 90 days after the slab has been placed.
                          and bolt holes and cleats necessary for the erection of timber works as shown, noted
                          or implied on these drawings or architects drawings and specification.                                         5.18   Where service pipes penetrate the floor and or walls provision should be made for
                                                                                                                                                movement of the floor/walls.
                   4.10   The roof structure has been designed for normal roof loads only and does not allow
                          for any extraneous loads such as hoists, monorails etc ... except where shown on                               5.19   All concrete shall be sampled and tested in accordance with AS 3600 adopting project
                          drawings.                                                                                                             assessment method for compressive strength and slump compliance. The results of all
                                                                                                                                                tests shall be promptly submitted to the Engineer for review.
                   4.11   When shop splices are necessary in beams, the position of the splice shall be
                          approved by the Engineer.                                                                                      5.20   Diagonal reinforcement shall be placed at all re-entrant corners. 2/N12 or 3-L11TM
                   4.12   Provide protective coating on all steelwork partially embedded in concrete UNO. The                                   1500mm Min. long. Typical.
                          coating should be non-conductive and extend a minimum of 200mm into the concrete                               5.21   The edge rebate shall be flashed and drained by weep holes at not more than 1m
                          in accordance with AS2312-2002 and a minimum of 100mm above the concrete.                                             spacing. Weep holes shall be located above the finished ground level any
                                                                                                                                                portion of a deepened rebate that cannot be drained shall be mortar filled.

                                                                                                                                         5.22   Approved steel reinforcement systems may be used in lieu of that stated on our plans
                                                                                                                                                (eg. Aquila steel "L" cage, Neumans F652 fabric etc ... ), provided the overall size of
                                                                                                                                                the footings and ground slab as detailed by us remains the same.

                                                                                                                                         5.23   All props and formwork under suspended concrete shall be removed before construction
                                                                                                                                                of brickwork or blockwork above UNO.




           Issue   Made By       Date              Description                                                             PROPOSED NEW JETTY                                                                                                                                                                                    Scale : N.T.S.     NOTES:
           A       BDK           18/06/20          Issue for construction
                                                                                                                           at No.1/4 PORTSIDE COURT, NOOSAVILLE
REVISION




                                                                                                                                                                                                                                                                                                                                 Job No.: 20-0274   1. Do not scale drawings.
                                                                                                                                                                                                                                                                                                                                                    2. Scale is correct at A3.
                                                                                                                           BUILDER: PONTOON WORKS
                                                                                                                                                                                                                                                                                                                                 Dwg No.: S01       3. Check and verify all dimensions
                                                                                                                           Designed By : B.R. CROMAR BEng (Civil) MIEAust CPEng RPEQ NER                                   Drawn By : BDK         Date : 18/06/20                                                                                     prior to commencement of work.
                                                                                                                           Certified By : B.R. CROMAR BEng (Civil) MIEAust CPEng RPEQ NER                                                         Date : 18/06/20   Ph: (07) 5444 5578   Email: [email protected]   GENERAL NOTES

Page 3

              FLOOR FRAMING SCHEDULE:

              MARK      SIZE                                              DESCRIPTION
              BR1       160x100x6.0 Rectangular Hollow Section            Bearer (single span + 600 max cantilever)
                        (Alloy & Temper - 6351/T5)

              DJ1       200x50x3.0 Rectangular Hollow Section             Deck Joist (2 spans + cantilever)
                        (Alloy & Temper - 6060/T5 or 6106/T6)

              TR1       200x50x3.0 Rectangular Hollow Section             Trimmer
                        (Alloy & Temper - 6060/T5 or 6106/T6)
                                                                                                                                                                                                   TR1
              P1        450Ø Jetty Concrete Piles                         Concrete Pier
                                                                                                                                                                                             BR1
           NOTES:




                                                                                                                                                                                                P1
           1. All floor joists to be at 450mm crs UNO.


             NOTE:
             All fixings, connectors, plates and angles
             to be Stainless Steel grade 316 or aluminium                                                                                                                      (Typical)                       (Typical)
                                                                                                                                                                                             BR1                                                                                                         450 inner diameter tube.
                                                                                                                                                                                                                                                                                                         Filled with concrete, N50/20.
                                                                                                                                                                                                                                                                                                         Provide 6/N12 bars and




                                                                                                                                                                                                P1
             NOTE:
                                                                                                                                                                                                                                                                                                         R10 helix with 150mm pitch.
             All dissimilar metals to be                                                                                                                                                           DJ1

             isolated to prevent corrosion
                                                                                                                                                                                                                Cantilevered decking must not
                                                                                                                                                                                                                be fixed to revetment wall.
                                                                                                                                                                                             BR1                Aluminum plate to end of jetty
                                                                           P1 below                                                                                                                             as specified by builder.




                                                                                                                                                                                                P1
                                                                                                                                                                Boundary                                                                                                                                                                                                                                      Approx Broadwater Bottom


                                        75m                                                                                                              Existing revetment wall
                                                                                                 m
                                           m                                                 75m




                                                                                                                                                                                                                                                                                                                                TBC by specilist contractor
                                                                   BR1                                                                                                                 JETTY LAYOUT


                                           m                                                  75m
                                       75m                                                       m



                                                                                                                                                                                                                                                         Decking as per
                                                                                                                                                                                                                                                         builder's specification




                                                                                                                                                                                                                                                                                                                                                              mm
                                                                                                                                                                                                                                                                                                                                                              100
                                                                                                                                                                                                                                                                                                                                                                           450mm Ø                Pile depth to be confirmed with
                                                                                                                                                                                                                                                 DJ1                                                                                                                                              specilist contractor and install piles
                                                                                                                                                                                                                                                                                                                                                                                                  achieve minimum working loads:
                                                                                                                                                                BR1                                                                                                                                                                                                                               Vertical load capacity - 21kN
                                                                                                                                                                           125x50x6.0mm UA
                                                                                                                                                                                                                                                                                                                                                                P1 - 450Ø PILE REINFORCEMENT      Horizontal load capacity - 4kN
                                                                                                                                                                                                                                                                                                                                                                                                  Confirm depth with engineer
                                                                                                                                                                           4mm CFW to BR1
                                                                                                                                High strength                                                                                                                                                                                                                                                     prior to construction
                                                                                                                                                                           4/M12 SS Grade 316
                                                                                                                                                                                                                                                             Provide 50x3.0 Equal Angle
                                                                   BR1                                                          compensated                                chemset anchors.                                     BR1                          (Alloy & Temper - 6060/T5 or 6106/T6)
                                                                                                                                grout pad                                  200mm min embedment.
                                                                                                                                                                                                                                                             with 1/No.14 x 20mm SS tek screw each way
                                                                                                                                                                                                                                                             Neoprene washers between
                                                                                                                                                                                                                                                             all SS fixings and aluminum.

                                96.9mm                                                             96.9mm
                                                                                                                                                                                                                                                                                                                                                                                               65mm
                                                                                                                                                                                                                                                                                                         450 inner diameter tube.
                                                                   P1




                                                                                                                                                                                                                                                                                                                                                                                               cover
                                                                                                                                                                                                                                                                                                         Filled with concrete, N50/20.
                                                                                                                                                         P1




                                                                                                                                                                                                                                                                                                         Provide 6/N12 bars and
                                                                 256.2mm                             Refer to separate detail                                                                                                                                                                            R10 helix with 150mm pitch.
                                                                                                     for reinforcement                                                                                                                                                                                                                                                                                 NOTE:
                                                                                                                                                                                                                                                                                                                                                                                                       Position Vertical bars to
                                                                                                                                                                                                                                                                                                                                                                                                       avoid clash with BR1 fixing


                                                                450mm Ø                                                                               450mm Ø                                                                                                                                                                                                              450mm Ø




            Issue     Made By      Date          Description                                                   PROPOSED NEW JETTY                                                                                                                                                                                              Scale : 1:100 UNO                                                         NOTES:
            A         BDK          18/06/20      Issue for construction
                                                                                                               at No.1/4 PORTSIDE COURT, NOOSAVILLE
REVISION




                                                                                                                                                                                                                                                                                                                               Job No.: 20-0274                                                          1. Do not scale drawings.
                                                                                                                                                                                                                                                                                                                                                                                                         2. Scale is correct at A3.
                                                                                                               BUILDER: PONTOON WORKS
                                                                                                                                                                                                                                                                                                                               Dwg No.: S02                                                              3. Check and verify all dimensions
                                                                                                               Designed By : B.R. CROMAR BEng (Civil) MIEAust CPEng RPEQ NER               Drawn By : BDK   Date : 18/06/20                                                                                                                                                                                prior to commencement of work.
                                                                                                               Certified By : B.R. CROMAR BEng (Civil) MIEAust CPEng RPEQ NER                               Date : 18/06/20      Ph: (07) 5444 5578    Email: [email protected]                                   JETTY LAYOUT & CONNECTIONS