1. CONCRETE GRADE Fc' = 32 mPa
ALL REINFORCEMENT N16-250 EF TYP. UNO 2. REINFORCEMENT STEEL:
RS1 ABBREVIATIONS FOR STEEL GRADE AND TYPE: - "N" -
GRADE D500N DEFORMED BAR TO AS/NZS 4671.
RS2 REINFORCEMENT IS REPRESENTED DIAGRAMMATICALLY AND
NOT NECESSARILY SHOWN IN TRUE PROJECTION.
RS3 ENSURE THE CORRECT SPACING OF BARS IS MAINTAINED AND
ALL REINFORCEMENT IS SUPPORTED IN ITS CORRECT
4/E 7.11
POSITION BY APPROVED PLASTIC BAR CHAIRS, SPACERS OR
IL2
X1 5
SUPPORT BARS AT 800 MAX CRS IN BOTH DIRECTIONS.
18
00
RS4 TIE ALL INTERSECTIONS OF BARS WITH 1.25mm MIN DIA.
(3
)
1 ANNEALED WIRE.
- RS5 DO NOT WELD REINFORCEMENT WITHOUT APPROVAL OF THE
ENGINEER.
3. FORMWORK IN ACCORDANCE WITH AS 3610.
A 4. DESIGNED FOR 25 kPa LIVE LOAD, W80 AXLE LOAD TO AS 5100.
- 5. REINFORCEMENT COVER 45 MIN. UNLESS NOTED OTHERWISE.
6. REFER SERVICE AUTHORITY FOR ACCESS HOLE ALTERNATIVE TO BE
1.100
ADOPTED.
N16-250 EW T&B COG AT WALL TYP.
TRAFFICABLE CLASS 'D' RISER AND MANHOLE COVER TO
IPWEA STD DRGS DS-018 & DS-019.
3.000
FSL31.532
1200 (RCBC)
2/1 2100 x
IL27.135
0.350
0.250
PLAN
SCALE 1:20 ON A1
1050mm DIA. MANHOLE
1.474 (PIT 2/1)
1.550 (PIT 3/1)
COG AT WALL TYP.
600 LAP
N16-250 EW T&B
TYP. N16-250 U-BARS TYP.
4/N16-75 ADDITIONAL TOP & BTM FOR
0.250
COG AT WALL TYP.
MAINTENANCE COVER OPENING
0.800
400 LAP
TYP.
2.150
0.600
TYP.
STARTER BARS TO MATCH
800 LAP
800 LAP
MAIN BARS TYP.
TYP.
TYP.
0.775
POUR BREAK TYP.
IL27.155
SFL27.058
DETAIL 1
0.250
SCALE (A1): 1:20 - N16-250 U-BARS
SCALE (A3): 1:40 600 LAP TYP.
0.200 0.250 3.000 0.250 0.200
3.900
PROVIDE 50mm BLINDING
INTERNAL BENCHING TYP. LAYER TYP. (F'c = 10MPa)
SECTION A -
NOOSA COUNCIL
SCALE (A1): 1:20 -
SCALE (A3): 1:40
APPROVED PLAN
OPW18/0343 8 JUN 2019
FILE: 3001-129.dwg DATE: 16-11-2018 USER: CURTIS BOORMAN
XREFS: X-18-001942-TITLE
DESIGN DRAWN CHECK APPROVED DATE STATUS SCALE CLIENT PROJECT DRAWING TITLE
FIRST AMENDMENT DETAILS Calibre Professional Services (QLD) Pty Ltd
ISSUE CB CB SD SP 16.04.19
FOR APPROVAL Level 3, 16 Innovation Parkway BLUE CARE SUNRISE BEACH STORMWATER DRAINAGE
A Birtinya QLD Australia 4575
A
M B NOT FOR CONSTRUCTION 0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
Telephone 07 5314 2520
Facsimile 07 5314 2522
RETIREMENT LIVING & STRUCTURAL DETAILS
E
N
D
C
D
APPROVED SCALE 1:20 (A1) SCALE 1:40 (A3) AGED CARE PITS 2/1 & 3/1
M
E BY: SHAUN PILCHER RPEQ 14593 DISCLAIMER
PROJECT No. DRAWING No. REVISION
E
N ALL DIMENSIONS TO BE CHECKED ON SITE BY CONTRACTOR
F
T
S
G SIGN: DATE: 16.04.2019
C calibregroup.com PRIOR TO CONSTRUCTION. USE WRITTEN DIMENSIONS ONLY,
DO NOT SCALE.
18-001942 3001-129 -