                                         Facsimile Transmission
                                    File No: 2007/2125
                                    Date:      Tuesday, 27 November 2007
                                    Fax No: 07 3893 4088
To:                      BMD Consulting
Attention:               David Polden
                         C/c Paul Pham – Bunnings - 3452 5970
From                     Ron Read, Senior Technical Assessment Officer
Phone No:                07 54495263                   Fax No: 07 54471062
Re:                       Operational works application – Bulk earthworks – Bunnings – 184
                         Eumundi Noosa Road, Noosaville.

Information Request

The following items require attention to assist in the assessment of this application:-

    1.       Please provide the proposed finished surface levels on the plan view.
    2.       Please ensure that provision for the drainage of stormwater runoff from the
             adjoining lot 26 SP151406 is proposed. Parts of lot 26 currently drain towards the
             gully that presently crosses the subject property.
    3.       Please advise how much material will be imported to the site and where it is
             intended to be bought from. Further should it come from elsewhere other than from
             the northern section of this property (Gateway Rise), then a Traffic Management
             Plan is required to be submitted.
    4.        Please provide a wash down facility at the exit from the site. With the type of
             material present on site there is a real need to remove surplus spoil from vehicles
             before they leave the site. The Rene Street/ Eumundi Road roundabout is
             exceptionally busy and there will no time to clean the pavement without disruption
             to the general traffic. Any disruption to the general traffic at this roundabout must be
             avoided.
    5.       Please use sediment fencing or rock checks in lieu of hay bales.
    6.       The sediment basin proposed for Area A to the north is shown to encroach onto the
             Gateway Drive road reserve, which is unacceptable. Further the outlet has been
             directed to Gateway Drive road reserve, when it should be directed to the existing
             culvert under Gateway Drive to the south.

Advice
   1.  Whilst it may be useful to use the existing access at the Rene Street/Eumundi Road
       roundabout, however with the amount of sediments/ mud that are likely to stick to
       the vehicles leaving the site it maybe advantageous to construct an access onto
       Gateway Drive. The new access with a wash down facility is to be an exit only
                           IMPORTANT  AND LEGAL PRIVILEGE NOTICE:
  The information contained in this facsimile message is CONFIDENTAL and may be subject to legal privilege. If you are
 not the intended recipient, you are notified that any use of this message is prohibited. If you received this message in error,
                     please notify us immediately by telephoning 07 54495200 and destroy the original.
       Page:                    1 of 2                                  NSC c:\docume~1\amoore\locals~1\temp\bcl
technologies\easypdf 5\@bcl@d00fb850\@[email protected]
         Original to follow:   No
         NOOSA COUNCIL         9 Pelican Street TEWANTIN (PO Box 141 TEWANTIN 4565)
         Ph 07 5449 5200       Fax 07 5447 1062     [email protected]
Full text of the other 1 page

Page 2

             access to Gateway Drive. Then should any sediment/mud fall on Council roads it
             could be confined to Gateway Drive where sweeping the pavement would be less
             disruptive to the general traffic.
    2.       With regard to the Geotechnical Report by Douglas Partners and the subsequent
             Insitu Ground Improvement report by Land Pac, Council does not have any issues
             with these reports, however there will be a condition in the decision notice that that
             filling and compaction is to be certified by a Geotechnical Engineer, that the works
             have been carried out in accordance with best practice methods.

Yours faithfully


Ron Read
SENIOR TECHNICAL ASSESSMENT OFFICER
LAND DEVELOPMENT




                           IMPORTANT  AND LEGAL PRIVILEGE NOTICE:
  The information contained in this facsimile message is CONFIDENTAL and may be subject to legal privilege. If you are
 not the intended recipient, you are notified that any use of this message is prohibited. If you received this message in error,
                     please notify us immediately by telephoning 07 54495200 and destroy the original.
       Page:                    2 of 2                                  NSC c:\docume~1\amoore\locals~1\temp\bcl
technologies\easypdf 5\@bcl@d00fb850\@[email protected]
         Original to follow:   No
         NOOSA COUNCIL         9 Pelican Street TEWANTIN (PO Box 141 TEWANTIN 4565)
         Ph 07 5449 5200       Fax 07 5447 1062     [email protected]

Used in these records

About this file

File size
11 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

07 2125 info req rread [As Published].pdf · 11 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.