230324 - RECOR Site Inspection Record - Bartlett Rd Existing Masonry Wall

of 2

Page text shows just the words. Original shows the document exactly as it was published.

                                                        SITE INSPECTION RECORD                                                                    Page 1 of 2


  CLIENT / CONTRACTOR: Old Sea Dog Pty Ltd

  PROJECT / SITE: 9 Bartlett Road, Noosaville Qld

  JOB No: 20210212                                        INSPECTION DATE: 24/03/2023                              TIME: 11:00am

  INSPECTION REQUESTED BY: Michael Klobas                                                                           WEATHER: Fine

  REASON(S) FOR INSPECTION: Inspect existing masonry wall at rear of site


      The following are observations and recommendations from the inspection of the existing masonry wall on the
      rear boundary of the site:

            1. The wall had been partially demolished at the sides, exposing the core which was unreinforced
               besides a bond beam at the top of the wall.
            2. The wall was about 4m high.
            3. There were several cracks within the wall.
            4. The wall had previously been braced at the top by the existing storage units which had been
               demolished at the time of inspection, leaving the wall unpropped.
            5. It is in our opinion that the wall is no longer structural adequate to supported itself and lateral loads
               from wind and earthquake loading.
            6. We recommend that the wall is demolished and replaced with a timber fence.




  Inspected by:             Josh Overell                                                   Received by:           Michael Klobas

  Signed:                                                                                                Issued via:
                                                                                           Email ☒                          In person ☐



  Notes:
      1.    Site safety remains the responsibility of the principal contractor / contractor.
      2.    This site inspection record does not relieve the contractor of their responsibility to comply with the documentation and specifications.
      3.    Should this report constitute a variation to the contract, the contractor is NOT to proceed with work until a variation order is approved.
      4.    Commencement of work included in this report signifies the contractor’s acceptance that the work does not constitute a variation to the contract.
      5.    No extensions of time shall result from this report without approval.




P +61 7 5211 1003              A 75 Noosa Drive, Noosa Heads Qld 4567                  E [email protected]                         recorconsulting.com
Log in to download the original file

230324 - RECOR Site Inspection Record - Bartlett Rd Existing Masonry Wall.pdf · 598 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.