         GENERAL                                                                                             DIMENSIONS/LEVELS                                                                                TIMBER FRAMING & BRACING:                                                                                                 ABBREVIATIONS:
         G1       STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE                                  L1.    CONSTRUCTION SHALL BE SET OUT USING SURVEY BENCHMARKS PROVIDED BY              COUNCIL.   T1    ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS 1720, AS 1684                                          A.C.F.     -   ALL CORES FILLED
                  SPECIFICATION, ARCHITECTURAL, AND OTHER CONSULTANTS' DOCUMENTS.                                                                                                                                   AND THE REFERENCED STANDARDS THEREIN.                                                                               BTM.       -   BOTTOM
                                                                                                             L2.    ALL LEVELS AND SETOUT POINTS ARE SHALL BE CONFIRMED ON SITE BY REGISTERED                                                                                                                                           B.W.       -   BOTH WAYS
         G2       REFER TO THE ARCHITECTURAL DRAWINGS FOR SETOUT. NO DIMENSIONS SHALL BE                            SURVEYOR PRIOR TO CONSTRUCTION. ADVISE ANY DISCREPANCY BEFORE PROCEEDING.                 T2    ALL FRAMING, BRACING AND TIE-DOWN INFORMATION FORMS THE BASIS OF THE                                                CB         -   CONSTRUCTION BREAK
                  OBTAINED BY SCALING FROM DRAWINGS.                                                                                                                                                                STRUCTURES STABILITY DOWN TO FOUNDATIONS. ALTERNATIVE METHODS SHALL                                                 C.O.S.     -   CONFIRM ON SITE
                                                                                                             L3.     DIMENSION STANDARDS:                                                                           ONLY BE ACCEPTED ON APPROVAL OF THE ENGINEER.
                                                                                                                                                                                                                                                                                                                                        D&C        -   DESIGN & CONSTRUCT
         G3       UNLESS OTHERWISE NOTED (UNO), ALL LEVELS ARE IN METRES AND ALL DIMENSIONS ARE IN                  - REDUCED LEVELS, CHAINAGES AND COORDINATES ARE ALL IN METRES.
                                                                                                                                                                                                                                                                                                                                        DWG        -   DRAWING
                  MILLIMETRES.                                                                                      - CIVIL DRAWINGS (SKC SERIES): ALL OTHER DIMENSIONS ARE IN METRES (m).                    T3    PREFABRICATED TIMBER ROOF TRUSSES, PROPRIETARY FLOOR JOIST SYSTEMS
                                                                                                                                                                                                                                                                                                                                        E.F.       -   EACH FACE
                                                                                                                    - STRUCTURAL DRAWINGS (SKS SERIES): ALL OTHER DIMENSIONS ARE IN MILLIMETRES (mm).               AND ALTERNATIVE TIMBER ELEMENTS TO THOSE SHOWN ON THE ENGINEERING
                                                                                                                                                                                                                                                                                                                                        H.D.G.     -   HOT DIP GALVANISED
         G4       THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE STABILITY OF THE                                                                                                                          DRAWINGS ARE TO BE DESIGNED AND CERTIFIED BY THE SUPPLIER'S STRUCTURAL
                  STRUCTURE UNTIL ITS COMPLETION AND SHALL ENSURE THAT NO PART OF THE STRUCTURE              L4.    ALL LEVELS ARE TO AUSTRALIAN HEIGHT DATUM.                                                      ENGINEER. DESIGN AND INSPECTION CERTIFICATES FOR THESE ELEMENTS ARE TO BE                                           Lg.        -   LONG
                  IS OVER-STRESSED BY EXCESSIVE LOADING.                                                                                                                                                            ISSUED TO THE CONTRACTOR FOR LODGEMENT WITH THE LOCAL AUTHORITY.                                                    L.V.       -   LENGTH VARIES
                                                                                                             L5.    DIMENSIONS SHALL NOT BE SCALED FROM DRAWINGS.                                                                                                                                                                       N.S.O.P.   -   NOT SHOWN ON PLAN
         G5       ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE CURRENT VERSION                                                                                                               T4    ALL TIMBER MEMBERS USED ARE TO HAVE A MINIMUM LEVEL OF DURABILITY AS                                                SS         -   STAINLESS STEEL
                  OF THE APPLICABLE STANDARD EXCEPT WHERE VARIED BY THE SPECIFICATION AND/OR                 L6.    DESIGN USES DIGITAL TERRAIN MODEL GENERATED FROM THE SITE SURVEY. SOME                          SPECIFIED IN AS1684.2 - APPENDIX B.                                                                                 TYP.       -   TYPICAL
                  DRAWINGS. APPLICABLE CODES OF PRACTICE INCLUDE BUT ARE NOT LIMITED TO THE                         ELEMENTS ARE INTERPOLATED AND MAY VARY FROM THE ACTUAL SITE CONDITIONS                                                                                                                                              U.N.O.     -   UNLESS NOTED OTHERWISE
                  FOLLOWING:                                                                                                                                                                                  T5    ALL HWD TIMBER SHALL BE SEASONED UNO.                                                                               V          -   VARIES
                  AS 1163        STRUCTURAL STEEL HOLLOW SECTIONS
                  AS 1170        SAA LOADING CODE                                                                                                                                                             T6    ALL TIMBER SHALL BE FREE OF GUM VEINS, KNOTS, SHAKES, CHECKS, WANES AND ANY
                  AS 1554        WELDING OF STEEL STRUCTURES                                                 CONSTRUCTABILITY CONSTRAINTS:                                                                          OTHER IMPERFECTIONS WITHIN CONNECTION ZONES.
                  AS 1664        ALUMINIUM STRUCTURES
                  AS 1684        RESIDENTIAL TIMBER-FRAMED CONSTRUCTION                                                                                                                                       T7    ALL TIMBER FRAMING TO BE MINIMUM H6 TREATED UNO.
                                                                                                             CC1. CONSTRUCTABILITY CONSTRAINTS:
                  AS 1720        TIMBER STRUCTURES
                  AS 2159        PILING CODE                                                                                                                                                                  T8    EXPOSED FRAMING (TIMBER FRAMING THAT MAY BE SUBJECT TO PERIODIC WETTING):
                                                                                                               A)   PROTECT ALL EXISTING INFRASTRUCTURE (EG CULVERT CROSSING, PAVEMENTS,
                  AS 4100        STEEL STRUCTURES                                                                                                                                                                       - SHALL BE EITHER H6 PRESSURE TREATED OR DURABILITY CLASS 1
                                                                                                                    FENCING & ELECTRICAL POLES/WIRES) FROM ANY DAMAGE.
                  AS 4997        GUIDELINES FOR THE DESIGN OF MARITIME STRUCTURES                                                                                                                                         SPECIES (MINIMUM) SAWN TIMBER (UNO)
                  AS 5100        BRIDGE DESIGN
                                                                                                              B)    ALLOW OF LIKELIHOOD OF FLOW WITHIN THE WATERWAY: EXISTING WATERWAY ARE
                  BCA            BUILDING CODE OF AUSTRALIA (NATIONAL CONSTRUCTION CODE)                                                                                                                      T9    WASHERS SHALL BE PROVIDED UNDER ALL NUTS AND BOLT HEADS (EXCEPT CUP-HEAD
                                                                                                                    FLOODED MULTIPLE TIMES PER YEAR. PROTECT CONSTRUCTION EQUIPMENT AND
                                                                                                                                                                                                                    BOLTS) BEARING AGAINST TIMBER AS FOLLOWS:
                                                                                                                    WORKS.
         G6       ANY DISCREPANCY SHALL BE REFERRED TO THE SUPERINTENDENT FOR A DECISION BEFORE                                                                                                                         BOLT SIZE      WASHER
                  PROCEEDING WITH THE WORK.                                                                                                                                                                             <=M12           50X50X3.0mm
                                                                                                             CC2. NO WORK TO COMMENCE ON SITE UNTIL:
                                                                                                                                                                                                                           M16          57X57X4.0mm
                                                                                                                  - OFFICIAL PRE-START MEETING HELD AND PRE-START MEETING MINUTES ISSUED
         G7       ALL PROPRIETARY PRODUCTS NOT DEEMED TO COMPLY WITH THE BCA SHALL HAVE                                                                                                                                    M20          65X65X5.0.mm
                                                                                                                  - CONTRACTOR'S MANAGEMENT PLANS SUBMITTED (SITE, TRAFFIC, ENVIRONMENT,
                  THIRD-PARTY CERTIFICATION WITH RELEVANT TESTING AND SIGN-OFF BY AN RPEQ ENGINEER.                                                                                                                      >M20           75X75X6.0mm
                                                                                                                  SAFETY) FOR SUPERINTENDENT'S REVIEW.
                  PROPRIETARY PRODUCTS INCLUDES PREFABRICATED TRUSSES, LIGHT-GAUGE STEEL
                  FRAMING, FLOORING PRODUCTS, RECYCLED TIMBER AND PLASTICS, BALUSTRADES, SCREENS,                                                                                                             T10   X….. INDICATES M12DIA ANCHOR ROD/BOLT
                  SHADE FABRICS, JOINERY, PARTITIONS AND OPERABLE WALLS.

         G8       REFER TO ARCHITECTS DRAWINGS FOR DETAILS OF ALL GROOVES, FILLETS, HOBS, DRIP
                                                                                                             DRIVEN PILES:                                                                                    T11   [X]….. INDICATES M16DIA ANCHOR ROD/BOLT

                  GROOVES AND THE LIKE.                                                                                                                                                                       T12   SB…. INDICATES STRAP BRACE ROOF BRACING FIXED TO TOP OF EACH JOIST WITH 2
                                                                                                             P1.    PILES SHALL BE CONSTRUCTED IN ACCORDANCE WITH AS2159.                                           SCREWS. BEND STRAP BRACING OVER AT ENDS, FIX WITH 2 SCREWS TO TOP OF JOIST
         G9       GIVE AT LEAST 24 HOURS NOTICE OF AN INSPECTION BEING REQUIRED FOR :                                                                                                                               AND 4 SCREWS TO SIDE FACE OF SUPPORTING MEMBER. ALL ROOFS TO BE BRACED.
                                                                                                             P2.    CONSTRUCTION CONSTRAINTS:      AVOID LOADING EXISTING REVETMENT WALLS.
                  - PILING
                  - JETTY FRAMING (TIMBER)                                                                                                                                                                    T13   ALL FASTENERS ARE TO BE GRADE A4-70 STAINLESS STEEL IN ACCORDANCE WITH
                                                                                                             P3.    DESIGN LOADS: PILES TO ACHIEVE GEOTECHNICAL CAPACITIES (VERTICAL &                              ISO-3506-1. EXTERNAL ANCHORS WHERE SUBJECT TO SALT AIR SHALL BE STAINLESS
                  - BRACING AND TIE DOWN
                                                                                                                    HORIZONTAL) SHOWN ON THE DRAWINGS
                                                                                                                                                                                                                    STEEL A4-70:
         G10      ALL FABRICATION SHOP DRAWINGS SHALL BE PROVIDED TO THE ENGINEER FOR REVIEW AND                                                                                                                         -SCREWS TO BE NO.14 TYPE 17 WITH 50MM EMBEDMENT (UNO)
                                                                                                             P4.    REQUIRED PILE POSITION TOLERANCES:
                  COMMENT IN A3 HARDCOPY OR PDF FORMAT.                                                                                                                                                                  -ALL JOIST HANGERS, FRAMING ANCHORS, TRIPLE GRIPS AND THE LIKE, SHALL BE
                                                                                                                                                                                                                         STAINLESS STEEL. TO BE MANUFACTURED BY PRYDA OR APPROVED
                                                                                                                    PLAN POSITION: +/- 50mm AT UNDERSIDE OF EACH GROUND BEAM.
         G11      ABBREVIATIONS (GENERAL):                                                                                                                                                                               EQUIVALENT, WITH 5 NO. 2.8mm DIA X 30MM
                                                                                                                    PILE VERTICALITY:
                  NTS      NOT TO SCALE                                                                                                                                                                                  NAILS EACH LEG MINIMUM. INSTALL AS PER MANUFACTURERS SPECIFICATION.
                                                                                                                    - WITHIN 4% FOR ALL PILES
                  UNO       UNLESS NOTED OTHERWISE
                  NSOE     NOT SHOWN ON ELEVATION                                                                                                                                                             T14   PROVIDE BLOCKING OVER SUPPORTS AT 1800 MAX CRS IN ACCORDANCE WITH AS 1684
                                                                                                             P5.    PILE TOE LEVELS ON THE DRAWINGS ARE ESTIMATED LEVELS. ACTUAL TOE LEVELS
                  NSOP     NOT SHOWN ON PLAN                                                                                                                                                                        FOR TIMBER BEARERS AND JOISTS WITH D/B >= 4.
                                                                                                                    SHALL BE DETERMINED DURING CONSTRUCTION BY AN RPEQ-CERTIFIED
                  TYP      TYPICAL
                                                                                                                    GEOTECHNICAL ENGINEER.
                  (O)      OVER                                                                                                                                                                               T15   FOR JOISTS WITH SPAN >3000 AND BOTTOM OF JOIST UNRESTRAINED BY CEILING
                  (U)       UNDER                                                                                                                                                                                   DIAPHRAGM:
                                                                                                             P6.    DO NOT FOUND PILES HIGHER THAN TOE LEVELS ON DRAWINGS, UNLESS APPROVED BY
                  CRS      CENTRES                                                                                                                                                                                       -PROVIDE 1 ROW OF BLOCKING BETWEEN EACH JOIST AT
                                                                                                                    BOTH THE SUPERINTENDENT AND THE GEOTECHNICAL ENGINEER. THE
                  NOM      NOMINAL                                                                                                                                                                                            MIDSPAN FOR SPANS < 4200mm
                                                                                                                    SUPERINTENDENT SHALL SEEK ADVICE FROM THE DESIGN ENGINEER AS REQUIRED.
                  CFW      CONTINUOUS FILLET WELD                                                                                                                                                                        -PROVIDE 2 ROWS OF BLOCKING BETWEEN EACH JOIST AT
                                                                                                                                                                                                                              THIRD POINTS FOR SPANS >4200mm


        DESIGN CRITERIA                                                                                      ALUMINIUM:                                                                                       T16   FIXING LOCATIONS TO BE FIXED ACCORDING TO THE FOLLOWING MINIMUM PACINGS
                                                                                                                                                                                                                    (D = FIXING SHANK DIA. IN mm):
                                                                                                                                                                                                                    BOLTS       4D  EDGE DISTANCE TO BOTH EDGES IN DIRECTION OF SHEAR LOAD
         DC1 THE STRUCTURAL ELEMENTS HAVE BEEN DESIGNED FOR THE FOLLOWING LIVE LOADS                         A1.    ALL WORKMANSHIP AND MATERIALS SHALL COMPLY WITH BEST PRACTISE ALUMINIUM                                    5D   PITCH BETWEEN BOLTS
             IN ACCORDANCE WITH AS 1170.1: LIVE LOAD REDUCTIONS ARE NOT APPLICABLE.                                 FABRICATION AND THE CURRENT AUSTRALIAN STANDARD AS 1664.                                                   5D   EDGE DISTANCE FROM END OF ELEMENT
             ELEMENT           UDL         CONCENTRATED                                                      A2.    ALUMINIUM SECTIONS SHALL COMPLY WITH AS 1734, AS 1886 OR AS 1867.                                          13D MINIMUM OVERALL ELEMENT DEPTH
             DECK               2.0kPa     2.7KN                                                             A3.    ALL WELDING SHALL COMPLY WITH AS 1665.
                                                                                                             A4.    ALL WELDING SHALL BE CARRIED OUT USING ARGONGAS SHIELDING. WELD
         DC2 WIND LOADS HAVE BEEN DETERMINED IN ACCORDANCE WITH AS 1170.2 BASED ON:                                                                                                                           MINIMUM SPACING, EDGE & END DISTANCES FOR NAILS AND SCREWS
                                                                                                                    CONSUMABLES SHALL BE COMPATIBLE WITH BOTH PARENT ALLOYS IN ACCORDANCE
             IMPORTANCE LEVEL            2                                                                          WITH AS AS 1665. FOR 6063-T6 USE 4043 FILLER WIRE. PLATE-TO-EXTRUSION ALLOYS
             REGION                      B                                                                                                                                                                                                                                                 MINIMUM DISTANCE
                                                                                                                    SHALL BE WELDED USING APPROPRIATE FILLERS IN ACCORDANCE WITH WTIA
             ULTIMATE WIND SPEED         51 m/s                                                                     TECHNICAL NOTES WHERE NOT COVERED BY AS 1665.
             SERVICEABILITY WIND SPEED   39.0 m/s                                                                                                                                                              SPACING TYPE                               HOLES FOR                         HOLES FOR
                                                                                                             A5.    ALL WELDS SHALL BE A MINIMUM 5mm CONTINUOUS FILLET WELD ALL ROUND,
             TERRAIN CATEGORY            1.5                                                                                                                                                                                                              NAILS NOT                         NAILS PREBORED    SCREWS
                                                                                                                    UNLESS NOTED OTHERWISE.
                                                                                                                                                                                                                                                          PREBORED                          TO 80% DIA.
                                                                                                             A6.    ALUMINIUM EXTRUSIONS SHALL BE STRUCTURAL GRADE ALLOY:- EXTRUSIONS 6063-T6
         DC3 EARTHQUAKE LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 1170.4 BASED                                                                                                                         END DISTANCE                                  20D                                  10D          10D
                                                                                                                    UNLESS NOTED OTHERWISE.
             ON:                                                                                                                                                                                               EDGE DISTANCE                                  5D                                   5D           5D
                                                                                                             A7.    ALUMINIUM PLATE IS TO BE WROUGHT GRADE ALLOY 5083 H116.
             ACCELERATION COEFFICIENT    0.06                                                                                                                                                                  ALONG-GRAIN SPACING                           20D                                  10D          10D
                                                                                                             A8.    ALL STEEL AND STAINLESS STEEL BOLTS AND ALL OTHER FIXINGS MUST BE ISOLATED
             SITE FACTOR                 1                                                                                                                                                                     CROSS-GRAIN SPACING                           10D                                   3D           3D
                                                                                                                    FROM ALUMINIUM USING NYLON OR SIMILAR APPROVED PACKERS/GASKETS, AND
             IMPORTANCE LEVEL            1                                                                          WASHERS WITH SHANK COLLARS.
             STRUCTURE TYPE                                                                                  A9.    SHOP DETAIL DRAWINGS ARE TO BE SUBMITTED TO THE ARCHITECT AND ENGINEER
             DESIGN CATEGORY             EDC1                                                                       FOR REVIEW. APPROVAL IS TO BE OBTAINED FROM THE COUNCIL, THE ARCHITECT AND
                                                                                                                    THE ENGINEER, PROIR TO COMMENCING FABRICATION.
         DC4 FIRE RESISTANCE LEVELS OF STRUCTURAL ELEMENTS HAVE BEEN TAKEN AS FOLLOWS:
             ELEMENT        FRL (mins)
             COLUMNS        -/-/-
             BEAMS          -/-/-                                                                            TEMPORARY WORKS:
             WALLS         -/-/-

         DC5 DETERMINATION OF DESIGN LOADING FOR NON-STRUCTURAL ELEMENTS SUCH AS                             T1.    MAINTAIN THE WORKS IN A SAFE CONDITION. ENSURE STRUCTURES ARE NOT
             CEILING AND CLADDING SYSTEMS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR                             OVER-STRESSED AT ANY TIME. TEMPORARY ROAD SURFACES SHALL BE TRAFFICABLE
                                                                                                                    AT ALL TIMES. POTHOLES ETC SHALL BE MONITORED AND REPAIRED.
         DC6 FLOOD LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 5100 WITH NOMINAL                       T2.    CONTRACTOR'S RPEQ TO CERTIFY DESIGN AND CONSTRUCTION FOR TEMPORARY
             FLOOD VELOCITY TO BE CONFIRMED BY HYDRAULIC REQUIREMENTS AS FOLLOWS:                                   WORKS: STRUTS, PROPPING, FORMWORK STRIPPING AND PROPPING PROCEDURES, TIE
             -V100 = 1m/s.                                                                                          BACKS, EXCAVATION SHORING, PROTECTION WORKS, DE-WATERING SYSTEMS,
                                                                                                                    FORMWORK, EARLY LOADING OF STRUCTURES AND THE LIKE.




                                                                                                                                                                                                                                                                                                                                                                               CONSTRUCTION ISSUE
© THIS DRAW ING IS                                                                                           ASSOCIATED CONSULTANT:                                CLIENT:                                                                                                                  PROJECT:                          DRAWING TITLE:

                                                                                                                                                                                                                           Long View
PROTECTED UNDER
COPYRIGHT IN ACCORDANCE
WITH AGREEMENT BETW EEN
LODESTAR MERIDIAN PTY LTD
                                                                                                                   NOOSA JETTY                                           GRAEME AND SUZANNE                                                                                                       PROPOSED NEW JETTY                               NOTES SHEET                                          21.101-013
T/AS LONG VIEW
CONSULTING ENGINEERS
AND THE CLIENT AS NAMED                                                                                             SERVICES                                                  CUTLER                                L      Consulting Engineers Pty Ltd                                                                                                                                             JOB No.
HEREIN. EXCLUSIVE USE IS
GRANTED UNDER THE                                                                                                                                                                                                   V      Lodestar Meridian Pty Ltd T/as Long View Consulting Engineers
AGREEMENT ONLY FOR THE
PROJECT. THIS DRAWING
                                                                                                                                                                                                                           Post:
                                                                                                                                                                                                                           ABN:
                                                                                                                                                                                                                                     PO Box 963 Cooroy QLD 456
                                                                                                                                                                                                                                     87 711 552 832                                                     11 MASTHEAD QUAY   DRAWN:
                                                                                                                                                                                                                                                                                                                           Author
                                                                                                                                                                                                                                                                                                                                      CHECKED: APPROVED:
                                                                                                                                                                                                                                                                                                                                      SAB                                                             S002            A
SHALL NOT BE                                                                                                                                                                                                               Mobile: 0414 681 676
CONSTRUCTED UNLESS
DESCRIBED AS
                            A     CONSTRUCTION ISSUE                             07/04/25   SAB     FJM                                                                                                                    Email: [email protected]
                                                                                                                                                                                                                           Internet: www.longviewconsulting.com.au
                                                                                                                                                                                                                                                                                                         NOOSAVILLE 4566   DESIGNED: CHECKED: RPEQ 19951 DATE:        SCALE:
                                                                                                                                                                                                                                                                                                                                                                      AS NOTED - A1 ORIGINAL SIZE   DRAWING No.   REVISION.
"CONSTRUCTION ISSUE".       REV   DESCRIPTION                                     DATE      DRAWN APPROVED                                                                                                                                                                                                                 Designer   FJM                  07/04/25
Log in to download the original file

21.101-013_11 Masthead Quay Jetty_[C1].pdf · 1.6 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.