S4400244 - Rev-A Sub 2 Pearsons Road, Cooroy 4563 Pkge - AC1286 [Approved]
Attached to the e-mail FW_ OPW21_0250 (2 Pearsons Rd Cooroy) - Revised Electrical Drawing Approval.msg.
Original PDF page 1, section 1. The text section number identifies this passage in the reader.
SURVEY DETAILS
203 AS/NZS 3000:2018 STREET LIGHTING CERTIFICATE LEGEND
3.11.5 Spacing from other underground services PRINCIPAL'S SURVEYOR TO PEG ALL BOUNDARIES PRIOR TO
CONSTRUCTION AND AFTER CONSTRUCTION TO PROVE ACCURACY SYMBOL DESCRIPTION
ROAD AND PUBLIC SPACE LIGHTING IS CERTIFIED
TO COMPLY WITH THE NOMINATED CATEGORIES OF OF ASSET INSTALLATION.
All underground wiring systems shall be spacing not less than 100 mm from 1 STATION NUMBER
other underground services. AS/NZS 1158.1.1:2005 AND AS/NZS 1158.3.1:2020.
CONSTRUCTION NOTES EXISTING OH CONDUCTOR
BLUE WREN PLACE - PR5 PROPOSED OH CONDUCTOR
Wiring systems shall be suitably marked with warning tape in accordance 1. CONTRACTOR TO INCLUDED PROVISIONAL SUM FOR VACUUM HV and LV POLE
with Clause 3.11.4.5 and maintain a separation from telecommunications, THE DESIGN ASSUMES MAINTENANCE FACTORS OF EXCAVATION AS U.G. SERVICES HAVE BEEN IDENTIFIED IN THE POLE TRANSFORMER
gas and water services in accordance with Table 3.7. 0.7 FOR MINOR ROAD LIGHTING, 0.75 FOR MAJOR VICINITY.
HV AIR BREAK OPEN
ROAD LIGHTING, 0.75 FOR LED LIGHTING, BASED ON 2. CONTRACTOR INCLUDE PROVISIONAL SUM FOR 'CUT AND
THE FOLLOWING SCHEDULE. REINSTATE' CONCRETE FOOTPATH, FULL PANEL AND FILL HV AIR BREAK CLOSED
Further requirements for the separation of telecommunications, gas and
WIDTH AT STATION 5 TO TRANSFER EXISTING CROSSROAD LV DISC LINK OPEN
water systems from low voltage wiring systems are provided in
1. LAMPS ARE TO BE REPLACED AT 36 MONTH CONDUIT TO EXISTING SPARE LV CONDUIT FROM STATION 4 LV DISC LINK CLOSED
Clause 3.9.8.4. INTERVALS, AT WHICH TIME LUMINAIRES ARE TO AND AT STATION 2 TO INSTALL LV CONDUIT/TERMINATION FROM HV POLE TERMINATION
TABLE 3.7 BE INSPECTED, CLEANED AND MAINTAINED. POLE AT STATION 1.
LV POLE TERMINATION
2. VEGETATION IS TO BE KEPT CLEAR OF STREET 3. TRAFFIC CONTROL REQUIRED.
MINIMUM SEPARATION OF UNDERGROUND SERVICES GROUND STAY
LIGHTS.
3. INSPECTION PATROLS AND SPOT LAMP EXISTING UG CABLE
Minimum separation to low Minimum separation REPLACEMENT SHALL MAINTAIN SERVICE
CONSTRUCTION NOTES - PRIVATE PROPERTY PROPOSED UG CABLE
voltage electrical service of conductive THE CLIENT'S CIVIL CONTRACTOR WILL BE RESPONSIBLE FOR THE
AVAILABILITY AT NOT LESS THAN 95%. EXISTING SUPPLY PILLAR
identified in accordance with enclosures to low FOLLOWING:
4. LUMINAIRES AND LAMPS SHALL BE REPLACED PROPOSED SUPPLY PILLAR
Type of service Clause 3.11.4.5 and mechanically voltage electrical · INSTALL CONDUITS THE FULL LENGTH OF THE ACCESS
WITH EXACT EQUIVALENTS.
protected (1) earthing electrode (1) CORRIDOR OR SUPERVISE INSTALLATION BY OTHERS. LINK PILLAR
· REMOVE REDUNDANT ELECTRICAL WIRING. PADMOUNTED TRANSFORMER
mm mm
EXISTING CABLE IN CONDUIT
Water service not THE ACCREDITED ENERGEX SERVICE PROVIDER WILL BE
100 500 PROPOSED CABLE IN CONDUIT
greater than DN65 (2) RESPONSIBLE FOR THE FOLLOWING:
SUPERVISE INSTALLATION OF CONDUITS THE FULL LENGTH OF MEN (EARTH GROUND STAKE)
Water service greater
300 500 RESIDENTIAL AND THE ACCESS CORRIDOR. E ELECTRICAL CABLE MARKER
than DN65 (2) CUSTOMER SWITCHBOARD
COMMERCIAL / INDUSTRIAL
Sanitary drainage 100 500 ELECTRICITY CONNECTION PROCESS PIT
SUBDIVISIONS
Stormwater drainage S70 STREET LIGHT
100 600 1. DEVELOPER'S REPRESENTATIVE SUBMITS CERTIFICATE OF
ONLY ENERGEX APPROVED MATERIALS, S250 STREET LIGHT
Gas 100 500 ELECTRICITY SUPPLY TO COUNCIL.
INSTALLATION EQUIPMENT, AND 2. DEVELOPER'S REPRESENTATIVE SUBMITS PLANS TO THE LED STREET LIGHT
Telecommunications 100 INSTALLATION TECHNIQUES SHALL BE TITLES OFFICE. TREE
USED DURING CONSTRUCTION. 3. ENERGEX ESTABLISHES A NATIONAL METER IDENTIFIER (NMI).
NOTES: 4. NEW CUSTOMER REFERENCES NMI AND MAKES AN LV SWITCH FUSE UNIT
1 Authorities, such as water and as suppliers and electricity distributors, may APPLICATION WITH THEIR ELECTRICITY RETAILER.
require their services to be spaced at a greater distance from underground wiring 5. ELECTRICAL CONTRACTOR REFERENCES NMI AND SUBMITS
systems. Also see Figure 3.10. THE APPLICATION WITH ENERGEX.
2 DN = internal diameter of pipe. 6. ENERGEX MAKES CONNECTION.
GENERAL NOTES
1. ALL CABLES TO BE INSTALLED IN CONDUIT WITHIN THE
STANDARD ELECTRICITY ALIGNMENT OF 250-900mm FROM
PROPERTY BOUNDARY.
2. CONSTRUCTION PERSONNEL SHALL MEASURE ACTUAL
CABLE LENGTHS REQUIRED ON SITE AFTER INSTALLATION
OF CONDUITS THEN NOTIFY SUPPLIER WHEN CONFIRMING
CABLE ORDER.
3. ALL BENDS INSTALLED ON 125mm RETICULATION
CONDUITS MUST BE 1830mm RADIUS UNLESS OTHERWISE
SPECIFIED.
AD
4. CONTRACTOR TO SUPPLY ALL LABELS AND SITE ID
WORK SITE
RO
NUMBERS TO ENERGEX SPECIFICATION.
ELM
5. DEVELOPERS CIVIL CONTRACTOR TO SUPPLY AND
NS
D
INSTALL CONDUITS AS SHOWN IN CIVIL WORK SCHEDULE.
OA
SO
STR
6. INSTALL ELECTRICAL CONDUIT AND
CARRU
R
THERS TELECOMMUNICATIONS PIT AND PIPE IN JOINT USE
AR
C OURT
NS
TRENCH - REFER PROJECT NUMBER AC1286-T
E
PE
ET
SO
Proposed Proposed
Proposed
AR
Lot 11 Lot 12
Lot 13 Proposed
Proposed
STANDARDS AND SPECIFICATIONS
PE
Lot 14
Lot Lot Lot 15
Lot Lot THIS WORKS PLAN IS TO BE READ IN CONJUNCTION AND
11 12 Lot Proposed
13 14 Proposed COMPLY WITH THE FOLLOWING ENERGEX MANUALS AND
Lot 15 Lot 10 Lot 100 SPECIFICATIONS:
Lot 100 Park
10 Park - UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
Lot BLUE W - OVERHEAD CONSTRUCTION MANUAL
Lot
9 R EN PLA Proposed BLUE W
16 Lot CE Lot 9 REN PL - PUBLIC LIGHTING MANUAL
8 Lot Lot Proposed ACE - NETWORK LABELLING AND SIGNAGE MANUAL
7 Lot Lot Lot 16
6 5 Lot Lot
4 Lot Proposed FOR DETAILS OF ADDITIONAL TRENCH CROSS-SECTIONS,
3 2 1 Lot 8 Proposed REFER TO ENERGEX UNDERGROUND DISTRIBUTION
Lot 7 Proposed
Proposed CONSTRUCTION MANUAL.
Lot 6 Proposed
Lot 5 Proposed
Lot 4
ACE
Lot 3 Proposed
SPOTT Lot 2 Proposed UG SERVICES INFORMATION
ED GUM Lot 1
COURT
RT
REN PL
UNDERGROUND SERVICES SHOWN ON THIS WORKS PLAN
COU
IN THE VICINITY OF PROPOSED EXCAVATION WORKS ARE
INDICATIVE ONLY.
BLUE W
OAK
ELM S
CONSTRUCTION PERSONNEL SHALL REQUEST ON-SITE
SURVEY PLAN IDENTIFICATION AND LOCATION OF EXISTING BURIED
SERVICES FROM THE QUEENSLAND DIAL BEFORE YOU DIG
EST
SCALE 1:1000 SERVICE. PH:1100 FAX:1300 652 077 (A MINIMUM OF TWO DAYS
TREE
NOTICE IS REQUIRED)
FOR
REFER JOB No: 21623980.
T
BLU
E W
REN P CONDUIT CROSS SECTION - FOOTPATH & ROADWAY
L
TR EET
GEM S CONDUIT CROSS SECTION -
ELECTRICAL SERVICE CONDUITS 600 FOOTPATH
750 MINOR ROAD
1200 MAJOR ROAD
LOCALITY MAP
500mm CAT A SYSTEM
SCALE 1:2000 500mm CAT B SYSTEM DETAIL O DETAIL D DETAIL P DETAIL E
50mm CAT C SYSTEM
600 FOOTPATH
750 MINOR ROAD
DETAIL 1 DETAIL 2 1200 MAJOR ROAD
NOTE: c c c
1. MINIMUM DEPTH OF COVER BASED ON NO SURFACE COVERING. SEE AS/NZS 3000:2018 TABLE 3.6
FOR FURTHER DETAILS.
2. MARKER TAPE SHALL BE POSITIONED 50% OF THE DEPTH OF COVER ABOVE THE WIRING SYSTEM. DETAIL H DETAIL N DETAIL Z
3. WIRING SYSTEM CATEGORY SPECIFIED IN AS/NZS 3000:2018 3.11.4 - INSTALLATION REQUIREMENTS.
NOTE: 5mm PROTECTION COVER STRIP REQUIRED WHEN NOT IN ALLOCATED ENERGEX UG ALIGNMENT
ISSUE DESCRIPTION DATE AUSPOWER CONNECT IS THE FIRST POINT OF DEVELOPER DETAILS ALIGNMENTS WORKS COORDINATOR - Approved
APPROVED: SUBDIVISION AUSPOWER CONNECT
AC1286
A ORIGINAL ISSUE 14/09/2021 CONTACT FOR CONSTRUCTION ENQUIRIES. Auspower Connect Pty Ltd Ventralia Pty Ltd ENERGEX OH 3.0m PARENT PROJECT NO. - Curtis Consulting Group
Alex Curtis - RPEQ No. 7917
RECONFIGURE 1 LOT INTO 16 LOTS PROJECT NO.
Darren Matthews ENERGEX UG 0 - 0.9m WORK REQUEST NO. - RAL 20/0021 SCALE: 1:2000 & 1:1000
PO Box 531
0499 339 155 STREETLIGHTS 0.7 & 1.2m I.O.K LOTS 1-16 ENERGEX PROJECT NO.
Buddina, QLD 4575 ELECTRICAL RETICULATION
[email protected] NBN REFER DBYD
Mob 0419 707 166 INSTALL 9 PILLARS, 441m OF 240 AL 4C UG LV CABLE
[email protected]
PROJECT MANAGER DETAILS GAS - CANCELLING LOTS 3 on RP113733 APPROVED DATE: 16/09/2021 AND 7 STREET LIGHTING COLUMNS S4400244
Ventralia Pty Ltd HP GAS - D.A RAL 20/0021 CHECKED: J McKenna
ABN 74 166 366 883
Darren Matthews WATER REFER DBYD LOCAL AUTHORITY Noosa Council DESIGNER: I Lubacheski
This drawing is the property of Auspower Connect Pty Ltd and 2 PEARSONS ROAD
0499 339 155 STORMWATER REFER DBYD UBD REF Map 5 A-20 PHONE: 0419 707 166
must not be used, retained or copied without written permission
COOROY 4563 ISSUE NO. A SHEET 1 OF 4 A1
[email protected] SEWER REFER DBYD PEGGED On Request ISSUE DATE: 14/09/2021