2508-47877 SRA - Attachment 5 - Plans and docs referenced in SARA response
Attached to the e-mail SARA response with conditions - MCU25/0090 and OPW25/0136.
Plans and drawings: the text below has words only, no drawings.
Original PDF page 7, section 1. The text section number identifies this passage in the reader.
ingeniir
DETENTION TANK OUTLET DETAILS
Feature Size Height from base
Top of Tank Overflow As per manufacturer 2400mm
150mm diameter (open
Top Outlet 2100mm
to sky)
Middle Outlet 2|150mm diameter pipes 1550mm
Low Flow 50mm diameter 0mm
Table 2: Detention tank outlet details
6.2 Detention Results
The peak water elevation achieved in the tanks by the analysis was 2100mm so falls short of discharging via
the top of tank overflow/access point.
The detention tanks are proposed to discharge to pit (6|1) and then flow into the downstream bio-retention
basin within a DN375RCP where it will then be piped to Myall Street stormwater network by 2|375 RCP. Peak
discharge rates to (6|1) are estimated at 164L/s for a 1% AEP 5 min critical storm which improves the current
estimated discharge of 198L/s.
WHOLE OF SITE DETENTION SUMMARY
Pre-Development Post-Development
AEP 3 Duration Duration Performance
Q (m /s) Q (m3/s)
(min) (min)
63.20% 50.27 5 32.701 5 -17.569 (65%)
39.35% 66.831 5 42.835 5 -23.996 (64%)
18.14% 93.218 5 58.855 5 -34.363 (63%)
10% 112.591 5 70.556 5 -42.035 (63%)
5% 134.732 5 83.879 5 -50.853 (62%)
2% 172.157 5 120.057 5 -52.1 (70%)
1% 198.512 5 163.788 5 -34.724 (83%)
1% 2100 238.215 5 215.074 5 -23.141 (90%)
Table 3: Comparison of pre and post development discharges
As demonstrated in Table 3, the proposed detention system successfully mitigates stormwater discharge to
pit (1|6) to achieve non worsening for the site stormwater discharge an maintain capacity in the downstream
stormwater infrastructure.
7. FLOODING
The site is in an elevated position locally and regionally and is not known to have any flood risk. A review of
the Noosa City Councils online mapping (accessed 24/07/2025) indicates that the site is not affected by any
known flood studies. Refer 3 for an excerpt of the site report.
Ingeniir Pty Ltd | 251502-SMP-01
ABN: 99 642 485 363 | PO Box 988 Maroochydore QLD 4558 | [email protected] | 0404157187
Page 10 | 16