Log in to see the plans as drawnEN 858-1:2002 (E) Annex A (normative) Analysis of effluent samples A.1 General Samples shall be analysed for their hydrocarbon content using infrared spectroscopy in accordance with A.2 or gas chromatography in accordance with A.3. In case of dispute, the infrared spectroscopy method is the reference method. A.2 Infrared spectroscopy method A.2.1 Extraction and preparation of the extract An effluent sample of approximately 500 ml is weighed into a separating funnel with a rated volume of 1000 mi, directly from the sampling device (see Figure A.1). Within 15 min of sampling the pH shall be set to between 1 and 2 using sulphuric acid (H2SO,) and 50 ml of 1.1.2-trichloro-1.2.2-trifluroethane (C2CI3F3) shall be added. It is then immediately shaken, with a frequency of 3 Hz to 4 Hz for 10 min and the phases allowed to settle for 30 min. Alternatively, tetrachloroethylene (C2Cl,) (IR grade) may be used as the extraction solvent. Key 1 Adding trichloro-trifluroethane up to the rated volume Figure A.1 Filling-up with trichloro-trifluroethane This is a licensed reproduction produced by SAI Global Ltd, an authorized distributor of British Standards 35
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalVery large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.