UPDATED DA - Attachment 6 - Bushfire Management Plan
Plans and drawings: the text below has words only, no drawings.
Very large file (28.4 MB): may take a few minutes to open.
9
the State as a bushfire hazard using a with that BVG vegetation structure class,
methodology developed by the provided in Figure 16 in the Bushfire
Commonwealth Science, Industry, Research Resilient Communities, Technical Reference
Organisation (CSIRO) bushfire scientists lead Guide for the State Planning Policy Natural
by Justin Leonard. Hazards, Risk and Resilience – Bushfire of
October 2019’.
The FFDI values that have been mapped and
used in the current bushfire hazard mapping The Qld Fire Department Catalyst Redi-Portal
has taken into account the projected changes maps the following bushfire characteristics
to the FFDI values into the future years. around the Doonan Waste Management
Centre administration and recycling and
The two documents are: - service areas (see Figure 8);
Leonard, J., Newnham, G., Opie, K., and FFDI – 48
Blanchi, R. (2014) A new methodology for VHC 9.1 Moist to dry eucalypt open
state-wide mapping of bushfire prone forests on coastal lowlands and ranges.
areas in Queensland. CSIRO, Australia. VHC9.1 is attributed with a Surface fuel
And load of 21.0t/ha and a total fuel load of
Leonard, J., Opie, K. (2017) Estimating 24.2t/ha
the potential bushfire hazard of VHC 29.3 Heathlands and associated
vegetation patches and corridors. CSIRO, scrubs and shrublands. VHC 29.3 is
Australia. attributed with a surface fuel load of
14.5t/ha and a total fuel load of 20.1t/ha.
The 2014 methodology and adaption by the
Queensland Fire Department (formally the Table 1 below calculates the minimal
Qld Fire and Emergency Service) has used separation distance that achieves a Radiant
the Qld Herbarium’s Broad Vegetation heat flux of 29kW/m2.
Groups (BVG) at 1:2m mapping scale along
Table 1 – Flamesol method Radiant heat flux calculation
Doonan Waste Management Centre - Minimum Distance Calculator - AS3959-2018 (Method 2)
(Calculated October 7, 2024, 6:50 pm (MDc v.4.9))
Inputs Outputs
Fire Danger Index 48 Rate of spread 1.25 km/h
Vegetation Forest Flame length 11.04 m
classification
Understorey fuel 21 t/ha Flame angle 53.5 °, 63.5 °, 72.5 °, 77.5 °, 78.5
load ° & 84.5 °
Total fuel load 24.2 t/ha Elevation of receiver 4.35 m, 4.83 m, 5.1 m, 5.16 m,
5.13 m & 4.79 m
Vegetation height n/a Fire intensity 15,654 kW/m
Effective slope .5 ° Transmissivity 0.879, 0.863, 0.841, 0.816, 0.803
& 0.736
Site slope .5 ° Viewfactor 0.5971, 0.4385, 0.2966, 0.2007,
0.1633 & 0.0445
Flame width 100 m Minimum distance to < 40 9.1 m
kW/m²
RFA24-059 – Noosa Land Fill and Waste Management Facility – Bushfire Management Plan
Rob Friend & Associates Pty Ltd 10th of October 2024