AA1384_Effluent Report_final

Attached to the e-mail Request for Negotiated Decision Notice REC16/0015.

of 21

Page text shows just the words. Original shows the document exactly as it was published.

Page text read automatically using OCR, there may be inaccuracies

 FEASIBILITY STUDY FOR
  ON-SITE WASTEWATER
TREATMENT AND DISPOSAL



 PROPOSED 2 LOT SUBDIVISION
      LOT 71 MCH2854
     2 DAVID LOW WAY,
   CASTAWAYS BEACH, QLD

            For




      KENLYNN PTY LTD




        AA1384EFF
      SEPTEMBER 2016
            JS/js
Log in to download the original file

AA1384_Effluent Report_final.pdf · 3.9 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 20 pages

Page 2

                                                  2




                                     Document Control
             Version           Parenthood                        Authorised for Issue
  No.       Date          Author          Reviewer             Name       Document Status
  0         26/09/16     Julie Schubert   Paula Duke      Julie Schubert          A




  A - Approval            B – Building Approval           C- Construction   V – Version
  T – For Tender          X - Information                 P – Preliminary


The content of this document is provided in strict commercial confidence. The content of
this document shall not be disclosed to any third party, without the express written authority
of Duke Environmental. Copyright © Duke Environmental 2016.




AA1384EFF
September 2016
JS/js

Page 3

                                                                           3


                                                         TABLE OF CONTENTS
 1.0 INTRODUCTION ........................................................................................................................ 5
     1.1 Preamble .............................................................................................................................. 5
     1.2 Site Location ....................................................................................................................... 5
     1.3 Description of the Proposal .............................................................................................. 5
     1.4 State and Local Government Authority Requirements................................................ 5

 2.0 SITE CHARACTERISTICS ....................................................................................................... 6
     2.1 Site Characteristics ............................................................................................................ 6
     2.2 Topography ......................................................................................................................... 6
     2.3 Site Hydrology .................................................................................................................... 6
     2.4 Geology................................................................................................................................ 6
     2.5 Soil Profile ........................................................................................................................... 7
     2.6 Soil Permeability................................................................................................................. 7
     2.7 Acid Sulfate Soils ............................................................................................................... 7
     2.8 Site Constraints & Opportunities..................................................................................... 7

 3.0 WASTEWATER TREATMENT AND DISPOSAL SYSTEM DESIGN PARAMETERS....... 7
     3.1 Wastewater Treatment and Disposal System ............................................................... 7
     3.2 Wastewater Treatment and Disposal System Design Parameters ............................ 7

 4.0 WASTEWATER TREATMENT AND DISPOSAL AREAS .................................................... 8
     4.1 Vertical & Horizontal Separation Distances ................................................................... 8
     4.2 Protection of Surface and Groundwater Quality........................................................... 9

 5.0 ON GOING MAINTENANCE AND MONITORING ................................................................. 9

 6.0 CONCLUSIONS AND RECOMMENDATIONS....................................................................... 9

 7.0 LIMITATIONS OF THIS STUDY .............................................................................................10

 8.0 CLOSURE ................................................................................................................................10

 9.0 REFERENCES .........................................................................................................................11




AA1384EFF
September 2016
JS/js

Page 4

                                         4




                                 APPENDICES
            APPENDIX A   -         FIGURES & DIAGRAMS
                             -     Drawing DE1384/01
                             -     Drawing DE1384/02
                             -     Drawing DE1384/03
                             -     JFP Consultants Reconfiguration Plan M2683-0-01-C
                             -     Site Borelogs

            APPENDIX B   -         SITE PHOTOGRAPHS




AA1384EFF
September 2016
JS/js

Page 5

                                               5

1.0    INTRODUCTION

       1.1       Preamble

       Duke Environmental has been commissioned by Kenlynn Pty Ltd to assess the
       location and sizing of the current on-site wastewater treatment and effluent disposal
       system in response to Item 2 of the Noosa Council Information Request (Ref:
       REC16/0015) dated 8 July 2016.

       This report has generally been prepared in accordance with AS/NZS 1547:2012
       (On-Site Domestic Wastewater Management), the Environmental Protection
       Regulation 2008, and the Department of Housing and Public Works ‘Queensland
       Plumbing and Wastewater Code’ (2013) (as applicable).

       1.2       Site Location

       The subject site is located at 2 David Low Way, Castaways Beach and is described
       as Lot 71 MCH2854. The site has an area of approximately 9,677m2.

       Refer Drawing DE1384/01 in Appendix A for Subject Site Location.

       1.3       Description of the Proposal

       The proposal consists of an application for Reconfiguration of a Lot (1 into 2 lots).
       We understand the current intent is to retain the existing dwellings, however the site
       plan includes potential building envelopes in the event that dwellings are replaced in
       the future.

       1.4       State and Local Government Authority Requirements

       A number of legislative requirements relate to onsite wastewater treatment and
       disposal systems under Queensland legislation, along with various other standards
       and guidelines that may place constraints on the suitability of the site for onsite
       wastewater disposal.

       Those potentially relevant to the proposed development include:

                Sustainable Planning Act 2009;

                Environmental Protection Act 1994;

                Environmental Protection (Water) Policy 2009;

                Environmental Protection Regulation 2008;

                Plumbing and Drainage Act 2002;

                Standard Plumbing and Drainage Regulation 2003;

                AS/NZS 1547:2012 ‘On Site Domestic Wastewater Management;

                Department of Energy and Water Supply ‘Planning Guidelines for Water
                 Supply and Sewerage’ 2010; and

                Department of Housing and Public Works ‘Queensland Plumbing and
                 Waste Water Code 2013’.




AA1384EFF
September 2016
JS/js

Page 6

                                                6
2.0    SITE CHARACTERISTICS

       2.1       Site Characteristics

       The southern section of the site (proposed lot 2) contains a residential dwelling and
       associated buildings. This lot was observed to be serviced by two (2) septic tanks
       and a grey-water tank. The dwelling is serviced by one (1) system, whilst the other
       system services a detached “amenities” building. Anecdotal evidence from the
       caretaker on site indicates this dwelling contains only one (1) bedroom. Manicured
       lawns surround the dwelling, bordered by dense vegetation. An access track
       provides pedestrian access to the beach.

       Proposed Lot 1 contains a dwelling with a granny flat. A single septic tank and
       disposal system was observed in this area. It is understood this dwelling contains 3
       bedrooms with a single bedroom in the granny flat. Manicured lawns and gardens
       surround the dwelling, bordered by dense vegetation. An access track provides
       pedestrian access to the beach.

       Vegetation surrounding the lawns was observed to be vigorous and comprised of
       native and pest plant species. Ponding was not observed on site and “sewage”
       smell was not detected in the location of the septic tanks or surrounds. However, the
       dwelling on proposed Lot 1 was unoccupied at the time of site assessment.

       2.2       Topography

       The site is undulating, with current dwellings located on flat areas within the site.
       The current dwelling on proposed Lot 1 is located on the high point of the site
       grading down to David Low Way in the west, the beach in the east and a waterway
       in the north. Proposed Lot 2 grades slightly toward David Low Way in the west. A
       depression was observed to the east of the dwelling on this lot from which the
       topography rises before grading down toward the beach.

       Refer to JFP Consultants Reconfiguration Plan M2683-0-01-C included in Appendix
       A for details of site contours.

       2.3       Site Hydrology

                 2.3.1   Surface Water

                 A depression separates the two dwellings with a grade toward the north-
                 west. The site grades generally to the east and north therefore directing the
                 surface flow generally towards the northern boundary.

                 2.3.2   Groundwater

                 A search of the registered groundwater bore database on Queensland
                 Globe indicated one (1) bore within close proximity to the site. This bore is
                 listed as Abandoned and Destroyed but had been advanced to a depth of
                 19.2m.

                 2.3.3   Flood Level

                 Council Flood Hazard Overlay map indicates the development is not within a
                 Flood Hazard Area.

       2.4       Geology

       Desktop analysis of minesonline geology maps for the site indicates soil
       types/geology as Holocene parabolic dune; quartz sand over the majority of the site.
AA1384EFF
September 2016
JS/js

Page 7

                                              7
       A section of Mud, peat; freshwater swamp deposits in coastal areas aged from the
       Quaternary period is located in the north of the site.

       2.5       Soil Profile

       Field sampling carried out by Duke Environmental on 31 August 2016 up to a depth
       of 800mm below surface level indicates that the soil is dominated by sand.

       Refer to Drawing DE1384/03 for location of boreholes and Site Borelogs in
       Appendix A.

       2.6       Soil Permeability

       Soil permeability (Ksat) of >3.0 is estimated from the site soil category of 1 (Gravels
       and sand) (Refer AS1547-2012).

       2.7       Acid Sulfate Soils

       Council Acid Sulfate Soil overlay mapping indicates a section in the north of the lot
       is mapped as Low Potential Acid Sulfate Area 5-20m AHD. This area generally
       correlates with the geology mapped area of mud, peat; freshwater swamps. The
       reconfiguration plan indicates this area of the site is designated for vegetation
       covenant and therefore is also outside of the disposal area.

       2.8       Site Constraints & Opportunities

       The site is mapped within a Coastal Protection Area under the Noosa Plan and is
       located in close proximity to the beach. Wastewater systems will need to be
       maintained and operated in a manner to prevent overflow or discharge to
       surrounding areas. The retention of vegetation under covenant may limit the
       opportunity for a reserve area, however the option exists to replace the soil in the
       treatment area should the need arise.


3.0    WASTEWATER TREATMENT AND DISPOSAL SYSTEM DESIGN PARAMETERS

       3.1       Wastewater Treatment and Disposal System

       The dwelling on proposed Lot 2 is serviced by a septic tank and trench bed system
       to treat on site wastewater. This dwelling is also serviced by a greywater tank and
       has a separate septic tank servicing a detached amenities building. The dwelling on
       proposed Lot 1 appeared to be serviced by a septic tank. As site plans for the
       systems were not available, a licensed plumber was commissioned by the client to
       inspect the systems. The results of the inspection indicate that all systems servicing
       the property do not meet current standards and will require replacement. According
       to the plumbing report there are no active trench bed systems. Septic tanks
       observed on site were contained within the proposed site boundaries of the lot
       which they serve. Refer to Drawing DE1384/03 included in Appendix A for location
       of current tanks.

       3.2       Wastewater Treatment and Disposal System Design Parameters

                 3.2.1   Design Flows

                 Design flows have been calculated for each dwelling, based on a potential
                 for five (5) persons per dwelling (assuming redevelopment).

                 Based on Table H2 of Australian Standard AS/NZS 1547:2012 we have
                 adopted a daily flow of all wastes of 150L/person/day.

AA1384EFF
September 2016
JS/js

Page 8

                                                          8

                    Therefore, assuming 150L/person/day the outflow is calculated as:

                              150L/person/day x 5 persons = 750 L/day

                    In accordance with AS/NZS 1547:2012, the Design Loading Rate (DLR) of a
                    trench and bed system, based on sand (Category 1 soil), primary treated
                    effluent and a conservative rate, is approximately 20mm/day.

                         Therefore, required trench/bed areas for primary treatment = 37.5m2

                    The conservative rate of 20mm/day has been adopted for the primary
                    effluent calculations in accordance with Section L4.1 of AS/NZS 1547/2012
                    and due to the low nutrient retention capacity of sand.

                    However due to the sensitive nature of the surrounding environment (coastal
                    protection area) we recommend advanced secondary treatment, with trench
                    systems designed in accordance with the requirements of AS/NZS
                    1547:2012 to reduce the potential for nutrient runoff. The recommended
                    Design Loading Rate for Category 1 soil with secondary treatment is
                    50mm/d.

                    This would reduce the required trench bed areas to 15m2.


4.0        WASTEWATER TREATMENT AND DISPOSAL AREAS

The information below details the requirements for the siting of on-site wastewater treatment
in accordance with AS/NZS 1547:2012 and the Queensland Plumbing and Wastewater
Code 2013 (QPWC).

           4.1       Vertical & Horizontal Separation Distances

           The on-site sewerage facility shall incorporate measures to ensure that the effects of
           the onsite wastewater systems are contained within the property boundaries
           including, if necessary, the use of set-backs (AS/NZS 1547:2012 Clause 2.4.1(k)).

                                         Table 4.1
                  Recommended horizontal separation distances for subsurface land
                         application areas in accordance with the QPWC

                            Feature                               Recommended Horizontal Separation
                                                                         Distance (metres)

                                                                Up slope           Down slope         Level
      Property boundaries, pedestrian paths and walkways,             2                  4                    2
      recreation areas, footings of buildings and retaining
      walls footings.
      In ground swimming pool                                         6                  6                    6
      In ground potable water tank                                    6*                 6*                   6*
      * Note: For Primary effluent and in accordance with the Noosa Shire Council Planning Scheme Policy 24, distance
      from an in-ground potable water tank must be 15 metres.


           Swimming pools and in ground potable water tanks were not observed on site.




AA1384EFF
September 2016
JS/js

Page 9

                                                    9
        4.2       Protection of Surface and Groundwater Quality

        The on-site sewerage facility shall incorporate measures to control the effects of an
        on-site wastewater system on surface water and groundwater flows and the quality
        of natural waters such that subsequent use of those waters is not impaired or
        compounded (AS/NZS 1547:2012 Clause 2.4.1 (k)).

        The nearest waterbody is located approximately 60m to the north of the dwelling on
        proposed Lot 1 (6m from the northern site boundary). Due to the depth of the
        groundwater at the nearest bore, it is considered unlikely that groundwater will be
        impacted, however trench beds must be designed in accordance with AS/NZS
        1547:2012 to reduce nutrient runoff.

                                          Table 4.2
                 Recommended separation distances for protection of water quality

                              Feature                              Recommended Separation
                                                                  Distance based on treatment
                                                                             level

                                                        Primary       Secondary    Advanced
                                                                                   Secondary
          Top of bank of permanent water course;           50m           30m           10m
          Top of bank of Intermittent water course;
          Top of bank of a lake, bay or estuary;
          Top water level of a surface water source
          used for agriculture, aquaculture or stock
          purposes;
          Easement boundary of unlined open
          stormwater drainage channel or drain.
          Bore or a dam used or likely to be used          50m           30m           10m
          for human and or domestic consumption
          Unsaturated soil depth to a permanent            1.2m         0.6m          0.3m
          water table (Vertically)
          Note:
                   The separation distances are recommended and
                   the local government may upon considering the
                   public health and environmental risks reduce or
                   increase the distances given in the above table.

        We consider the property offers sufficient area to provide the required setback
        distance from the treatment area to the nearest waterway.


5.0     ON GOING MAINTENANCE AND MONITORING

Monitoring and maintenance of the on-site wastewater treatment and disposal system is to
be undertaken in strict accordance with the manufacturer’s recommendations, requirements
of State and Local Governments, and AS/NZS 1547: 2012. For sub-surface application,
once the soil becomes saturated with nutrients, or becomes saline, we recommend the soil
is remediated or replaced or that a reserve wastewater disposal area is commissioned.


6.0     CONCLUSIONS AND RECOMMENDATIONS

In our opinion, we consider that an advanced secondary on-site wastewater treatment and
disposal systems to be suitable and viable for the proposal. We also consider that sufficient
area is available on site for the installation of trench beds whilst complying with required set-
back distances.




AA1384EFF
September 2016
JS/js

Page 10

                                                10
Based on the above assessment we provide the following recommendations, aimed at
mitigating potential environmental impacts associated with the proposal within the study
location and adjacent areas:

         Replacement of systems servicing both proposed allotments with an advanced
          secondary treatment system, for each of the dwellings, that comply with current
          standards and guidelines;

         Systems are to be operated and maintained in strict accordance with the
          manufacturer’s recommendations, and the requirements of AS/NZS 1547:2012
          and/or Local Authority / State Government requirements;


7.0       LIMITATIONS OF THIS STUDY

This study has been tailored to investigate issues at the area of interest, being Lot 71
MCH2854, 2 David Low Way, Castaways Beach, Queensland.

Individual sub-catchments situated above, and below the area of interest, may have
different hydrological / hydraulic influences. Hence, the information contained in this report is
not to be used outside of the subject area.

We consider that the study accurately reflects the conditions for the area of interest, as
detailed in our correspondence to Kenlynn Pty Ltd, and is solely for the use of Kenlynn Pty
Ltd and Noosa Council.

This report is only to be used in full, and may not be used to support objectives other than
those set out herein, except where written approval, with comments, are provided by Duke
Environmental.

Duke Environmental accept no responsibility for the accuracy of information supplied to
them by second and third parties.


8.0       CLOSURE

This report has been undertaken in general accordance with relevant industry standards
and guidelines. Should further information be required please contact our office.


Yours faithfully




Julie Schubert                             Paula Duke
BEnvSc (in progress), CDEC Qld             MEngSc BAppSc(Chem) PGDipEd CEnvP MEIANZ
Environmental Technician                   Director
For Duke Environmental                     For Duke Environmental




AA1384EFF
September 2016
JS/js

Page 11

                                           11
9.0    REFERENCES

       1. AS/NZS 1547:2012 On-Site Domestic Wastewater Management

       2. State of Queensland, 2014. Planning Guidelines for Water Supply and
          Sewerage April 2010, Chapter 6 amended March 2014. Department of Energy
          and Water Supply.

       3. Department of Housing and Public Works ‘Queensland Plumbing and Waste
          Water Code 2011’

       4. Environmental Protection Act 1994

       5. Environmental Protection (Water) Policy 2009

       6. Environmental Protection Regulation 2008

       7. Noosa Council. (2006) Planning Scheme Policy 24 – Effluent Disposal.
          Retrieved from http://www.noosa.qld.gov.au/documents/40217326/40227898
          /psp24_effluent_disposal.pdf.

       8. Plumbing and Drainage Act 2002

       9. Standard Plumbing and Drainage Regulation 2003

       10. Sustainable Planning Act 2009




AA1384EFF
September 2016
JS/js

Page 12

                 APPENDIX


                  A



   FIGURES & DIAGRAMS




AA1384EFF
September 2016
JS/js


[OCR of page images]
 

 

APPENDIX

A

 

FIGURES & DIAGRAMS

 

 

Page 13

                                                                          Site Location




                                                                                                                                                                                             0   40     80        120        160        200m


     Aerial Image sourced from Queensland Globe                                                                                                                                                        SCALE 1:4000 A3


No    Date               Amendment                                                                                                                                         KENLYNN PTY LTD
                                                  Design:    J.S.                  APPROVED                    DOCUMENT STATUS                                   CLIENT:

                                                  Drawn:     J.S.                                                FOR APPROVAL                                    PROJECT: PROPOSED 2 LOT SUBDIVISION

                                                                              ..........................       (Not for Construction)                                                                                Sheet         of
                                                  Date:      26.09.2016                                                                                          AT:       2 DAVID LOW WAY
                                                                                                           Survey By:                                                      CASTAWAYS BEACH                               DRAWING No:
                                                  Checked:   P.M.D.        DATE:     .............                                      T/A Duke Environmental
                                                                                                                                                                                                                         DE1384/01
                                                                                                            Datum: A.H.D.   SIZE   A3   ABN 53 111 368 944       TITLE:    SITE LOCATION

Page 14

                                                                             INDICATIVE EFFLUENT TRENCH



                                                                                                                                                                          0     10     20         30   40   50m
            Base Plan provided by JFP - refer Reconfiguration Plan M2683-0-01-C
            Effluent disposal trench bed areas indicative only and subject to on site
                                                                                                                                                                                     SCALE 1:1000 A3
            confirmation.

No   Date          Amendment                                                                                                                                                  KENLYNN PTY LTD
                                               Design:     J.S.                    APPROVED                    DOCUMENT STATUS                                   CLIENT:

                                               Drawn:      J.S.                                                  FOR APPROVAL                                    PROJECT: PROPOSED 2 LOT SUBDIVISION

                                                                              ..........................       (Not for Construction)                                                                             Sheet   of
                                               Date:       26.09.2016                                                                                            AT:          2 DAVID LOW WAY
                                                                                                           Survey By:                                                         CASTAWAYS BEACH                       DRAWING No:
                                               Checked:    P.M.D.          DATE:     .............                                      T/A Duke Environmental
                                                                                                                                                                                                                     DE1384/02
                                                                                                            Datum: A.H.D.   SIZE   A3   ABN 53 111 368 944       TITLE:       EFFLUENT TREATMENT LOCATIONS

Page 15

                                                                                                                                                                                     LEGEND

                                                                                                                                                                                            Location of existing septic tanks

                                                                                                                                                                                            Borehole number




                                                                                                                                                                                            0    5.0    10         15           20        25m


     Aerial Image sourced from Queensland Globe                                                                                                                                                        SCALE 1:500 A3


No    Date               Amendment                                                                                                                                        KENLYNN PTY LTD
                                                  Design:    J.S.                 APPROVED                    DOCUMENT STATUS                                   CLIENT:

                                                  Drawn:     J.S.                                               FOR APPROVAL                                    PROJECT: PROPOSED 2 LOT SUBDIVISION

                                                                             ..........................       (Not for Construction)                                                                                    Sheet        of
                                                  Date:      26.09.2016                                                                                         AT:       2 DAVID LOW WAY
                                                                                                          Survey By:                                                      CASTAWAYS BEACH                                 DRAWING No:
                                                  Checked:   P.M.D.       DATE:     .............                                      T/A Duke Environmental
                                                                                                                                                                                                                           DE1384/03
                                                                                                           Datum: A.H.D.   SIZE   A3   ABN 53 111 368 944       TITLE:    BOREHOLE LOCATIONS

Page 16

                                                                                                                                        1

                                                                                                                                                                                                                           2



                                                                                                                                                                                                                                                                                                                                      NOTES
                                                                                                                                                                                                                                                                                                                                      (1) This plan was prepared for the purpose and exclusive use of KENLYNN PTY LTD
                                                                                                                                                                                                                                                                                                                                      to accompany an application to NOOSA SHIRE COUNCIL for a Development
                                                                                                                                                                                                                                                                                                                                      Permit to Reconfigure the land described in the plan and is not to be used for any
                                                                                                                                                                                                                                                                                                                                      other purpose or by any other person or corporation.
                                                                                                                                                                                                                                                                                                                                      JFP URBAN CONSULTANTS PTY LTD accepts no responsibility for any loss or
                                                                                                                                                                                                                                                                                                                                      damage suffered howsoever arising to any person or corporation who may use or
                                                                                                                                                                                                                                                                                                                                      rely on this plan in contravention to the terms of this clause or clauses 2, 3, 4, 5
                                                                                                                                                                                                                                                                                                                                      or 6 hereof.

                                                                                                                                                                                                                                                                                                                                      (2) The contours on this plan are approximate and are suitable only for the
                                                                                                                                                                                                                                                                                                                                      purpose of this application. The accuracy of the contours has not been verified
                                                                                                                                                                                                                                                                                                                                      and no reliance should be placed upon such contours for any purpose other than
                                                                                                                                                                                                                                                                                                                                      for the purpose of this application.

                                                                                                                                                                                                                                                                                                                                      (3) The dimensions, areas, size and location of improvements, flood information
                                                                                                                                                                                                                                                                                                                                      (if shown) and number of lots shown on this plan are approximate only and may
                                                                                                                                                                                                                                                                                                                                      vary.
                                                                                                                                                     LEGEND                                                                                                                                                                           (4) The positions of vegetation shown on this plan has been interpreted from
                                                                                                                                                                                                                                                                                                                                      aerial photography and are approximate only.
                                                                                                                                                     SUBJECT SITE                                                                 PROPERTY DESCRIPTION
                                                                                                                                                                                                                                                                                                                                      (5) Safety in Design
                                                                                                                                                                                                                                  PROPOSED LOTS 1 & 2                                                                                 The Urban Design for the layout proposal has been developed to meet the stated
                                                                                                                                                     VEGETATION COVENANT                                                          CANCELLING                                                                                          project brief, as expressed in JFP Urban Consultants Offer for the works, and the
                                                                                                                                                                                                                                                                                                                                      Design Standards stipulated by the Local Authority named on this plan.
                                                                                                                                                                                                                                  LOT 71 ON MCH2854                                                                                   Non-standard design solutions adopted in the preparation of the layout are listed
                                                                                                                                                     INDICATIVE BUILDING ENVELOPE                                                 PARISH OF WEYBA                                                                                     as follows;
                                                                                                                                                                                                                                                                                                                                         · None
                                                                                                                                                                                                                                  COUNTY OF MARCH
                                                                                                                                                                                                                                  TOTAL AREA 9677m² (Deed)                                                                            (6) This plan may not be reproduced unless these notes are included.


                                                                                                NORTH:   SCALE:                                                                                            ISSUES:                                                      TITLE:                                                                                                                                 DETAILS:
                                                                                                                                                                                                                                                                                                                                                                                                                 PROJECT:                STAGE:        PLAN:          ISSUE:
                                                                                                         SCALE: @ A3 1:1000
                               BRISBANE - SUNSHINE COAST - CENTRAL QLD   PLANNERS                        0            10           20           30            40           50           60            70
                                                                                                                                                                                                                                                                         RECONFIGURATION PLAN                                                                                                                    M2683 0                               01             C
                               SUNSHINE COAST                            URBAN DESIGNERS                  SCALE 1:1000 at (A3) size                                                                                                                                                                                                                                                                              SHEET:

                               237-239 Bradman Avenue,                                                   THIS SCALE SHOWN IS ORIGINAL DRAWING SCALE - (A3 SIZE)                                                                                                                                                                                                                                                 1 OF 1
                                                                         SURVEYORS                                                                                                                          C        AMEND BUILDING ENVELOPES        13-09-16   DWW
                                                                                                                                                                                                                                                                         KENLYNN PTY LTD
                                                                                                N




                               Maroochydore Qld 4558                                                     DO NOT SCALE FROM THIS DRAWING - USE ONLY DIMENSIONS PROVIDED - IF IN DOUBT PLEASE ENQUIRE
                                                                                                                                                                                                            B        AMEND COVENANT & ADD BUSHFIRE   14-07-16   DWW                                                                                                                                              FILE:
                                                                         ENGINEERS
                               P 07 5450 3900 W www.jfp.com.au                                                                                                                                                       MAPPING                                                                                                                                                                                    M2683-01C-RP.dwg
C O N S U L T A N T S JFP URBAN CONSULTANTS PTY LTD A.C.N. 050 414 045   LANDSCAPE ARCHITECTS            DESIGNED
                                                                                                         DRAWN
                                                                                                                           GB
                                                                                                                           TJM
                                                                                                                                 CHECKED
                                                                                                                                 APPROVED
                                                                                                                                                  LS
                                                                                                                                                 GB
                                                                                                                                                         DATUM AHD
                                                                                                                                                                                                            A        ORIGINAL                        30-05-16   TJM      2 DAVID LOW WAY, CASTAWAYS BEACH                                                                                                        DATE:
                                                                                                                                                                                                                                                                                                                                                                                                                13th September 2016
                                                                                                                                                         L.A. NOOSA SHIRE COUNCIL                          ISSUE:    DETAILS:                        DATE:      INIT:
                                                                                                                                                                                                                                                                  COPYRIGHT © 2016 JFP URBAN CONSULTANTS PTY LTD. THIS DOCUMENT MAY NOT BE COPIED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS IN PART OR IN WHOLE WITHOUT THE WRITTEN CONSENT OF JFP URBAN CONSULTANTS PTY LTD.

Page 17

JOB NO:                      DE1384                   BOREHOLE NO:                                                          BH1
LOCATION:                    David Low Way, Castaways DATE:
                                                      Beach 31/08/2016
Surface elevation:    approx 20m AHD                           Drill type: Hand Auger
Logged by: Julie Schubert       Checked by:                    Drill method: Auger




                                                                                 Classification Symbol
                                                                 Graphical Log
                   Soil Description                                                                      Field Monitoring    Sample Interval




                                                   Depth (m)
Silty sand - light brown, dry, some gravel        0.0                            ZS

Sand- fine, dry, yellow/brown                     0.2                            S

Sand - fine, slightly moist, yellow/brown         0.4                            S

Borehole terminated - target depth                0.6                            S




AA1384EFF
September 2016
JS/js

Page 18

JOB NO:                        DE1384                  BOREHOLE NO:                                                               BH2
LOCATION:                     David Low Way, Castaways DATE:
                                                       Beach 31/08/2016
Surface elevation:    approx 20m AHD                            Drill type: Hand Auger
Logged by: Julie Schubert       Checked by:                     Drill method: Auger




                                                                                  Classification Symbol
                                                                  Graphical Log
                   Soil Description                                                                            Field Monitoring    Sample Interval




                                                    Depth (m)
Silty sand - light brown, slightly moist           0.0                            ZS                      Shaded area




Silty sand = lgiht grey, slightly moist            0.5                            ZS


Borehole terminated - target depth                 0.8                            ZS




AA1384EFF
September 2016
JS/js

Page 19

JOB NO:                        DE1384                   BOREHOLE NO:                                                          BH3
LOCATION:                      David Low Way, Castaways DATE:
                                                        Beach 31/08/2016
Surface elevation:    approx 20m AHD                             Drill type: Hand Auger
Logged by: Julie Schubert       Checked by:                      Drill method: Auger




                                                                                   Classification Symbol
                                                                   Graphical Log
                    Soil Description                                                                       Field Monitoring    Sample Interval




                                                     Depth (m)
Silty sand - light grey, slightly moist             0.0                            ZS


Sand - yellow/brown, slightly moist                 0.3                            S


Borehole Terminated - target depth                  0.6                            S




AA1384EFF
September 2016
JS/js

Page 20

                      APPENDIX


                       B


          SITE PHOTOGRAPHS




AA1384EFF
September 2016
JS/js


[OCR of page images]
 

APPENDIX

B

 

 

 

SITE PHOTOGRAPHS

 

Page 21

                                   Site Photographs
                          2 David Low Way, Castaways Beach
                                 As at 31 August 2016




P1 – Tank servicing proposed Lot 1.       P2 - Looking west toward BH1.




P3 – Tank servicing proposed Lot 2.       P4 – Tank servicing external facilities on
                                                proposed Lot 2.




AA1384EFF
September 2016
JS/js