Slope Stability - lindsays
NOTES d) Design - Design suitable for sites up to and including Class H (AS2870-2011)
1. STRUCTURAL - If pool is located in fill or aboveground refer to Structural Engineer.
a) Concrete - F'c = 25MPa at 28 days. 32MPa if within 1km of coastline - Drawing not to be used for pools in Exposure Classification C (AS2783)
- Concrete shall comply with AS2783. - Walls have not been designed for cantilever walkways. LINDSAY CONSULTING PTY LTD
LINDSAY CONSULTING PTY
- Concreting shall be carried out in one continuous operation by pneumatic spraying process.
LTD
2. CONSTRUCTION
- Shade concrete and keep moist for 7 days. a) Construction shall comply with AS2783. RPEQ 4928
- Exposure Classification (AS2783) - B2. OFF. 2C/82 PARKER STREET, MAROOCHYDORE PH 54 792 118
3. GENERAL THIS DRAWING REMAINS THE PROPERTY OF
b) Reinforcement
- Fy = 250MPa. S12 bars throughout, lap 400 where required. a) Ground water pressure shall be relieved by Hydrostatic valve as shown. LINDSAY CONSULTING PTY LTD AND IS FOR
- Bars shall be tied securely in position. b) Surface water shall be prevented from penetrating down beside pool wall by THE SOLE USE OF THE CLIENT. NO PART
- Cover shall be 65mm to vertical reinforcement to the inside face. grading surrounding areas away from the pool. MAY BE USED IN PART OR WHOLE WITHOUT
c) Security fencing shall be as required by the Local Authority. PRIOR EXPRESS WRITTEN CONSENT OF
c) Foundations - Excavation shall follow contours of pool shape. Where over excavation occurs fill with concrete. d) Finishes to pool surface shall be as detailed by Pool Contractor. LINDSAY CONSULTING PTY LTD
- Foundation material shall be uniform over entire pool base, if not refer to Engineer. e) All hydraulic equipment (eg. pump, filter, hydrostatic relief valve, skimmer box etc.)
- In clay or rocky ground use 75mm thick layer of 20mm nominal gravel under base. shall be as specified by the Pool Contractor
CLIENT AND PROJECT DESCRIPTION
- Minimium safe bearing capacity - 100kPa
- Pool walls shall be poured against undisturbed natural ground, if not refer to Structural Engineer.
GUY MELDRUM
900 wide x 75 thick slab all round with F52 PROPOSED RESIDENCE
fabric CP or pavers with cement stabilized
A B filling sand. Refer Note 3(b). NO.4 TRISTANIA DRIVE
MARCUS BEACH
300 Total length 16700 MAX 300
Maximium surface area - 100m 2 Finish to Clients or
Contractors requirements
DRAWING TITLE
200 150 Water Level
POOL DETAILS
3 /S12
in bond beam
H
600
Overall depth (D)
H
R/2
2250 MAX
00
R4
SCALES
R/2
R4
100
00
0
20
DIA 200 Anti vortex
200
Unreinforced cutoff wall
cover REQUIRED FOR
20
0
S12 - 200 EW CP Washed gravel to underside (CLASS H2 & E SITES)
of pool, refer Note 1(c)
A
BASE 300 SURVEY DATUM
Earth wire to reinforcement Dia 40 suction line 300
S12 Verticals @ 200 crs
Connect to dwelling earth system to filter (Client option)
Hydrostatic relief valve .
75
S12 Horiz @ 200 crs
300 Varies
75
600
Sump containing
100
crushed rock ASSOCIATED CONSULTANTS
275
275
nominal size 50 mm
Water Level 600 SQ
NOTE
B
500
Where pool wall height (H) exceeds
1400 but less than 1900
H
provide intermediate vertical S12 bars
00
as shown dotted. R4
00
LONGITUDINAL SECTION COPING VARIATION WET EDGE DETAIL
R/2
(ie. S12 bars in this area at 100 c/c)
R4
300 Varies
800 gth
ig ht len
Stra 200
200
H
REVISION LIST
R/2
A BUILDER REVIEW - NOT FOR CONSTRUCTION 25/03/22
R4
00
R4
00
20
0
20
0
SECTION B-B SECTION A-A
Computer File
220061FD.DWG
DRAWING NUMBER SHEET REV.
22-0061-F23 23 A