                                                                                                                                                                                                                                                                                                                                                                   GENERAL NOTES




                  lot 45 on N21844
24 wesley court, noosa heads 4567                                                                                                                                                                                                                                                                                                                                  TIMBER FRAMING AND CONSTRUCTION
                                                                                                                                                                                                                                                                                                                                                                   1. ALL CONSTRUCTION TO BE IN ACCORDANCE WITH
                                                                                                                                                                                                                                                                                                                                                                   THE AUSTRALIAN DOMESTIC BUILDING CODE.
                                                                                                                                                                                                                                                                                                                                                                   2. ALL TIMBER FRAMING TO BE IN ACCORDANCE WITH
                                                                                                                                                                                                                                                                                                                                                                   AS 1684.2 2010 RESIDENTIAL TIMBER FRAMING MANUAL.
                                                                                                                                                                                                                                                                                                                                                                   3. PINE FRAMING TO BE MINIUMUM STRESS GRADE
                                                                                                                                                                                                                                                                                                                                                                   MGP 10/MGP12
                                                                                                                                                                                                                                                                                                                                                                   4.HARDWOOD FRAMING TO BE MINIMUM STRESS
                                                                                                                                                                                                                                                                                                                                                                   GRADE F14 & MINIMUM JOINT GROUP J2.
                                                                                                                                                                                                                                                                                                                                                                   5. TIMBER FOR TRUSSES TO BE MINIMUM JOINT GROUP JD4.
                                                                                                                                                                                                                                                                                                                                                                   6. TRUSSES TO BE FIXED IN ACCORDANCE WITH MANUF.
                                                                                                                                                                                                                                                                                                                                                                   SPECIFICATIONS ALL OTHER FIXINGS TO BE IN
                                                                                                                                                                                                                                                                                                                                                                   ACCORDANCE WITH AS 1684.2 2010
                                                                                                                                                                                                                                                                                                                                                                   7.LAMINATED BEAM SIZES BASED ON HYNEBEAM SPAN
                                                                                                                 3070                                                                                                                                                                                                                                              TABLES WHERE OTHER BRANDS ARE USED, SIZES TO
                                                                                                                                                                                                                                                                                                                                                                   BE CONFIRMED WITH MANUFACTURERS SPECIFICATIONS.
                                                                                                 proposed powder coated                                                                                                                                                                                                                                            8. ALL DIMENSIONS TAKE PRECEDENCE OVER SCALES
                                                                                                 aluminium framed structure +                                                                                                                                                                                                                                      9. BUILDER AND TRADES ARE TO CONFIRM ALL
                                                                                                 tinted glass sheeting over                                                                                                                                            proposed structural aluminium                                                               MEASUREMENTS, DETAILSAND SPECIFICATIONS PRIOR TO
                                                                                                 painted black                                                                                                                  existing upper                         powder coated pergola                                                                       SETOUT AND ORDERING OF MATERIALS
                                                                                                                          1085                                                                                                  floor                                  as per engineers design                                                                     10. ANY ERRORS ARE TO BE ADDRESSED TO THE DESIGNER
                                                                 existing rafters
                                                                                                                                                                                                                                                                                                                                                                   AS NO RESPONSIBILITY WILL BE TAKEN AFTER




                                                                                                                                                                                                                                                                            150
                                                                                                                                                                                                                                                                                                                                                                   CONSTRUCTION HAS COMMENCED
                                                                                                                                                                                                                                         2335                  1695                                                                                                11. ALL TRADES ARE TO CONFORM WITH THE
                                                                      5350                                                                  100x100 shs post                                                                                                                                                                                                       CURRENT AUSTRALIAN STANDARDS RELATING TO HIS OR




                                                                                                                                                                                                                                                                                                                               from natural ground line
                                                                                                                                            in line with master
                                                                              2790

                                                                                                                                                                                                                                                                                                                                                                   HER OWN WORK




                                                                                                                                                                                                                                                                                                                               in line with structure
                                                                                                          2540



                                                                                                                        2540




                                                                                                                                                                                                                                        2540




                                                                                                                                                                                                                                                                            2540
                                                                                          2400




                                                                                                                                                                                                                         2400
                                                                                                                                            suite wall behind                                                                                                                                                                                                      12. TERMITE PROTECTION TO BE PROVIDED AS PER AS




                                                                                                                                                                                                                                                                                                                        3790
                                                                                                                                                                                                                                                                                                                                                                   3660.1.2000




                                                                                                                                                                                                                                                                1200
                                                                                                                                                 deck extension                                                                                                                            balustrading as per
                                                                                     existing         existing deck                              (cantilevered)                                                                                existing deck                               aus standards
                                                                                                                                                                                                                                                                                                                                                                   DOMESTIC SMOKE ALARMS
                                                                                                                                                                                                                                                                                                                                                                   1. ALL BEDROOMS AND HALLWAYS ARE TO BE INSTALLED




                                                                                                                                                                                                                                                                            1100
                                                                                                                                                                                                                                                                                                                                                                   WITH PHOTO ELECTRIC SMOKE ALARMS IN ACCORDANCE
                                                                                                                                                                                                                                                                                           proposed aluminium                                                      WITH BUILDING FIRE SAFETY LEGISLATION AMENDMENT
                                                       Section 1                             existing height underside of
                                                                                             covered deck
                                                                                                                                           950                                                                                                                                             framed sliding gate under                                               REGULATION 2016
                                                                                                                                                                                                                                                                                                                                                                   2. SMOKE ALARMS MUST BE POSITIONED IN ACCORDANCE
                                                                                             proposed to suit in line
                                                                                                                                                                                                                                                                                                                                                                   WITH AS 1670.6 - 1997 FIRE DETECTION, WARNING, CONTROL
                                                                                                                                                                                                                                                                                                                                                                   AND INTERCOM SYSTEMS.
                                                                                                                                                                                                                                                                                                                                                                   3. DEVICES MUST BE INTERCONNECTED AND HARD
                                                                                                                                                                                                                                                                           Section 2                                                                               WIRED (EXISTING DWELLINGS ONLY) THAT CANNOT BE
                                                                                                                                                                                                                                                                                                                                                                   REMOVED FROM DEVICE
                                                                                                                                                                                                                                                                                                                                                                   4. ALARMS TO BE INSTALLED IN ALL HALLWAYS AND
                                                                                                                                                                                                                                                                                                                                                                   BEDROOMS TO EXISTING RESIDENCES
                                                                                                                                                                                                                                                                                                                                                                   S INDICATES THE LOCATION OF WIRED SMOKE ALARMS

                                                                                                                                                                                                                                                                                                                                                                   GLAZING
                                                                                                                                                                                                                                                                                                                                                                   1. DOOR AND WINDOW SCHEDULE IS INDICATIVE ONLY AND
                                                                                                                                                                                                                                                                                                                                                                   SUBJECT TO CONFIRMATION UPON SITE MEASURE
                                                                                                                                                                                                                                                                                                                                                                   2. OBSCURE WINDOW NOTATION REFERENCE ONLY, CLIENT
                                                                     aluminium powdercoated pergola                                                                                proposed aluminium                                                                                                                                                              TO CONFIRM WITH BUILDER AND WINDOW SUPPLIER FOR
                                                                     + tinted glass sheets over                                                                                    angle blade framed screen                                                                                                                                                       PRIVACY OPTIONS
                                                                     in line with existing floor                                                                                   details + installation
                                                                     over as per engineers design                                                                                  as per manufacturers specifications                                                                                                                                             ELECTRICAL AND ENERGY EFFICIENCY
                                     existing master
                                                                                                                                                                                                                                                                                                                                                                   1. ELECTRICALS TO BE CONFIRMED BY OWNER/BUILDER
                                     pavillion                                                                                        existing upper floor
                                                                                                                                                                                                                                                                                                                                                                   AND ELECTRICIAN, PROPOSED PLAN IF REQUESTED
                                                                                                                                                                                                                                                                                                                                                                   INDICATIVE ONLY
                                                                                      5680                                                       proposed timber




                                                                                                                                                                                                                                                                                   boundary line
                                                                                                                                                 frame in line with                                                                                                                                                                                                DOWNPIPES
                                                                                                                                                 existing brick wall                                                                                                                                                                                               ALL LOCATED DOWNPIPES INDICATIVE ONLY AND
                                                                                                                               2650




                                                                     100x100 shs post pergola
                                                                     details tie down as per engineers design+                                   to propose bbq bench                          existing boundary fence                           existing       existing garden                                                                                    CONFIRMED AT TIME OF ROOFING CONSTRUCTION
                                                                     manufacturers specifications                                                                                                                                                               + deck                                                                                             AND COMPLIANCE
                                                                                                                                                                                                                                                 master
                                                                   existing deck           proposed deck extension                               existing deck                                                                                   pavillion                         0                                                                      10000


                                                                                                                                                                                                                                                                                                                       proposed jetty
                                                                                                        deck joist system as

      Section 3                                                                                         per engineers design                                            existing slab



                                                                                                                                                                                                                                                                                             deck joist system + concrete pilings
                                                                                                                                                                                                                                                                                             details as per jetty specialists specifications
                                                                                                                                                                                                                                                                                             + engineers design                                                   Section 4




                                                                                                                                                                                                                                                                                                                                                                                                              sections
                                NOTE: INSTALLATION OF ALL EXTERNAL MATERIALS BY BUILDER AS PER MANUFACTURERS SPECIFICATIONS AND CERTIFICATION REQUIREMENTS AS OUTLINED BY NCC


                                 PROPOSED:         CLIENT: CATHERINE + BUILDER: NOOSA'S OWN BUILDING                                                                                                                                                MANDY'S DRAFTING ONLY SHEET: 7 of 7 DATE:       ISSUE NO:
                                 EXTENSION + JETTY ROBERT MARTYR       + MAINTENANCE PH: 5474 1906 QBCC:1254229                                                                                                                                     PH: 0403 481 474      SCALE: 1:100 13 JULY 2022 CR-2022-I
                                 NOTE: THESE DRAWINGS TO BE READ IN CONJUNCTION                  NOTE: BUILDER TO CONFIRM SITING AND DIMENSIONS BEFORE CONSTRUCTION
                                 WITH ENGINEERS DRAWINGS                                         RESPONSIBILITY LIES THERE WITH

Used in these records

About this file

File size
1.5 MB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Proposed plans.pdf · 1.5 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.