Project No. PG-2096                                                                                                    Page | 5
December 2022
Ref: PG-2096, 2022-11-03, GR VER 1
Keith & Jeannette Ince – Geotechnical Stability Assessment - Proposed Residence, 22 Arakoon Crescent, Sunshine Beach




           Density testing should be carried out to check the standard of compaction
            achieved and the placement moisture content. The frequency and extent of
            testing should be as per guidelines in AS.3798-2007.
           All earthworks operations should be performed under Pacific Geotech’s
            supervision, in general accordance with the requirements of AS3798.

6.0 SITE CLASSIFICATION

Site investigation and laboratory test results indicate the development site would be
classified Class S in accordance with AS 2870-2011 'Residential Slabs and Footings',
from a reactivity perspective.

It is recommended that the readers satisfy themselves that the use of AS 2870-2011 is
applicable for the proposed design and the above site classification re-confirmed
following the completion of the bulk earthworks operation.

7.0 BUILDING FOUNDATIONS

Foundations

In order to provide a uniform and stable foundation and due to the site stability
issues, it is recommended a deepened foundation, incorporating either
appropriately founded pad footings or piers founded into medium dense or better
sands be adopted for the proposed constructions. Pad footings should socket a
minimum depth of 0.9m into the medium dense or better sands and piers should
found a minimum of 1.5m into the medium dense or better sands, if adopted.

Lateral Forces

In view of the global stability in the area, sloping natural terrain and the presence of
loose sands, it is recommended that all footing systems be designed to
accommodate forces due to potential soil creep within the surficial fill strata.

The potential lateral force due to creep in the soil strata may be determined from
the following:

Force                  =           1.5KpH2D

Where Kp               =           2.5

         =           Soil Density=20kN/m3

            H          =           Depth of sands, a depth of up to 2.8m was indicated in
                                   the boreholes. Final depth subject to further
                                   geotechnical assessment at time of pier excavations.
            D          =            Footing/Pier Width (m) - perpendicular to slope

Used in these records

About this file

File size
1.8 MB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Geotech Report.pdf · 1.8 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.